Code
Display text Description
Adjustment range
Subme
nu
570
710
860
1000 1150 1300
AP102
Boiler Pump
function
Configuration of the boiler
pump as zone pump or
system pump (feed low
loss header)
0 = No
1 = Yes
Gas
fired ap
pliance
0
0
0
0
0
0
CP010
Tflow set
point zone
Zone flow temperature
setpoint, used when the
zone is set to a fixed flow
setpoint.
7 - 100 °C
Direct
zone
90
90
90
90
90
90
CP290
ConfigZone
PumpOut
Configuration of Zone
Pump Output
0 = Zone output
1 = CH mode
2 = DHW mode
3 = Cooling mode
4 = Error report
5 = Burning
6 = Service flag
7 = System error
8 = DHW looping
9 = Primary pump
10 = Buffer pump
Zone
disabled
Direct
zone
0
0
0
0
0
0
CP520
Zone Power
setpoint
Power setpoint per zone
0 - 100 %
Direct
zone
100
100
100
100
100
100
CP530
Zone PWM
Pump
speed
Pulse Width Modulation
pump speed per zone
20 - 100 %
Direct
zone
100
100
100
100
100
100
CP680
ConfPairing
RU Zone
Select the Bus channel of
the room unit for this zone
0 - 255
Direct
zone
0
0
0
0
0
0
DP003
Abs. max
fan DHW
Maximum fan speed on
Domestic Hot Water
1000 - 7000 Rpm
Gas
fired ap
pliance
5200 5500 3500 3800 4300 4100
DP010
Hysteresis
DHW
Temperature hysteresis
for the heat generator to
start on domestic hot wa
ter production
1 - 10 °C
Gas
fired ap
pliance
5.5
5.5
5.5
5.5
5.5
5.5
DP011
Stop offset
DHW
Temperature offset to stop
heat generator on domes
tic hot water production
0 - 100 °C
Gas
fired ap
pliance
5
5
5
5
5
5
DP020
Postrun
DHW
pump/3wv
Post run time of the DHW
pump/3 way valve after
DHW production
0 - 99 Sec
Gas
fired ap
pliance
10
10
10
10
10
10
DP140
DHW load
type
DHW load type (0 : Combi,
1 : Solo)
0 = Combi
1 = Solo
2 = Layered cylin
der
3 = Process heat
4 = External
Gas
fired ap
pliance
1
1
1
1
1
1
GP010
GPS Check Gas Pressure Switch
check on/off
0 = No
1 = Yes
Gas
fired ap
pliance
1
1
1
1
1
1
GP017
Max power
Maximum power percent
age in kilo Watt
0 - 1000 kW
Gas
fired ap
pliance
294.
2
351.
2
425.
6
494.
7
564.
4
642
GP022
Tfa Filter
Tau
Tau factor for average flow
temperature calculation
0 - 255
Gas
fired ap
pliance
1
1
1
1
1
1
GP042
Fan RPM
Max
Maximum fan speed
0 - 65535 Rpm
GVC
Pneu
matic
5700 5800 3700 4000 4500 4300
GP050
Power Min
Minimum power in kilo
Watt for RT2012 calcula
tion
0 - 300 kW
Gas
fired ap
pliance
80
111
142
141
170
180
8 Settings
7734324 - v.03 - 29092020
65