12 Troubleshooting
12.1 Error codes
The boiler is fitted with an electronic regulation and control unit. The heart
of the control is a e-Smart microprocessor, which controls and also
protects the boiler. In the event of an error, a corresponding code is
displayed.
Error codes are displayed at three different levels:
Warning (A00.00)
Important
The boiler continues to operate but the cause of the warning must
be investigated. A warning can change into a blocking or lock-out.
Blocking (H00.00)
Important
The boiler starts up again automatically when the cause of the
blocking has been rectified. A blocking can become a lock-out.
Lock out (E00.00)
Important
The boiler starts up again only when the cause of the lock-out has
been rectified and reset manually.
The meaning of the code can be found in the various error code tables.
Make a note of the code displayed.
Important
The error code is needed to find the cause of the error quickly and
correctly and for any support from Remeha.
12.1.1 Warning - FSB-WHB-HE-150-300
Tab.42 Warning codes
Code
Description
Solution
A01.21
Maximum Dhw Temperature Gradient Level3
Exceeded
Temperature warning:
Check the flow.
A02.06
Water Pressure Warning active
Water pressure warning:
Water pressure too low; check the water pressure
A02.18
Object Dictionary Error
Configuration error:
Reset CN1 and CN2
See
The data plate for the CN1 and CN2 val
ues.
A02.37
Uncritical device has been disconnected
SCB PCB not found:
Bad connection: check the wiring and connectors
Faulty SCB PCB: Replace SCB PCB
A02.45
Full Can Connection Matrix
SCB PCB not found:
Carry out an auto-detect
A02.46
Full Can Device Administration
SCB PCB not found:
Carry out an auto-detect