4.4
Positioning the boiler
The boiler is delivered with a mounting template.
A suspension clamp situated at the rear of the casing enables the
boiler to be directly suspended on the mounting bracket.
1. Position the mounting template to the wall with adhesive tape.
CAUTION
4
Using a spirit level, check that the mounting axis is
perfectly horizontal.
4
During mounting, cover up the connection points for
the air supply and the combustion gas exhaust, to
protect the boiler and its connections from dust. Only
remove this protection at the time when these
connections are made.
2. Drill 2 holes with a Ø of 10 mm.
Additional holes are provided in case one or other of the
standard locating holes prevents the correct location of the
plugs.
3. Insert the rawplugs with a Ø of 10 mm.
4. Attach the mounting bracket to the wall with the provided bolts with
a Ø of 10 mm.
5. Hang the boiler on the mounting bracket.
The relevant assembly instruction describes how to hang
the mounting frame (accessory).
T001540-A
2
1
5
4
3
Calenta 25s - 28c - 35s - 40c
4. Installation
040412 - 7600585-01
25