background image

Model F1-28 Pendent Sprinkler

SIN RA1311

 

Technical Specifications

 Style:

 

Pendent 
Recessed Pendent

 Threads:

 1/2” NPT or ISO 7-R1/2

 Nominal K-Factor:

 2.8 (40 metric)

 Max. Working Pressure:

 175 psi (12 bar)

 

Material Specifications

 Thermal Sensor:

 5.0mm Glass Bulb

 Sprinkler Frame:

 Brass Alloy

 Cap:

 Bronze Alloy

 Sealing Washer:

 Nickel with PTFE

 Load Screw:

 Copper Alloy

 Deflector:

 Brass Alloy

 

Sprinkler Finishes 

(See Table B)

 

Sensitivity

Standard Response

 

 

Temperature Ratings

(1)

135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
360°F (182°C)
500°F (260°C)

Recessed Escutcheons

 Model F1
 Model F2
 Model FP

Guards & Shields (New Frames)

(2)

 F-7 Guard 
 F-8 Guard/Shield Kit

Guards & Shields (Legacy Frames)

(2)

 D-1 Guard

Sprinkler Wrenches

 Model W2 (pendent)
 Model W4 (recessed)

 Model J (New frame with guard installed)
 Model JD (Legacy frame with guard installed)

 

Listings and Approvals

 cULus

Notes: 

1. 

286°F (141°C) and higher temperature rated sprinklers not listed for recessed use.

2. 

Not suitable for recessed pendent installations.

Model F1-28 Pendent Sprinkler Components and Dimensions

Figure 2

Note: 

Please refer to Figure 3 for recessed installation.

Bulletin 066
May 2021

Page 3 of 6

www.reliablesprinkler.com

Summary of Contents for F1-28 Series

Page 1: ...tion on the following pages for specific listings for recessed installations and refer to Figure 3 for dimensional information When fitted with an approved water shield these sprinklers may considered intermediate sprinklers for use in racks below grated walkways and other areas where intermediate level sprinklers are required Table A provides a summary of the approvals and availability of specifi...

Page 2: ...ector Brass Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C 360 F 182 C 500 F 260 C Guards Shields New Frames F 1 Guard Kit F 3 Guard Shield Kit Guards Shields Legacy Frames D 1 Guard Sprinkler Wrench Model W2 Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and ...

Page 3: ... 79 C 200 F 93 C 286 F 141 C 360 F 182 C 500 F 260 C Recessed Escutcheons Model F1 Model F2 Model FP Guards Shields New Frames 2 F 7 Guard F 8 Guard Shield Kit Guards Shields Legacy Frames 2 D 1 Guard Sprinkler Wrenches Model W2 pendent Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus Notes 1 286 F 141 C and higher tem...

Page 4: ...Recessed Installation Pendent Sprinklers Figure 3 FP Escutcheon F1 Escutcheon F2 similar Bulletin 066 May 2021 Page 4 of 6 www reliablesprinkler com ...

Page 5: ...ated Black Paint Black Paint Off White Off White Chrome Dull Chrome Dull Notes 1 Other finishes and colors are available on special order Consult your Reliable sales representative for details 2 Paint or any other coating applied over the factory finish will void all approvals and warranties 3 The Model FP assembly consists of a sprinkler mounted in a galvanized steel cup with a finished trim ring...

Page 6: ...ion Upright Pendent Pendent FP Temperature Rating See sprinkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B Sprinkler Wrench Model W2 upright and pendent Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Note 286 F 141 C and higher temperature rated sprinklers are not listed to be...

Reviews: