Code
Display text Description
Adjustment range
Subme
nu
285
355
430
500
575
650
AP091
Outside
Sens.
Source
Type of outside sensor
connection to be used
0 = Auto
1 = Wired sensor
2 = Wireless sen
sor
3 = Internet meas
ured
4 = None
Outdoor
tempera
ture
0
0
0
0
0
0
AP098
BL1 contact
config.
BL1 input contact configu
ration
0 = Open
1 = Closed
2 = Off
Gas
fired ap
pliance
1
1
1
1
1
1
CP000
MaxZoneT
FlowSet
point
Maximum Flow Tempera
ture setpoint zone
7 - 100 °C
Direct
zone
80
80
80
80
80
80
CP020
Zone Func
tion
Functionality of the zone
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Tempera
ture
5 = Fan Convector
6 = DHW tank
7 = Electrical DHW
8 = Time Program
9 = ProcessHeat
10 = DHW Layered
11 = DHW Internal
tank
12 = DHW Com
mercial Tank
13 = DHW FWS
31 = DHW FWS
EXT
200 = BSB
254 = Occupied
Zone
manager
Zone
disabled
Direct
zone
1
1
1
1
1
1
CP040
Postrun
zone pump
Pump post runtime of the
zone
0 - 20 Min
Direct
zone
0
0
0
0
0
0
CP060
RoomT.
Holiday
Wished room zone tem
perature on holiday period
5 - 20 °C
Direct
zone
6
6
6
6
6
6
CP070
MaxRedu
ce
dRoomT.Li
m
Max Room Temperature
limit of the circuit in re
duced mode, that allows
switching to comfort mode
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP210
Zone HCZP
Comfort
Comfort footpoint of the
temperature of heat curve
of the circuit
15 - 90 °C
Direct
zone
15
15
15
15
15
15
CP220
Zone HCZP
Reduced
Reduced footpoint of the
temperature of heat curve
of the circuit
15 - 90 °C
Direct
zone
15
15
15
15
15
15
CP230
Zone Heat
ing Curve
Heating curve temperature
gradient of the zone
0 - 4
Direct
zone
1.5
1.5
1.5
1.5
1.5
1.5
CP240
ZoneRoo
mUnitInfl
Adjustment of the influ
ence of the zone room unit
0 - 10
Direct
zone
3
3
3
3
3
3
CP250
CalSon
deAmbZone
Calibration of Zone Room
Unit
-5 - 5 °C
Direct
zone
0
0
0
0
0
0
CP340
TypeRedu
cedNight
Mode
Type of reduced night
mode, stop or maintain
heating of circuit
0 = Stop heat de
mand
1 = Continue heat
demand
Direct
zone
0
0
0
0
0
0
CP470
Zone screed
drying
Setting of the screed dry
ing program of the zone
0 - 30 Days
Direct
zone
0
0
0
0
0
0
8 Settings
56
7734324 - v.03 - 29092020