background image

 

 

 

 

 

CONPROSYS 

 

 

Digital Input/Output Module 

CPS-MC341-DS1 -111 

Hardware Manual 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTEC CO.,LTD. 

Summary of Contents for CPS-MC341-DS1 -111

Page 1: ...CONPROSYS Digital Input Output Module CPS MC341 DS1 111 Hardware Manual CONTEC CO LTD ...

Page 2: ...To the customer Before using the product visit our website to check the firmware version and be certain to use the latest one ...

Page 3: ...icate 1 Serial number label 1 3pin Connector Power 1 5pin Connector RS 422A 485 1 10pin Connector Digital 2 This product was authenticates the standard with a power supply of our recommended Accordingly when you use other than power supply of our recommended doing so may become non standard Information about recommended power supply see the Contec s website Product Gide Warranty Certificate Produc...

Page 4: ... in this document is subject to change without notice All relevant issues have been considered in the preparation of this document Should you notice an omission or any questionable item in this document please feel free to notify CONTEC CO LTD Regardless of the foregoing statement CONTEC assumes no responsibility for any errors that may Trademarks This product is a registered trademark or trademar...

Page 5: ...e First Time 7 Switch Setup 7 RS 422A 485 Full duplex setup 9 Installation 10 Mounting on a DIN Rail 10 Wall Installation 12 Installation Conditions 13 How to set and remove the SD cover 16 Cable Connection 17 Power 17 LAN LAN A LAN B 17 RS 422A 485 COM A 18 Digital Input DI 21 Digital output DO 22 Software Setup 23 3 Component Name and Function 25 Component Name 25 Component Function 26 Power Con...

Page 6: ...put Connector DO0 DO1 DO2 DO3 DO4 DO5 DO6 DO7 30 Isolation Digital Input Connector DI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 31 Isolated RS 422A 485 Connector COM A 31 4 System Reference 33 Specification 33 Power Requirements 35 External dimensions CPS MC341 DS1 111 36 5 List of Option 37 Power supply 37 SD card 37 ...

Page 7: ...puting conditional branch and data output you can set the execution process and the process in the image that you write in the flowchart All operations are completed only by the operation of the Web browser Message Communication Function Using RS 422A RS 485 and Ethernet device TCP UDP the product can do message communication setting 10 links maximum The product can realize to send and receive mes...

Page 8: ... remove terminal connector without screwdriver in a short time even if this product is failure Because of DIN rail Installation it is easy to exchange the product Equipped LED for operation check The product has LED for operation check so that you can confirm communication Status of each interface visually Electrolytic capacitor and primary battery unused Because the product is not used an electro...

Page 9: ...charge only when this device is returned freight prepaid with a copy of the original invoice and a Return Merchandise Authorization to the distributor or the CONTEC group office from which it was purchased This warranty is not applicable for scratches or normal wear but only for the electronic circuitry and original products The warranty is not applicable if the device has been tampered with or da...

Page 10: ...or use incomplete mountings This may cause the device to fall Be sure to connect the product to the stipulated power supply voltage Connecting to a different voltage might cause a fire or electrical shock Do not use or store this product in a location exposed to high or low temperature that exceeds range of specification or susceptible to rapid temperature changes Example Exposure to direct sun In...

Page 11: ...hange without notice for enhancement and quality improvement Even when using this product continuously be sure to read the manual of CONTEC s website and understand the contents If you want to use in places where the influence of the overcurrent or overvoltage is please select appropriate surge protection device for all of the route Power line signal line earth etc Regardless of the foregoing stat...

Page 12: ...1 Before Using the Product 6 CPS MC341 DS1 111 Hardware Manual ...

Page 13: ...normality after turning on the power turn it off and check to see if the setup has been performed properly Switch Setup Switching Half duplex and full duplex is available by the setup switch for data transfer mode of this product Please set data transmission mode according to the external device connected with the product Please refer to Chapter 3 for more information on the switch position RS 422...

Page 14: ... 100Ω resistor as a terminator SW bit one is for TX To set the terminal to a resistor other than 100Ω set the terminator setting switch to OFF and insert an external terminator Half duplex Figure 2 1 Half duplex connection Party line connection Terminator 1 bit Terminator 1 bit A D C B 1 3 2 4 ON Insert the external terminator B or C 1 3 2 4 ON Insert the external terminator 1 3 2 4 ON Insert the ...

Page 15: ...r depending on the external device to which to connect this product This product contains a 100Ω resistor as a terminator Each bit corresponds to each signal line SW bit 1 is for TX and SW bit 2 is for RX To set the terminal to a resistor other than 100Ω set the terminator setting switch to OFF and insert an external terminator Full duplex Figure 2 2 Full duplex connection RxD TxD Terminator 1 bit...

Page 16: ...ng a slotted screwdriver to make it unlockable Figure2 3 Mounting on a DIN Rail 1 3 2 Hook the product from the upper part of the DIN rail and press the lower part on to the DIN rail Figure2 3 Mounting on a DIN Rail 2 3 3 Push the fixing hook up using a slotted screwdriver to make it lockable Figure2 3 Mounting on a DIN Rail 3 3 ...

Page 17: ...o unlock it Figure 2 4 Removing the unit from the DIN Rail 1 3 2 With the fixing hook unlocked pull the lower part of this unit toward you Figure 2 4 Removing the unit from the DIN Rail 2 3 3 By lifting this unit you can easily remove it from the DIN rail Figure 2 4 Removing the unit from the DIN Rail 3 3 ...

Page 18: ...2 Setup 12 CPS MC341 DS1 111 Hardware Manual Wall Installation To mount the product on the wall purchase the commercially available screw fitting for Φ3 5 separately Figure 2 5 Wall Installation ...

Page 19: ...hin the range of installation environment conditions such as keeping the system unit well ventilated and sufficiently spaced its surroundings DIN rail fixation Vertical installation Installation angle 0 Figure 2 6 DIN rail fixation Screws fixation Vertical installation Installation angle 0 Figure 2 7 Screws fixation Be sure that the ambient temperature is within the range specified in the installa...

Page 20: ...he measurement points exceed the specified temperature Note that even though the ambient temperature is within the specified range an operational malfunction may occur if there is other device generating high heat the radiation will influence the product to increase its temperature Do not install this product into the fully sealed space except the case in which the internal temperature is adjustab...

Page 21: ...2 Setup CPS MC341 DS1 111 Hardware Manual 15 Spacing between the system unit and any surrounding objects reference Figure 2 8 Spacing between the system unit and any surrounding objects reference ...

Page 22: ... at tip of the arrow 1 2 Slide the SD cover in the direction of the arrow 2 3 Drive a SD cover screw SD cover screw Pan head screw M2 6 5 Tightening torque 3 5 kgFcm Figure 2 9 Setting the SD Cover Figure 2 10 After setting the SD Cover How to remove Procedure of How to set is reversed to that of How to remove 1 Remove a SD cover screw 2 Slide the SD cover opposite the direction of the arrow 2 and...

Page 23: ...nfiguration is designed to operate at least 15W power supply In addition the power supply must satisfy the following requirements Build up time time of up to a voltage 12V within 2ms 30ms Recommended power supply is CPS PWD 15AW12 01 CONTEC If the maximum output current of the external power supply can not afford compared with the maximum current consumption of this product the abnormal operation ...

Page 24: ...gth which is shown on the following table because attenuation may be different by the material of the cable The following table does not guarantee communication speed with the cable length Table 2 3 Estimated cable length and the communication speed Cable Length m Communication speed bps 300 115 200 600 57 600 900 19 200 1 200 9 600 The baud rate that you can set with this product is the following...

Page 25: ...ctively so that each becomes a pair of twisted pair wire Figure 2 12 RS 422A 485 Full Duplex Communication Notice of the shield connection Please ground Shield to the frame ground FG of the external device Shield is not used as the signal ground SG If there is no terminal and place for ground please use an unshielded cable Do not ground to Power GND Shielded cable is not done correctly wiring grou...

Page 26: ... 422A 485 according to the specifications of the external device Communication with the external device of Half Duplex Communication with the external device of Full Duplex Figure 2 13 Wiring Specifications TX TX RX RX SG SG External Device TX TX RX RX SG RX RX TX TX SG External Device ...

Page 27: ...ate of a device which can be current driven as digital value The signal input unit is Photocoupler isolated input Corresponded to current sink output Figure 2 14 Digita Input Circuit Examples of Connecting the Product to an External Device Figure 2 15 Connecting the input to the sink type output Vcc Vcc 12V External device Input pin Opto coupler Switch Switch Input pin Opto coupler Minus common Th...

Page 28: ...y current ON OFF of the device to be controlled by the current drive is controlled by digital value The rated of output current is up to 100mA per point Figure 2 16 Digital Output Circuit When the power is turned on all output will be OFF Vcc 12V External device This Product External power supply 12 24VDC Output pin Minus Load Zener diode Output pin Load Zener diode common Opto coupler Opto couple...

Page 29: ...tput Acceptable Input Software Setup See the CPS MC341 System Setup Guide for details Output pin LED 5 1kΩ Minus Common When 1 is output to a relevant bit the corresponding LED comes on When 0 is output to the bit in contrast the LED gose out External power supply 12 24 VDC This Product External power supply 12 24VDC Output sink type Minus Common External Device This Product Input plus Input Compa...

Page 30: ...2 Setup 24 CPS MC341 DS1 111 Hardware Manual ...

Page 31: ...reset this product 7 Shut Down Switch It shut down this product 8 LAN It is a Connector for LAN 9 Digital Output DO It uses the attached 10pin connector 10 Digital Input DI It uses the attached 10pin connector 11 RS 422A 485 It uses the attached 5pin connector DO7 DO6 DO5 DO4 DO3 DO2 DO1 DO0 DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0 DO 7 6 5 4 3 2 1 0 N C MCOM LANA V V FG Link Act Speed PWR ST1 ST2 TX RX CO...

Page 32: ...ower Connector 12 24VDC It uses the attached connector Connector type PHOENIX CONTACT MC 1 5 3 ST 3 5 Equivalent product Table 3 1 Power Connector Pin No Signal name 1 FG 2 V GND 3 V 12 24VDC Debug Connector Please do not use it SD slot Insert the SD card and use to store such data 1 2 3 ...

Page 33: ...transmission of the RS 422A 485 OFF It put the lights out at the time of not transmission of the RS 422A 485 COM A RX Yellow Blinking It blinks at the time of reception of the RS 422A 485 OFF It put the lights out at the not reception of the RS 422A 485 DO1 DO7 Yellow ON It will light if there is output OFF It will put the lights out if there is not output DI0 DI7 Yellow ON It will light if there ...

Page 34: ...ys 3 System Reservation Please be OFF always 2 System Reservation Please be OFF always 1 ON RTS Communication Mode Half Duplex OFF RTS Communication Mode Full Duplex SW2 4 ON Internal connection state of TX and RX Short Half Duplex OFF Internal connection state of TX and RX Open Full Duplex 3 ON Internal connection state of TX and RX Short Half Duplex OFF Internal connection state of TX and RX Ope...

Page 35: ...ed data Input 7 N C Not connected 8 N C Not connected Table 3 5 LED Indicator Side LAN ports LED Operatio n Meaning Speed Orange ON Indicate that LAN port is connected by 100Mbps OFF Indicate that LAN port is connected by 10Mbps or a non connection state Link Act Green ON Indicate that LAN port is a connection state Blinking Indicate that LAN port transmits and receives data with connected externa...

Page 36: ...O1 DO2 DO3 DO4 DO5 DO6 DO7 This product has 8 channel of digital output It uses the attached connector Connector type PTR MESSTECHNIK AK1550 10 3 5 GREEN Equivalent product Table 3 6 Digital Output Connector Pin No Signal Name 1 N C 2 DO7 3 DO6 4 DO5 5 DO4 6 DO3 7 DO2 8 DO1 9 DO0 10 MCOM 1 2 3 4 5 6 7 8 9 10 ...

Page 37: ...5 GREEN Equivalent product Table 3 7 Digital Input Connector Pin No Signal Name 1 N C 2 DI7 3 DI6 4 DI5 5 DI4 6 DI3 7 DI2 8 DI1 9 DI0 10 MCOM Isolated RS 422A 485 Connector COM A This product has 1port of RS 422A 485 communication It uses the attached communication connector Connector type PTR MESSTECHNIK AK1550 5 3 5 GREEN Equivalent product Table 3 8 Communication Connector Pin No Signal Name 1 ...

Page 38: ...3 Component Name and Function 32 CPS MC341 DS1 111 Hardware Manual ...

Page 39: ...ion element SG FG gas discharge tube arrester Discharge voltage 300V impulse current tolerance 2000A 8 20us 10 times SD Card slot Standard SD standard follow Connector SD Memory Card slot LED Read Write Yellow Digital Input Input type Non voltage input negative logic 1 Isolation Photocoupler Isolation 1000V Open circuit Impedance 10kΩ or more Short circuit Impedance 500Ω or less Input Resistance 3...

Page 40: ...ires a mounting screws on the market Table 4 2 Installation Environment Requirements Item CPS MC341 DS1 111 Operating non operating ambient Temperature 20 to 60 C Operating non operating ambient Humidity 10 to 90 RH No condensation Floating dust particles Not to be excessive Corrosive gases None Noise resistance Line noise AC Line 2kV 4 Signal Line 1kV IEC61000 4 4 Level 3 EN61000 4 4 Level 3 Stat...

Page 41: ...Power supply cable and the input and output signal lines are avoid absolutely bundle wire proximity and parallel wiring If lightning serge measures is required please connect surge protective device SPD Please consult separately the ground of this product and the ground of surge protective device SPD Please select the ones which do not exceed the maximum allowable circuit voltage of surge protecti...

Page 42: ...1 DO0 DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0 DO 7 6 5 4 3 2 1 0 N C MCOM LAN A V V FG Link Act Speed PWR ST1 ST2 TX RX COMA 12 24VDC SG RX RX TX TX COM A RESET SW1 SD LAN B Link Act Speed Isolated RS 422A 485 SHUT SD SW2 DOWN TERM Half Full 4 3 2 1 4 3 2 1 MODE Half Full 6 5 4 3 2 1 4 3 2 1 6 5 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 ON OFF SW2 SW1 DI 7 6 5 4 3 2 1 0 N C MCOM CPS MC341 DS1 Φ3 5 154 55 ...

Page 43: ...t of Option CPS MC341 DS1 111 Hardware Manual 37 5 List of Option Power supply CPS PWD 15AW12 01 Power supply 15 w SD card SD 2GB B SD card 2GB Information about the option products see the Contec s website ...

Page 44: ... 555 0025 Japan Japanese http www contec co jp English http www contec com Chinese http www contec com cn No part of this document may be copied or reproduced in any form by any means without prior written consent of CONTEC CO LTD 09252015 09252015 Management No NA04457 Parts No LYTE201 ...

Reviews: