8
Sentinel Kinetic Advance S, SX - www.regulus.eu
Flow Rate settings
The Sentinel Kinetic Advance has four (4) user defined speeds in addition to the non-adjustable Maximum
speed.
User defined speeds can be assigned a Mode name from the list below. (some options may not be available
in your region)
- Low
- Normal (Unit default operating mode)
- Boost
- Purge
- Holiday
- Night time
- Party
- Unoccupied
- Over pressure
- Fireplace
Note: The flow rate for each mode is set independently and not defined by the mode name.
When setting up Over Pressure or Fireplace Mode, the supply rate must be set higher than extract rate. This
is to provide a positive internal pressure in the dwelling to assist with the initial expulsion of combustion
products from the fireplace via the flue.
Fireplace mode does not prevent under-pressure
Mechanical Ventilation with Heat Recovery (MVHR) systems are not designed to provide combustion air.
NOTE: It is the responsibility of the open-flued appliance installer to ensure conformance with the current
local building regulations for fuel burning appliances.