background image

Model F1-28 Upright Sprinkler 

SIN RA1321

Technical Specifications

Style: 

Upright

 Threads:

 1/2” NPT or ISO 7-R1/2

 Nominal K-Factor:

 2.8 (40 metric)

 Max. Working Pressure:

 175 psi (12 bar)

Material Specifications

Thermal Sensor: 

5.0mm Glass Bulb

Sprinkler Frame: 

Brass Alloy

Cap: 

Bronze Alloy

Sealing Washer: 

Nickel with PTFE

Load Screw: 

Copper Alloy

Deflector: 

Brass Alloy

Sprinkler Finishes 

(See Table B)

Sensitivity

Standard Response

Temperature Ratings

 135°F (57°C)
 155°F (68°C)
 175°F (79°C)
 200°F (93°C)
 286°F (141°C)
 360°F (182°C)
 500°F (260°C)

Guards & Shields (New Frames)

 F-1 Guard Kit
 F-3 Guard/Shield Kit

Guards & Shields (Legacy Frames)

 D-1 Guard

Sprinkler Wrench

 Model W2

 Model J (New frame with guard installed)
 Model JD (Legacy frame with guard installed)

Listings and Approvals

 cULus

Model F1-28 Upright Sprinkler Components and Dimensions 

Figure 1

Bulletin 066
May 2021

Page 2 of 6

www.reliablesprinkler.com

Summary of Contents for F1-28 Series

Page 1: ...tion on the following pages for specific listings for recessed installations and refer to Figure 3 for dimensional information When fitted with an approved water shield these sprinklers may considered intermediate sprinklers for use in racks below grated walkways and other areas where intermediate level sprinklers are required Table A provides a summary of the approvals and availability of specifi...

Page 2: ...ector Brass Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C 360 F 182 C 500 F 260 C Guards Shields New Frames F 1 Guard Kit F 3 Guard Shield Kit Guards Shields Legacy Frames D 1 Guard Sprinkler Wrench Model W2 Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and ...

Page 3: ... 79 C 200 F 93 C 286 F 141 C 360 F 182 C 500 F 260 C Recessed Escutcheons Model F1 Model F2 Model FP Guards Shields New Frames 2 F 7 Guard F 8 Guard Shield Kit Guards Shields Legacy Frames 2 D 1 Guard Sprinkler Wrenches Model W2 pendent Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus Notes 1 286 F 141 C and higher tem...

Page 4: ...Recessed Installation Pendent Sprinklers Figure 3 FP Escutcheon F1 Escutcheon F2 similar Bulletin 066 May 2021 Page 4 of 6 www reliablesprinkler com ...

Page 5: ...ated Black Paint Black Paint Off White Off White Chrome Dull Chrome Dull Notes 1 Other finishes and colors are available on special order Consult your Reliable sales representative for details 2 Paint or any other coating applied over the factory finish will void all approvals and warranties 3 The Model FP assembly consists of a sprinkler mounted in a galvanized steel cup with a finished trim ring...

Page 6: ...ion Upright Pendent Pendent FP Temperature Rating See sprinkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B Sprinkler Wrench Model W2 upright and pendent Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Note 286 F 141 C and higher temperature rated sprinklers are not listed to be...