Type
Execution
Description
C33
Closed
4
Exhaust of combustion gases above the roof.
4
The opening for the air-supply inlet is located in the same pressure zone as the vent (For
example, a concentric passage to the roof).
C43
(2)
Closed/Cascade
4
Common channelling for the air-supply and exhaust of combustion gases (CLV):
-
Concentric.
-
Eccentric; Air supply from the shaft.
4
This also relates to the overpressure cascades.
C53
Closed
4
Closed equipment.
4
Separate channelling for the air-supply.
4
Separate channelling for the combustion gases.
4
Terminating on different pressure surfaces.
C63
Closed
4
The manufacturer delivers this type of equipment without a supply or exhaust system.
C83
(3)
Closed
4
The equipment can be connected on a so-called semi-CLV system (with common combustion
gas exhaust).
C93
(4)
Closed
4
Channel for the air-supply and exhaust fumes in a duct or surrounded by a sleeve:
-
Concentric.
-
Eccentric; Air supply from the shaft.
-
Exhaust of combustion gases above the roof.
-
The opening for the air-supply inlet is located in the same pressure zone as the vent.
(1) Including the pressure classification P1
(2) EN483: 0,5 mbar suction by pressure reduction
(3) An under pressure of 4 mbar is possible
(4) See table for minimum sizes of duct or sleeving
Type Execution Diameter
Minimum size of the duct or jacket.
Without air-supply
With air-supply
∅
Channel
⃞
Channel
∅
Channel
⃞
Channel
C93 Rigid
60 mm
110 mm
110 x 110 mm
120 mm
110 x 110 mm
80 mm
130 mm
130 x 130 mm
140 mm
130 x 130 mm
100 mm
160 mm
160 x 160 mm
170 mm
160 x 160 mm
Flexible
60 mm
110 mm
110 x 110 mm
120 mm
110 x 110 mm
80 mm
130 mm
130 x 130 mm
145 mm
130 x 130 mm
100 mm
160 mm
160 x 160 mm
170 mm
160 x 160 mm
Concentric
60/100 mm
120 mm
120 x 120 mm
120 mm
120 x 120 mm
80/125 mm
145 mm
145 x 145 mm
145 mm
145 x 145 mm
100/150 mm
170 mm
170 x 170 mm
170 mm
170 x 170 mm
4.8.2.
Outlets
in general, it is possible to use a standard kit for passage via the roof
or outside wall. In the case of such passage via the outside wall
directly above the boiler, use the Remeha kit for passage via an
outside wall. This is available as an accessory.
For exhausting combustion gases of types C1, C3 and C5, it is
appropriate to use a
M&G Skyline / Mugro 3000
or a
Coxstand E
HR
. When exhausting combustion gases of type C6, the material of
the exhaust must conform with Gastec QA and/or be provided with
CE marking.
The exhaust vent for combustion gases must conform to EN
1856-1. The flue gas pipes must be calculated conforming to EN
13384 (parts 1 & 2).
Calenta 25s - 28c - 35s - 40c
4. Installation
040412 - 7600585-01