The Security Code determines the programming mode and the accessibility

of programming parameters. This code can be used along with the Program
Mode Lock-out (

Pro Loc

) in the User Input Function parameter (Module 1).

Two programming modes are available. Full Programming mode allows all

parameters to be viewed and modified. Quick Programming mode permits only
the setpoint output time-out and counter load values (when applicable) to be
modified, but allows direct access to these values without having to enter Full
Programming mode.

Programming a Security Code other than 0, requires this code to be entered

at the 

Pro CodE

prompt in order to access Full Programming mode. Depending

on the code value, Quick Programming may be accessible before the 

Pro CodE

prompt appears (see chart).

PROGRAMMING SECURITY CODE

The 

yES

selection will return the meter to the factory default settings. The

meter will display 

rESEt

and then return to 

Pro

, at which time all settings have

been changed.

LOAD FACTORY DEFAULT SETTINGS

to

999

yES

NO

"

#

000

Pro CodE

"

#

MO

FACt SEt

* Entering Code 222 allows access regardless of security code.

The 

yES

selection allows the 

SEL

button to toggle through the enabled

displays.

FRONT PANEL DISPLAY SELECT ENABLE (SEL)

The 

yES

selection allows the 

RST

button to reset the selected counter(s). The

shaded selections are only active when Counter B is enabled (Dual Count mode
or batch counter).

FRONT PANEL COUNTER RESET ENABLE (RST)

The 

yES

selection allows the display to automatically scroll through the

enabled displays. Each display is shown for 4 seconds.

DISPLAY SCROLL ENABLE

NO

yES

Count b

both A-b

dSPLAy

yES 

NO

NO

Count A

NO

yES

"

#

yES

SEL Enb

"

#

YES

RSt Enb

"

#

NO

d-ScroLL

Enter the desired display color, red or green. This parameter is active for

backlight units only.

DISPLAY COLOR (BACKLIGHT UNIT ONLY)

6rn

rEd

"

#

rEd

d-COLOr

Enter the desired Display Intensity Level (1-5). The display will actively dim

or brighten as levels are changed. This parameter is active for backlight units only.

DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)

"

#

5

d-LEVEL

to

5

Select 

YES

to momentarily display the meter software version before advancing

to the next parameter. The software version is also displayed at power-up. 

SOFTWARE VERSION DISPLAY

"

#

NO

CodE UEr

6.3  MODULE 3 - D

ISPLAY AND

F

RONT

P

ANEL

K

EY

P

ARAMETERS

(

3-dSPLAY

)

PARAMETER MENU

NO

yES

Immediate Access

Full Programming

0-999

Not Active

With correct code entry

at 

Pro CodE

prompt *

Pro CodE

prompt

100-999

Pro Loc

No Access

Quick

Programming

1-99

Active

No Access

Programming

Lock

0

With correct code entry

at 

Pro CodE

prompt *

Pro CodE

prompt

100-999

After Quick Programming

with correct code entry 

at 

Pro CodE

prompt *

Quick

Programming

1-99

______

not 

Pro Loc

Immediate Access

Full Programming

0

FULL PROGRAMMING

MODE ACCESS

MODE WHEN “SEL”

KEY IS PRESSED

SECURITY

CODE

USER INPUT

STATE

USER INPUT

FUNCTION

Summary of Contents for CUB5B

Page 1: ...Setpoint capability is field installable with the addition of the single setpoint relay output module or the dual setpoint solid state output module Serial communications capability for RS232 or RS48...

Page 2: ...ature 35 to 85 C Operating and Storage Humidity 0 to 85 max relative humidity non condensing Vibration According to IEC 68 2 6 Operational 5 to 500 Hz in X Y Z direction for 1 5 hours 5 g s Shock Acco...

Page 3: ...se widths to 10 msec To access the switches remove the rear cover of the meter as described below A bank of 4 switches is located in the upper right hand corner After setting the switches install any...

Page 4: ...pplications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter 4 Signal or Control cables within an enclosu...

Page 5: ...erators Etc Input A Two Wire Proximity Current Source Input A Magnetic Pickup Input A Current Sourcing Output Input A Interfacing With TTL Input A Current Sinking Output Input A Switch or Isolated Tra...

Page 6: ...move to the next parameter PROGRAMMING MODE EXIT SEL KEY The Programming Mode is exited by pressing the SEL key with Pro NO displayed This will commit any stored parameter changes to memory and return...

Page 7: ...is value if Reset to Count Load action is selected 9999999 to 99999999 00000500 CmtA Ld COUNTER B BATCH COUNT ENABLE The Counter B batch count function internally counts the number of output activatio...

Page 8: ...y reset of the selected counter s Change backlight color with each activation backlight version only Inhibit Maintained Reset Freeze display of selected counter s while allowing counts to accumulate i...

Page 9: ...a pulse every 2 seconds RATE HIGH UPDATE TIME 0 2 to 99 9 seconds 01 0 LO Udt 02 0 HI Udt SCALING FOR RATE INDICATION To scale the rate enter a Scaling Display value with a corresponding Scaling Input...

Page 10: ...are only active when Counter B is enabled Dual Count mode or batch counter FRONT PANEL COUNTER RESET ENABLE RST The yES selection allows the display to automatically scroll through the enabled displa...

Page 11: ...Setpoint Action not applicable for Counter B Assignment Select the Setpoint Output to be programmed starting with Setpoint 1 The n in the following parameters reflects the chosen Setpoint number After...

Page 12: ...vated Reverse rEV turns the output off when activated and on when deactivated NOr SPn OUt SETPOINT ANNUNCIATOR Normal NOr displays the setpoint annunciator when the corresponding output is on Reverse...

Page 13: ...om the meter in response to a Transmit Value command or a Block Print Request Select NO for a full print transmission consisting of the meter address mnemonics and parameter data Select YES for abbrev...

Page 14: ...es not issue a reply to value change commands follow with a transmit value command for readback verification Receiving Data From The Meter Data is transmitted from the meter in response to either a tr...

Page 15: ...o take place The figures list the data formats employed by the meter Start Bit and Data Bits Data transmission always begins with the start bit The start bit signals the receiving device to prepare fo...

Page 16: ...16 CUB5 PROGRAMMING QUICK OVERVIEW Press and hold SEL key to enter Programming Mode...

Reviews: