Code
Display text Description
Adjustment range
Subme
nu
570
710
860
1000 1150 1300
AP010
Service noti
fication
Select the type of service
notification
0 = None
1 = Custom notifi
cation
2 = ABC notifica
tion
Gas
fired ap
pliance
0
0
0
0
0
0
AP011
Service
hours mains
Hours powered to raise a
service notification
100 - 25500 Hours Gas
fired ap
pliance
8750 8750 8750 8750 8750 8750
AP056
Outdoor
sensor
Enable outdoor sensor
0 = No outside sen
sor
1 = AF60
2 = QAC34
Outdoor
tempera
ture
0
0
0
0
0
0
AP063
Max CH
flow setpoint
Maximum central heating
flow temperature setpoint
20 - 90 °C
Produc
er Ge
neric
Gas
fired ap
pliance
90
90
90
90
90
90
AP073
Summer
Winter
Outdoor temperature: up
per limit for heating
15 - 30.5 °C
Outdoor
tempera
ture
22
22
22
22
22
22
AP079
Building In
ertia
Inertia of the building used
for heat up speed
0 - 10
Outdoor
tempera
ture
3
3
3
3
3
3
AP080
Frost min
out temp
Outside temperature be
low which the antifreeze
protection is activated
-30 - 20 °C
Outdoor
tempera
ture
-10
-10
-10
-10
-10
-10
AP091
Outside
Sens.
Source
Type of outside sensor
connection to be used
0 = Auto
1 = Wired sensor
2 = Wireless sen
sor
3 = Internet meas
ured
4 = None
Outdoor
tempera
ture
0
0
0
0
0
0
AP098
BL1 contact
config.
BL1 input contact configu
ration
0 = Open
1 = Closed
2 = Off
Gas
fired ap
pliance
1
1
1
1
1
1
CP000
MaxZoneT
FlowSet
point
Maximum Flow Tempera
ture setpoint zone
7 - 100 °C
Direct
zone
80
80
80
80
80
80
CP020
Zone Func
tion
Functionality of the zone
0 = Disable
1 = Direct
2 = Mixing Circuit
3 = Swimming pool
4 = High Tempera
ture
5 = Fan Convector
6 = DHW tank
7 = Electrical DHW
8 = Time Program
9 = ProcessHeat
10 = DHW Layered
11 = DHW Internal
tank
12 = DHW Com
mercial Tank
13 = DHW FWS
31 = DHW FWS
EXT
200 = BSB
254 = Occupied
Zone
manager
Zone
disabled
Direct
zone
1
1
1
1
1
1
8 Settings
62
7734324 - v.03 - 29092020