Sentinel Kinetic Advance S, SX - www.regulus.eu
Internal RH Trip
The integral humidity sensor increases airflow speed
in proportion to relative humidity levels. The sensor
also reacts to small but rapid increases in humidity,
even if the normal trigger threshold is not reached.
The night time relative humidity setback feature
suppresses nuisance tripping as humidity gradually
increases with falling temperature.
Go to Mode
Scroll through the settings using the
buttons and select the required Go To mode.
Internal RH Setpoint
Adjust the internal Relative Humidity using the
buttons. Selectable range is 60% - 90%.
Internal RH sensing can be switched off by selecting
“OFF”, this option is above 90%, or below 60%.
CONTROL MODE
Select whether the unit should operate in Normal or
Constant Volume mode.
/
-
&