background image

1. 

DISPLAY

: 8 digit LCD 0.46" (11.7 mm) high digits

CUB5R000

: Reflective LCD with full viewing angle

CUB5B000

: Transmissive LCD with selectable red or green LED backlight,

viewing angle optimized. Display color change capability with output state
when using an output module.

2. 

POWER

: Input voltage range is +9 to +28 VDC with short circuit and input

polarity protection. Must use an RLC model MLPS1 or a Class 2 or SELV
rated power supply.

3. 

COUNTER DISPLAYS

:

Counter A

: 8-digits, enabled in all count modes

Display Range: -9999999 to 99999999
Overflow Indication: Display flashes “

Cnt OVEr

Counter B

: 7-digits, enabled in Dual Counter Mode or batch counting

Display Designator: “

b

” to the left side of the display

Display Range: 0 to 9999999 (positive count only)
Overflow Indication: Display flashes “

bCntOVEr

Maximum Count Rates

: 50% duty cycle

Without setpoint option card: 20 KHz (all count modes)
With setpoint option card: 20 KHz for any count mode except Dual Counter

(16 KHz), Quadrature x2 (14 KHz) and Quadrature x4 (13 KHz).

4. 

RATE DISPLAY

: 6-digits, may be enabled or disabled in any count mode 

Display Designator

: “

R

” to the left side of the display

Display Range

: 0 to 999999

Over Range Display

: “

R OLOLOL

Maximum Frequency

: 20 KHz

Minimum Frequency

: 0.01 Hz

Accuracy

: ±0.01%

5. 

COUNT/RATE SIGNAL INPUTS (INP A and INP B):

Input A

: DIP switch selectable to accept pulses from a variety of sources. 

See Section 2.0 Setting the DIP Switches for Input A specifications. 

Input B

: Logic signals only

Trigger levels: V

IL

= 1.0 V max; V

IH

= 2.4 V min; V

MAX

= 28 VDC

Current sinking: Internal 10K

pull-up resistor to +9 to 28 VDC

Filter (LO Freq.): Damping capacitor provided for switch contact bounce.

Limits input frequency to 50 Hz and input pulse widths to 10 msec min.

6. 

USER INPUT (USR):

Programmable input. Connect to input common (INP

COMM) to activate function. Internal 10K

pull-up resistor to +9 to 28 VDC.

Threshold Levels

: V

IL

= 1.0 V max; V

IH

= 2.4 V min; V

MAX

= 28 VDC 

Response Time

: 5 msec typ.; 50 msec debounce (activation and release)

7. 

MEMORY

: Nonvolatile E

2

PROM memory retains all programming

parameters and count values when power is removed.

8. 

CONNECTIONS

: Wire clamping screw terminals

Wire Strip Length

: 0.3" (7.5 mm)

Wire Gage

: 30-14 AWG copper wire

Torque

: 5 inch-lbs (0.565 N-m) max.

9. 

CONSTRUCTION

: This unit is rated for NEMA 4X/IP65 requirements for

indoor use. Installation Category I, Pollution Degree 2. High impact plastic
case with clear viewing window. Panel gasket and mounting clip included.

10

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range for CUB5R000

: -35 to 75°C

Operating Temperature Range for CUB5B000 depends on display color

and intensity level as per below

:

Storage Temperature

: -35 to 85°C

Operating and Storage Humidity

: 0 to 85% max. relative humidity (non-

condensing)

Vibration According to IEC 68-2-6

: Operational 5 to 500 Hz, in X, Y, Z

direction for 1.5 hours, 5 g’s.

Shock According to IEC 68-2-27

: Operational 40 g, 11 msec in 3 directions.

Altitude

: Up to 2000 meters

11.

CERTIFICATIONS AND COMPLIANCES

:

SAFETY

UL Recognized Component, File #E179259, UL61010A-1, CSA 22.2 No. 61010-1 

Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.

UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95

LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

Type 4X Indoor Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/9257C/UL

CB Scheme Test Report #E179259-V01-S02

Issued by Underwriters Laboratories, Inc.

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment

for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for
Measurement, Control and Laboratory use.

Notes:
1. Criterion A: Normal operation within specified limits.

Refer to EMC Installation Guidelines for additional information.

12. 

WEIGHT

: 3.2 oz (100 g)

2

G

ENERAL

M

ETER

S

PECIFICATIONS

O

RDERING

I

NFORMATION

TYPE

MODEL NO.

DESCRIPTION

PART NUMBER

CUB5

CUB5R

CUB5R000

CUB5B

CUB5B000

Optional Plug-in Cards

CUB5SNK

CUB5RLY

CUB5COM

RS232 Serial Communications Card

RS485 Serial Communications Card

Dual Sinking Open Collector Output card

Single Relay Option Card

CUB5COM2

CUB5COM1

CUB5SNK0

CUB5RLY0

Accessories

SFCRD

CBLPRO

CBPRO

MLPS1

Crimson 2 PC Configuration Software for Windows 98, ME, 2000, XP

*

Programming Cable RS232 (RJ11-DB9)
Programming Cable RS485 (RJ11-DB9)

Micro-Line Power Supply, 85 to 250 VAC

SFCRD200

CBLPROG0

CBPRO007

MLPS1000

Dual Counter & Rate Indicator with Reflective Display
Dual Counter & Rate Indicator with Backlight Display

MODEL

NO.

DISPLAY COLOR

INPUT CURRENT

@ 9 VDC WITHOUT

CUB5RLY0

CUB5R000

---

10 mA

30 mA

CUB5B000

Red (max intensity)

85 mA

115 mA

CUB5B000

Green (max intensity)

95 mA

125 mA

TEMPERATURE

1 & 2

-35 to 75°C

3

-35 to 70°C

4

-35 to 60°C

5

-35 to 50°C

1 & 2

-35 to 75°C

3

-35 to 65°C

5

4

-35 to 35°C

-35 to 50°C

INTENSITY LEVEL

Class A

EN 55011

Emissions

Emissions:

30 A/m 

3 V/rms 
Criterion A

Criterion A

EN 61000-4-8

EN 61000-4-6

RF conducted interference

1 kV L-L, 

Criterion A

EN 61000-4-5

Surge 

1 kV signal

2 kV power

Criterion A

EN 61000-4-4

Fast transients (burst)

2 kV L&N-E power

10 V/m

Criterion A

EN 61000-4-3

Electromagnetic RF fields

8 kV air discharge

4 kV contact discharge

Criterion A

EN 61000-4-2

Electrostatic discharge

Immunity to Industrial Locations:

Power frequency magnetic fields

Green Display

*Crimson 2 software is available for download from http://www.redlion.net/

Red Display

INPUT CURRENT

@ 9 VDC WITH

CUB5RLY0

Summary of Contents for CUB5B

Page 1: ...Setpoint capability is field installable with the addition of the single setpoint relay output module or the dual setpoint solid state output module Serial communications capability for RS232 or RS48...

Page 2: ...ature 35 to 85 C Operating and Storage Humidity 0 to 85 max relative humidity non condensing Vibration According to IEC 68 2 6 Operational 5 to 500 Hz in X Y Z direction for 1 5 hours 5 g s Shock Acco...

Page 3: ...se widths to 10 msec To access the switches remove the rear cover of the meter as described below A bank of 4 switches is located in the upper right hand corner After setting the switches install any...

Page 4: ...pplications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter 4 Signal or Control cables within an enclosu...

Page 5: ...erators Etc Input A Two Wire Proximity Current Source Input A Magnetic Pickup Input A Current Sourcing Output Input A Interfacing With TTL Input A Current Sinking Output Input A Switch or Isolated Tra...

Page 6: ...move to the next parameter PROGRAMMING MODE EXIT SEL KEY The Programming Mode is exited by pressing the SEL key with Pro NO displayed This will commit any stored parameter changes to memory and return...

Page 7: ...is value if Reset to Count Load action is selected 9999999 to 99999999 00000500 CmtA Ld COUNTER B BATCH COUNT ENABLE The Counter B batch count function internally counts the number of output activatio...

Page 8: ...y reset of the selected counter s Change backlight color with each activation backlight version only Inhibit Maintained Reset Freeze display of selected counter s while allowing counts to accumulate i...

Page 9: ...a pulse every 2 seconds RATE HIGH UPDATE TIME 0 2 to 99 9 seconds 01 0 LO Udt 02 0 HI Udt SCALING FOR RATE INDICATION To scale the rate enter a Scaling Display value with a corresponding Scaling Input...

Page 10: ...are only active when Counter B is enabled Dual Count mode or batch counter FRONT PANEL COUNTER RESET ENABLE RST The yES selection allows the display to automatically scroll through the enabled displa...

Page 11: ...Setpoint Action not applicable for Counter B Assignment Select the Setpoint Output to be programmed starting with Setpoint 1 The n in the following parameters reflects the chosen Setpoint number After...

Page 12: ...vated Reverse rEV turns the output off when activated and on when deactivated NOr SPn OUt SETPOINT ANNUNCIATOR Normal NOr displays the setpoint annunciator when the corresponding output is on Reverse...

Page 13: ...om the meter in response to a Transmit Value command or a Block Print Request Select NO for a full print transmission consisting of the meter address mnemonics and parameter data Select YES for abbrev...

Page 14: ...es not issue a reply to value change commands follow with a transmit value command for readback verification Receiving Data From The Meter Data is transmitted from the meter in response to either a tr...

Page 15: ...o take place The figures list the data formats employed by the meter Start Bit and Data Bits Data transmission always begins with the start bit The start bit signals the receiving device to prepare fo...

Page 16: ...16 CUB5 PROGRAMMING QUICK OVERVIEW Press and hold SEL key to enter Programming Mode...

Reviews: