background image

13

6.5  MODULE 5 - S

ERIAL

C

OMMUNICATIONS

P

ARAMETERS

(

5-SEriAL

PARAMETER MENU

DATA BIT

ABBREVIATED PRINTING 

PRINT OPTIONS

PARITY BIT

METER ADDRESS

The Serial Communications Parameters are only accessible when an

optional RS232 or RS485 serial communications module is installed in the
meter.

This section replaces the bulletin shipped with the RS232 and RS485 serial

communications plug-in cards. Discard the separate bulletin when using those
serial plug-in cards with the CUB5B and CUB5R.

BAUD RATE 

Set the baud rate to match that of other serial communications equipment.

Normally, the baud rate is set to the highest value that all of the serial
communications equipment is capable of transmitting and receiving.

Select either 7- or 8-bit data word length. Set the word length to match the

other serial communications equipment on the serial link.

This parameter only appears when the Data Bit parameter is set to a 7-bit

data word length. Set the parity bit to match that of the other serial equipment
on the serial link. The meter ignores parity when receiving data and sets the
parity bit for outgoing data. If parity is set to 

NO

, an additional stop bit is used

to force the frame size to 10 bits.

Enter the serial node address. With a single unit, an address is not needed

and a value of zero can be used (RS232 applications). Otherwise, with multiple
bussed units, a unique address number must be assigned to each meter. The
node address applies specifically to RS485 applications.

This parameter determines the formatting of data transmitted from the meter

in response to a Transmit Value command or a Block Print Request. Select 

NO

for a full print transmission, consisting of the meter address, mnemonics, and
parameter data. Select 

YES

for abbreviated print transmissions, consisting of the

parameter data only. This setting is applied to all the parameters selected in the
PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent
during a full transmission.) 

This parameter selects the meter values transmitted in response to a Print

Request. A print request is also referred to as a block print because more than
one parameter can be sent to a printer or computer as a block.

Selecting 

YES

displays a sublist for choosing the meter parameters to appear

in the print block. All active parameters entered as 

YES

in the sublist will be

transmitted during a block print. Parameters entered as 

NO

will not be sent.

The “Print All” (

Prnt ALL

) option selects all meter values for transmitting

(

YES

), without having to individually select each parameter in the sublist.

Note: Inactive parameters will not be sent regardless of the print option

setting. For example, Counter B or Scale Factor B will only be sent if Counter
B is enabled (Dual Counter mode or batch count). Likewise, the Setpoint
value(s) will not be sent unless an optional setpoint card is installed in the
meter.

"

#

9600

bAUd

"

#

7-bit

dAtA

"

#

Odd

PAritY

"

#

00

Addr

"

#

NO

Abbr

"

#

NO

Prnt OPt

to

99

9600

4800

38400

19200

2400

600

1200

300

8-bit

7-bit

EVEN

Odd

NO

YES

NO

YES

NO

Scale Factor B

Scale Factor A

FACTORY

SETTING

DESCRIPTION

CLD

SP2

SP1

NO

NO

NO

Setpoint 2

Setpoint 1

CntA Ld

SP2

sSP1

SFB

NO

Cntb ScF

SFA

NO

CntA ScF

RTE

NO

Rate Value

rAtE

CTB

NO

Counter B

Count b

CTA

YES

Counter A

Count A

MNEMONIC

DISPLAY

Counter A Count Load

Summary of Contents for CUB5B

Page 1: ...Setpoint capability is field installable with the addition of the single setpoint relay output module or the dual setpoint solid state output module Serial communications capability for RS232 or RS48...

Page 2: ...ature 35 to 85 C Operating and Storage Humidity 0 to 85 max relative humidity non condensing Vibration According to IEC 68 2 6 Operational 5 to 500 Hz in X Y Z direction for 1 5 hours 5 g s Shock Acco...

Page 3: ...se widths to 10 msec To access the switches remove the rear cover of the meter as described below A bank of 4 switches is located in the upper right hand corner After setting the switches install any...

Page 4: ...pplications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter 4 Signal or Control cables within an enclosu...

Page 5: ...erators Etc Input A Two Wire Proximity Current Source Input A Magnetic Pickup Input A Current Sourcing Output Input A Interfacing With TTL Input A Current Sinking Output Input A Switch or Isolated Tra...

Page 6: ...move to the next parameter PROGRAMMING MODE EXIT SEL KEY The Programming Mode is exited by pressing the SEL key with Pro NO displayed This will commit any stored parameter changes to memory and return...

Page 7: ...is value if Reset to Count Load action is selected 9999999 to 99999999 00000500 CmtA Ld COUNTER B BATCH COUNT ENABLE The Counter B batch count function internally counts the number of output activatio...

Page 8: ...y reset of the selected counter s Change backlight color with each activation backlight version only Inhibit Maintained Reset Freeze display of selected counter s while allowing counts to accumulate i...

Page 9: ...a pulse every 2 seconds RATE HIGH UPDATE TIME 0 2 to 99 9 seconds 01 0 LO Udt 02 0 HI Udt SCALING FOR RATE INDICATION To scale the rate enter a Scaling Display value with a corresponding Scaling Input...

Page 10: ...are only active when Counter B is enabled Dual Count mode or batch counter FRONT PANEL COUNTER RESET ENABLE RST The yES selection allows the display to automatically scroll through the enabled displa...

Page 11: ...Setpoint Action not applicable for Counter B Assignment Select the Setpoint Output to be programmed starting with Setpoint 1 The n in the following parameters reflects the chosen Setpoint number After...

Page 12: ...vated Reverse rEV turns the output off when activated and on when deactivated NOr SPn OUt SETPOINT ANNUNCIATOR Normal NOr displays the setpoint annunciator when the corresponding output is on Reverse...

Page 13: ...om the meter in response to a Transmit Value command or a Block Print Request Select NO for a full print transmission consisting of the meter address mnemonics and parameter data Select YES for abbrev...

Page 14: ...es not issue a reply to value change commands follow with a transmit value command for readback verification Receiving Data From The Meter Data is transmitted from the meter in response to either a tr...

Page 15: ...o take place The figures list the data formats employed by the meter Start Bit and Data Bits Data transmission always begins with the start bit The start bit signals the receiving device to prepare fo...

Page 16: ...16 CUB5 PROGRAMMING QUICK OVERVIEW Press and hold SEL key to enter Programming Mode...

Reviews: