background image

8

6.2  MODULE 2 - R

ATE

S

ETUP

P

ARAMETERS

(

2-rAtE

)

PARAMETER MENU

RATE ENABLE

Module 2 is the programming for the rate parameters. For maximum input

frequency, Rate Enable should be set to 

NO

when not in use. When set to 

NO

, the

remaining rate parameters are not accessible. The rate value is shown with an
annunciator of “

R

” in the Display Mode.

This selects the decimal point position for the rate display and any setpoint

value assigned to rate. This parameter does not affect rate scaling calculations.

RATE DECIMAL POINT

0.00000

0.000

0.0

0.0000

0.00

0

RATE SCALING INPUT VALUE

RATE SCALING DISPLAY VALUE

Enter the desired Rate Display Value for the Scaling Point.*

Enter the corresponding Rate Input Value for the Scaling Point.*

to

999999

0.1 

to

99999.9

*For value entry instructions, refer to selection/value entry in the Programming

The Meter section.

USER INPUT ASSIGNMENT

The User Input Assignment is only active when Counter B is enabled and the

User Input performs a Reset, Inhibit or Store function on one or both counters.

USER INPUT FUNCTION

MODE

DISPLAY

No Function

NO

DESCRIPTION

User Input disabled.

Program Mode Lock-out

Pro Loc

rESEt

Inhibit

Inhibit counting for the selected counter(s).

Store

StorE

Store and Reset

Stor-rSt

Display Select *

d-SELECt

d-LEVEL

Increase intensity one level for each
activation. (backlight version only)

rESEt-12

rESEt-2

rESEt-1

Prnt-r5t

Print

d-COLOr

Advance once for each activation

both A-b

Count b

Count A

See Programming Mode Access chart.
(Module 3)

Setpoint 1 and 2 Reset *

Setpoint 2 Reset *

Setpoint 1 Reset *

Print and Reset *

Print Request

Backlight Color *

Edge triggered reset of the selected
counter(s) after storing the count.

"

#

NO

USEr INP

"

#

Count A

USEr ASN

"

#

YES

RAtE Enb

"

#

001000

RAtE dSP

"

#

O

RAtE dP

"

#

01000.0

RAtE INP

YES

NO

Reset Setpoint 1 and 2 outputs

Reset Setpoint 2 output

Reset Setpoint 1 output

Same as Print Request followed by a
momentary reset of the selected counter(s).

Change backlight color with each activation
(backlight version only)

Inhibit

Maintained Reset

Freeze display of selected counter(s) while
allowing counts to accumulate internally.

Display Intensity Level *

Serial transmit of the active parameters
selected in the Print Options (Module 5)

SCALING FOR COUNT INDICATION

The CUB5’s scale factor is factory set to 1, to provide one count on the

display for each pulse that is input to the unit. In many applications, there will
not be a one-to-one correspondence between input pulses and display units.
Therefore, it is necessary for the CUB5 to scale or multiply the input pulses by
a scale factor to achieve the desired display units (feet, meters, gallons, etc.)

The Count Scale Factor Value can range from 00.0001 to 99.9999. It is

important to note that the precision of a counter application cannot be improved
by using a scale factor greater than one. To accomplish greater precision, more
pulse information must be generated per measuring unit. The following formula
is used to calculate the scale factor.

Scale Factor  = Desired Display Units x  Decimal Point Position

Number of Pulses

WHERE:

Desired Display Units

: Count display units acquired after pulses that occurred.

Number of Pulses

: Number of pulses required to achieve the desired

display units.

Decimal Point Position

0

=

1

0.0

=

10

0.00

=

100

0.000

=

1000

0.0000

=

10000

0.00000

=

100000

EXAMPLE

:  The counter display is used to indicate the total number of feet

used in a process. It is necessary to know the number of pulses for the desired
units to be displayed. The decimal point is selected to show the resolution in
hundredths.

Scale Factor  = Desired Display Units x  Decimal Point Position

Number of Pulses

Given that 128 pulses are equal to 1 foot, display total feet with a one-

hundredth resolution. 

Scale Factor  = 1.00 x  100

128

Scale Factor  =  0.007812  x  100
Scale Factor =  0.7812

Level active reset of the selected counter(s).

Note: * indicates Edge Triggered function. Other functions are Level Active

(maintained)

YES

0

100

100.0

0.1

0.2

Press 'SEL' 
to display 
'R' on CUB5

Summary of Contents for CUB5B

Page 1: ...Setpoint capability is field installable with the addition of the single setpoint relay output module or the dual setpoint solid state output module Serial communications capability for RS232 or RS48...

Page 2: ...ature 35 to 85 C Operating and Storage Humidity 0 to 85 max relative humidity non condensing Vibration According to IEC 68 2 6 Operational 5 to 500 Hz in X Y Z direction for 1 5 hours 5 g s Shock Acco...

Page 3: ...se widths to 10 msec To access the switches remove the rear cover of the meter as described below A bank of 4 switches is located in the upper right hand corner After setting the switches install any...

Page 4: ...pplications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter 4 Signal or Control cables within an enclosu...

Page 5: ...erators Etc Input A Two Wire Proximity Current Source Input A Magnetic Pickup Input A Current Sourcing Output Input A Interfacing With TTL Input A Current Sinking Output Input A Switch or Isolated Tra...

Page 6: ...move to the next parameter PROGRAMMING MODE EXIT SEL KEY The Programming Mode is exited by pressing the SEL key with Pro NO displayed This will commit any stored parameter changes to memory and return...

Page 7: ...is value if Reset to Count Load action is selected 9999999 to 99999999 00000500 CmtA Ld COUNTER B BATCH COUNT ENABLE The Counter B batch count function internally counts the number of output activatio...

Page 8: ...y reset of the selected counter s Change backlight color with each activation backlight version only Inhibit Maintained Reset Freeze display of selected counter s while allowing counts to accumulate i...

Page 9: ...a pulse every 2 seconds RATE HIGH UPDATE TIME 0 2 to 99 9 seconds 01 0 LO Udt 02 0 HI Udt SCALING FOR RATE INDICATION To scale the rate enter a Scaling Display value with a corresponding Scaling Input...

Page 10: ...are only active when Counter B is enabled Dual Count mode or batch counter FRONT PANEL COUNTER RESET ENABLE RST The yES selection allows the display to automatically scroll through the enabled displa...

Page 11: ...Setpoint Action not applicable for Counter B Assignment Select the Setpoint Output to be programmed starting with Setpoint 1 The n in the following parameters reflects the chosen Setpoint number After...

Page 12: ...vated Reverse rEV turns the output off when activated and on when deactivated NOr SPn OUt SETPOINT ANNUNCIATOR Normal NOr displays the setpoint annunciator when the corresponding output is on Reverse...

Page 13: ...om the meter in response to a Transmit Value command or a Block Print Request Select NO for a full print transmission consisting of the meter address mnemonics and parameter data Select YES for abbrev...

Page 14: ...es not issue a reply to value change commands follow with a transmit value command for readback verification Receiving Data From The Meter Data is transmitted from the meter in response to either a tr...

Page 15: ...o take place The figures list the data formats employed by the meter Start Bit and Data Bits Data transmission always begins with the start bit The start bit signals the receiving device to prepare fo...

Page 16: ...16 CUB5 PROGRAMMING QUICK OVERVIEW Press and hold SEL key to enter Programming Mode...

Reviews: