Code
Description
Range
160
GP021
Modulate back when delta temperature is large then
this treshold
5 °C - 25 °C
25
GP024
Valve Proofing System check on / off
0 = No
1 = Yes
0
PP015
Central heating pump post run time
1 Min - 99 Min
1
PP016
Maximum central heating pump speed (%)
20 % - 100 %
100
PP018
Minimum central heating pump speed (%)
20 % - 100 %
20
PP023
Hysteresis to start burner in heating mode
1 °C - 25 °C
10
9.3
Reading out measured values
9.3.1
Reading out counters
You can read out the counters of the appliance and the connected control
boards, sensors and so on.
1. Navigate to the Counter menu.
2. Press the
key to open the menu.
3. Press the
key to confirm the selection.
The text CODE flashes in the display.
4. Press the
key to confirm the selection.
5. Keep pressing the key until the code 0012 is displayed.
6. Keep pressing the key until the required value is displayed.
7. Press the
h
key multiple times to go back to the main display.
9.3.2
Reading out signals and software versions
You can read out the signals and software versions of the appliance and
the connected control boards, sensors and so on.
1. Navigate to the Information menu.
2. Press the
key to open the menu.
Fig.69
Step 2
MW-3000320-01
Fig.70
Step 3
MW-3000422-01
Fig.71
Step 4
MW-3000453-01
Fig.72
Step 5
MW-3000439-01
Fig.73
Step 6
MW-3000439-01
Fig.74
Step 7
MW-3000441-01
Fig.75
Step 2
MW-3000306-01
9 Settings
7625116 - v.06 - 17102018