Error
code
Description
Probable causes
Checking / solution
e[04
e[05
Temperature of heat
exchanger too low
Exchanger temperature
too high
4
Bad connection
4
Sensor fault
4
Sensor not or badly
connected
4
No circulation
4
Check the wiring
4
Replace the sensor if necessary
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Check the cleanliness of the heat exchanger
e[06
Return temperature
sensor short circuited
4
Bad connection
4
Sensor fault
4
Sensor not or badly
connected
4
Check the wiring
4
Check that the sensor has been correctly fitted
4
Check that the sensors are operating correctly
e[07
Return temperature
sensor open circuit
4
Bad connection
4
Sensor fault
4
Sensor not or badly
connected
4
Check the wiring
4
Check that the sensor has been correctly fitted
4
Check that the sensors are operating correctly
e[08
e[09
Return temperature too
low
Return temperature too
high
4
Bad connection
4
Sensor fault
4
Sensor not or badly
connected
4
No circulation
4
Check the wiring
4
Replace the sensor if necessary
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Check the cleanliness of the heat exchanger
e[10
e[11
Difference between the
flow and return
temperatures too great
4
Sensor fault
4
Sensor not or badly
connected
4
No circulation
4
Replace the sensor if necessary
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Check the cleanliness of the heat exchanger
4
Check that the heating pump is operating correctly
e[12
Temperature of heat
exchanger above normal
range (high-limit
thermostat STB)
4
Bad connection
4
Sensor fault
4
Sensor not or badly
connected
4
No circulation
4
Check the wiring
4
Replace the sensor if necessary
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check that the sensors are operating correctly
4
Check that the sensor has been correctly fitted
4
Check the cleanliness of the heat exchanger
8. Troubleshooting