INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Pulse output module ...........................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.
 

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

HOT SWAPPABLE MODULES

• Replacing the module does not affect other modules on 

the same base.  Thus, the module can be replaced while 
the power is ON.  However, replacing multiple modules 
at once may greatly change live voltage levels.  We highly 
recommend to replace them one by one.

 

GENERAL PRECAUTIONS

• DO NOT set the switches on the module while the power 

is supplied.  The switches are used only for maintenance 
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

Use the Installation Base (model: R3-BSx).

PULSE OUTPUT MODULE

(open collector output, 16 points)

MODEL

R3-PC16A

Summary of Contents for R3-PC16A

Page 1: ...y HOT SWAPPABLE MODULES Replacing the module does not affect other modules on the same base Thus the module can be replaced while the power is ON However replacing multiple modules at once may greatly change live voltage levels We highly recommend to replace them one by one GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintena...

Page 2: ...reen in normal operating conditions Output status indicator Red LED turns on with the output ON SIDE DIP SW Factory setting ON OFF Pulse Width SW1 1 through 1 6 ON OFF PULSE WIDTH TIME 1 1 2 3 4 5 6 OFF OFF OFF OFF OFF OFF 5 msec ON OFF OFF ON OFF OFF 10 msec OFF ON OFF OFF ON OFF 50 msec ON ON OFF ON ON OFF 100 msec OFF OFF ON OFF OFF ON 500 msec ON OFF ON ON OFF ON 1 sec OFF ON ON OFF ON ON 1 5 ...

Page 3: ...RNAL BUS B For dual redundant communication BUS CONNECTOR 1 18 Po 1 Po 16 17 Po 15 16 Po 14 15 Po 13 14 Po 12 13 Po 11 12 Po 10 11 Po 9 8 Po 8 7 Po 7 6 Po 6 5 Po 5 4 Po 4 3 Po 3 2 Po 2 1 19 9 10 20 24V DC L L L L L L L L 24V DC 24V DC L L L L L L L L COM COM WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Sp...

Page 4: ... 2 Present value 9000 and target value 500 it out puts 1500 pulses E g 3 Present value 1000 and target value 3001 it does not outputs any pulse present value 3001 When the totalized pulse upper limit is initial setting 10000 MANUAL COUNT RESET 1 Remove Network Module or its cables and interrupt com munication with other devices 2 Turn ON the Count Reset SW SW3 1 3 Return the module to the base and...

Reviews: