background image

3

1.0 I

NSTALLING THE

M

ETER

INSTALLATION 

The meter meets NEMA 4X/IP65 requirements when properly installed. The

unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch
from the unit. Slide the panel gasket over the rear
of the unit to the back of the bezel. The unit
should be installed fully assembled. Insert
the unit into the panel cutout. 

While holding the unit in place, push the panel latch over the rear of the unit

so that the tabs of the panel latch engage in the slots on the case. The panel latch
should be engaged in the farthest forward slot possible. To achieve a proper seal,
tighten the latch screws evenly until the unit is snug in the panel (Torque to
approx. 28 to 36 in-oz [0.202 to 0.26 N-m]). Do not over-tighten the screws.

INSTALLATION ENVIRONMENT

The unit should be installed in a location that does not exceed the operating

temperature and provides good air circulation. Placing the unit near devices that
generate excessive heat should be avoided.

The bezel should only be cleaned with a soft cloth and neutral soap product.

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the

keypad of the unit.

2.0 S

ETTING THE

DIP S

WITCHES

SETTING THE INPUT DIP SWITCHES

The meter has four DIP switches for Input A and

Input B that must be set before applying power. 

SWITCH 1

LOGIC

: Input A trigger levels V

IL

= 1.25 V max.;

V

IH

= 2.75 V min.; V

MAX

= 28 VDC

MAG

: 200 mV peak input sensitivity; 100 mV

hysteresis; maximum input voltage: 

±

40 V peak 

(28 Vrms); Must also have SRC switch ON. 
(Not recommended with counting applications.)

SWITCH 2

SNK.

: Adds internal 7.8 K

pull-up resistor to +9 to

28 VDC, I

MAX

= 3.8 mA.

SRC.

: Adds internal 3.9 K

pull-down resistor, 

7.2 mA max. @ 28 VDC max.

SWITCHES 3 and 4

HI Frequency

: Removes damping capacitor and allows max. frequency. 

LO Frequency

: Adds a damping capacitor for switch contact bounce. Limits

input frequency to 50 Hz and input pulse widths to 10 msec.

To access the switches, remove the rear cover of the meter as described

below. A bank of 4 switches is located in the upper right hand corner. After
setting the switches, install any optional plug-in cards before replacing the rear
cover (see next section).

Warning

: Exposed line voltage exists on the circuit boards.

Remove all power to the meter and load circuits before accessing
inside of the meter.

REMOVING THE REAR COVER

To remove the rear cover, locate the cover locking tab below the 2nd and 3rd

input terminals. To release the tab, insert a small, flat blade screwdriver between
the tab and the plastic wall below the terminals. Inserting the screwdriver will
provide enough pressure to release the tab locks. To replace the cover, align the
cover with the input terminals and press down until the cover snaps into place.

4

3

2

1

ON

Input B  LO Freq.

Input 

A

  LO Freq.

Input 

A

  SRC.

Input 

A

  MAG.

HI Freq.

HI Freq.

SNK.

Logic

Factory Setting

O

PTIONAL

P

LUG

-

IN

C

ARDS

ADDING OPTION CARDS

The CUB5 meters can be fitted with optional output cards and/or serial

communications cards. The details for the plug-in cards can be reviewed in the
specification section below. The plug-in cards, that are sold separately, can be
installed initially or at a later date.

WARNING: Disconnect all power to the unit before

installing Plug-in card.

SINGLE RELAY OUTPUT CARD (One setpoint only)

Type

: Single FORM-C relay

Isolation To Sensor & User Input Commons

: 1400 Vrms for 1 min.

Working Voltage: 150 Vrms

Contact Rating

: 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive

Life Expectancy

: 100,000 minimum operations

Response Time

:

Turn On Time: 4 msec max.
Turn Off Time: 4 msec max.

DUAL SINKING OUTPUT CARD (One or two setpoints)

Type

: Non-isolated switched DC, N Channel open drain MOSFET

Current Rating

: 100 mA max. 

V

DS ON

: 0.7 V @ 100 mA

V

DS MAX

: 30 VDC

Offstate Leakage Current

: 0.5 mA max.

RS485 SERIAL COMMUNICATIONS CARD

Type

: RS485 multi-point balanced interface (non-isolated)

Baud Rate

: 300 to 38.4k

Data Format

: 7/8 bits; odd, even, or no parity

Bus Address

: 0 to 99; max 32 meters per line

Transmit Delay

: Selectable, 2 msec min. or 50 msec min.

RS232 SERIAL COMMUNICATIONS CARD

Type

: RS232 half duplex (non-isolated)

Baud Rate

: 300 to 38.4k

Data Format

: 7/8 bits; odd, even, or no parity

Summary of Contents for CUB5B

Page 1: ...Setpoint capability is field installable with the addition of the single setpoint relay output module or the dual setpoint solid state output module Serial communications capability for RS232 or RS48...

Page 2: ...ature 35 to 85 C Operating and Storage Humidity 0 to 85 max relative humidity non condensing Vibration According to IEC 68 2 6 Operational 5 to 500 Hz in X Y Z direction for 1 5 hours 5 g s Shock Acco...

Page 3: ...se widths to 10 msec To access the switches remove the rear cover of the meter as described below A bank of 4 switches is located in the upper right hand corner After setting the switches install any...

Page 4: ...pplications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter 4 Signal or Control cables within an enclosu...

Page 5: ...erators Etc Input A Two Wire Proximity Current Source Input A Magnetic Pickup Input A Current Sourcing Output Input A Interfacing With TTL Input A Current Sinking Output Input A Switch or Isolated Tra...

Page 6: ...move to the next parameter PROGRAMMING MODE EXIT SEL KEY The Programming Mode is exited by pressing the SEL key with Pro NO displayed This will commit any stored parameter changes to memory and return...

Page 7: ...is value if Reset to Count Load action is selected 9999999 to 99999999 00000500 CmtA Ld COUNTER B BATCH COUNT ENABLE The Counter B batch count function internally counts the number of output activatio...

Page 8: ...y reset of the selected counter s Change backlight color with each activation backlight version only Inhibit Maintained Reset Freeze display of selected counter s while allowing counts to accumulate i...

Page 9: ...a pulse every 2 seconds RATE HIGH UPDATE TIME 0 2 to 99 9 seconds 01 0 LO Udt 02 0 HI Udt SCALING FOR RATE INDICATION To scale the rate enter a Scaling Display value with a corresponding Scaling Input...

Page 10: ...are only active when Counter B is enabled Dual Count mode or batch counter FRONT PANEL COUNTER RESET ENABLE RST The yES selection allows the display to automatically scroll through the enabled displa...

Page 11: ...Setpoint Action not applicable for Counter B Assignment Select the Setpoint Output to be programmed starting with Setpoint 1 The n in the following parameters reflects the chosen Setpoint number After...

Page 12: ...vated Reverse rEV turns the output off when activated and on when deactivated NOr SPn OUt SETPOINT ANNUNCIATOR Normal NOr displays the setpoint annunciator when the corresponding output is on Reverse...

Page 13: ...om the meter in response to a Transmit Value command or a Block Print Request Select NO for a full print transmission consisting of the meter address mnemonics and parameter data Select YES for abbrev...

Page 14: ...es not issue a reply to value change commands follow with a transmit value command for readback verification Receiving Data From The Meter Data is transmitted from the meter in response to either a tr...

Page 15: ...o take place The figures list the data formats employed by the meter Start Bit and Data Bits Data transmission always begins with the start bit The start bit signals the receiving device to prepare fo...

Page 16: ...16 CUB5 PROGRAMMING QUICK OVERVIEW Press and hold SEL key to enter Programming Mode...