Installation

Model F1 Series sprinklers must be installed in accordance with 
NFPA13 and the requirements of all applicable authorities having 
jurisdiction. Model F1 Series sprinklers must be installed with the 
Reliable sprinkler installation wrench identified in this Bulletin. Any 
other wrench may damage the sprinkler.  A leak tight sprinkler joint 
can be obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m). Do 
not tighten sprinklers over the maximum recommended installation 
torque. Exceeding the maximum recommended installation torque 
may cause leakage or impairment of the sprinkler.

Glass bulb sprinklers have orange bulb protectors or protective 
caps to minimize bulb damage during shipping, handling and 

installation. Reliable sprinkler installation wrenches are designed 

to install sprinklers with bulb protectors in place. Remove the bulb 
protector at the time when the sprinkler system is placed in service 
for fire protection. Removal of the bulb protector before this time 
may leave the bulb vulnerable to damage. Remove bulb protectors 
by undoing the clasp by hand. Do not use tools to remove bulb 

protectors.

Standard Finishes

Special Application Finishes

Sprinkler

F1, F2 and FP

(3)

Escutcheons

Sprinkler

F1, F2 and FP

(3)

Escutcheons

Bronze

Brass

Electroless Nickel PTFE

(4)

Bright Brass

Chrome Plated

Chrome Plated

Bright Brass

(5)

Black Plated

White Polyester

(4)

White Polyester

Black Plated

Black Paint

Black Paint

Off White

Off White

Chrome Dull

Chrome Dull

Notes:

1. 

Other finishes and colors are available on special order. Consult your Reliable sales representative for details.

2. 

Paint or any other coating applied over the factory finish will void all approvals and warranties.

3. 

The Model FP assembly consists of a sprinkler mounted in a galvanized steel cup with a finished trim ring or cover plate.

4. 

cULus Listed as corrosion resistant.

5. 

For 200°F (93°C) maximum temperature rated sprinklers only.

Finishes

(1)(2)

Table B

Maintenance

Reliable Model F1 series sprinklers should be inspected and the 

sprinkler system maintained in accordance with NFPA 25, as well 
as the requirements of any Authorities Having Jurisdiction.

Prior to installation, sprinklers should remain in the original 
cartons and packaging until used. This will minimize the potential 
for damage to sprinklers that could cause improper operation or 

non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or 
any other cleaning fluids. Remove dust by gentle vacuuming 

without touching the sprinkler.

Replace any sprinkler which has been painted (other than factory 

applied). A stock of spare sprinklers should be maintained to 
allow quick replacement of damaged or operated sprinklers.  
Failure to properly maintain sprinklers may result in inadvertent 
operation or non-operation during a fire event.

 Wrenches

Model W2 (upright, pendent)

Model J (New frame with guard installed)

Model W4 (recessed pendent)

Model JD (Legacy frame with guard installed)

Bulletin 066
May 2021

Page 5 of 6

www.reliablesprinkler.com

Summary of Contents for F1-28 Series

Page 1: ...tion on the following pages for specific listings for recessed installations and refer to Figure 3 for dimensional information When fitted with an approved water shield these sprinklers may considered intermediate sprinklers for use in racks below grated walkways and other areas where intermediate level sprinklers are required Table A provides a summary of the approvals and availability of specifi...

Page 2: ...ector Brass Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C 360 F 182 C 500 F 260 C Guards Shields New Frames F 1 Guard Kit F 3 Guard Shield Kit Guards Shields Legacy Frames D 1 Guard Sprinkler Wrench Model W2 Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and ...

Page 3: ... 79 C 200 F 93 C 286 F 141 C 360 F 182 C 500 F 260 C Recessed Escutcheons Model F1 Model F2 Model FP Guards Shields New Frames 2 F 7 Guard F 8 Guard Shield Kit Guards Shields Legacy Frames 2 D 1 Guard Sprinkler Wrenches Model W2 pendent Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus Notes 1 286 F 141 C and higher tem...

Page 4: ...Recessed Installation Pendent Sprinklers Figure 3 FP Escutcheon F1 Escutcheon F2 similar Bulletin 066 May 2021 Page 4 of 6 www reliablesprinkler com ...

Page 5: ...ated Black Paint Black Paint Off White Off White Chrome Dull Chrome Dull Notes 1 Other finishes and colors are available on special order Consult your Reliable sales representative for details 2 Paint or any other coating applied over the factory finish will void all approvals and warranties 3 The Model FP assembly consists of a sprinkler mounted in a galvanized steel cup with a finished trim ring...

Page 6: ...ion Upright Pendent Pendent FP Temperature Rating See sprinkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B Sprinkler Wrench Model W2 upright and pendent Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Note 286 F 141 C and higher temperature rated sprinklers are not listed to be...