background image

6

INSTALLATION ENVIRONMENT

The  unit  should  be  installed  in  a  location  that  does  not

exceed  the  maximum  operating  temperature  and  provides
good  air  circulation.  Placing  the  unit  near  devices  that
generate excessive heat should be avoided.

Continuous exposure to direct sunlight may accelerate the

aging process of the bezel. The bezel should be cleaned only
with  a  soft  cloth  and  neutral  soap  product.  Do  NOT  use
solvents.

Do not use tools of any kind (screwdrivers, pens, pencils,

etc.) to operate the keypad of the unit.

INSTALLATION

The Lynx Counters meet NEMA 4X/IP65 requirements for

indoor use, when properly installed. These units are intended
to be mounted into an enclosed panel with a gasket to provide
a water-tight seal.

One mounting clip and two screws with nuts are provided for easy

installation.  Consideration  should  be  given  to  the  thickness  of  the
panel. A panel that is too thin, may distort and not provide a water-tight
seal. (Recommended minimum panel thickness is 0.125" [3.18 mm].)

After the panel cut-out has been completed and deburred, carefully slide

the  panel  gasket  over  the  rear  of  the  counter  body  to  the  back  of  the  bezel.
Insert  the  unit  into  the  panel.  As  depicted  in  the  drawing,  install  the  two
tinnerman nuts and two self-tapping screws onto the mounting clip. To install
the  mounting  clip;  hold  the  mounting  clip  with  both  hands  so  that  the  top
corners rest on the index finger of each hand and the bottom corners rest on the
middle  finger  of  each  hand.  While  doing  this,  place  the  thumb  of  each  hand
over the mounting screws. By pressing on the screws, flex the clip enough to
slide it over the back end of the Lynx case until the clip snaps into the groove
of the bezel. Tighten the two mounting screws.

Caution:  Only  minimum  pressure  is  required  to  seal  the  panel. 

Do 

NOT

overtighten mounting screws.

TROUBLESHOOTING

For further technical assistance, contact technical support at the appropriate company numbers listed.

Summary of Contents for CUB 1

Page 1: ...g pull down transition of count or reset signal 4 OPERATING TEMPERATURE RANGE 0 to 50 C 32 to 122 F 5 STORAGE TEMPERATURE RANGE 20 to 60 C 4 to 140 F NO WEAR NO NOISE The CUB s micro circuits can accu...

Page 2: ...increased to 250 Hz if de bounce is not needed LOW SPEED COUNT INPUT 50 Hz MAX For 250 Hz see note in text Moving the white wire to the H S CNT Input allows the CUB Counter to operate at speeds up to...

Page 3: ...CTIONS There are certain considerations that shoud be observed when running the count and control signal wires A length of wire can act like an antenna and the closer it is to a source of electrical n...

Page 4: ...PUTS Approval and Rating is voided if electronic sensors VCM s or other active elements are used Hazardous location rating also limits usage to approved batteries See Power Source Specifications Conne...

Page 5: ...lace Install batteries as shown below observing proper polarity Note Push battery spring clips to the left toward connector to completely free the batteries when removing or installing batteries Condu...

Page 6: ...IP65 requirements when properly installed Panel gasket and mounting clips included 8 WEIGHT 5 1 oz 145 g ELECTRICAL CONNECTIONS There are certain considerations that should be observed when running th...

Page 7: ...ce Module used for powering RLC sensors with CUB Counters has proper interface output for direct drive to H S CNT HIGH SPEED COUNT INPUT 5 KHz MAX Connecting the RST EN Reset Enable Input to Common ac...

Page 8: ...er will count UP on the falling edge of the Count Input when the Quad Input is low Counter will decrement on the rising edge of the Count Input when the Quad Input is low No count change will occur wh...

Page 9: ...g edge of the Count Input if the Quad Input is low The counter will decrement with every rising edge of the Count Input if the Quad Input is low When the Quad Input is high no change in count value wi...

Page 10: ...roperly installed Panel gasket and mounting clips included with unit 8 WEIGHT 5 1 oz 145 g ELECTRICAL CONNECTIONS There are certain considerations that should be observed when running the count and co...

Page 11: ...signals Motor starter contacts tungsten contacts and brush type contacts should NOT be used Normally open contacts are recommended for longer battery life and greater noise immunity LOW SPEED COUNT I...

Page 12: ...n only CUB 3R Remote Reset Only Switch Contact or Solid State Transistor Switch See Connections Contact burden 14 A Max OFF State leakage current must be less than 2 A Counter resets with negative pul...

Page 13: ...close proximity or if the installation is near a commercial radio transmitter 3 Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays tra...

Page 14: ...ontact or Solid State Transistor Switch See Connections Contact burden 14 A Max OFF State leakage current must be less than 2 A Counter resets with negative pulse on a min pulse width of 5 msec 4 COUN...

Page 15: ...it or raceway with AC power lines conductors feeding motors solenoids SCR controls and heaters etc The cables should be run in metal conduit that is properly grounded This is especially useful in appl...

Page 16: ...that remain closed for long periods of time will reduce battery life 3 BACKLIGHT POWER REQUIREMENTS 9 to 28 VDC 35 mA typical 50 mA max Above 26 VDC derate operating temperature to 50 C Must use the M...

Page 17: ...er to the EMC Installation Guidelines section of this bulletin for additional information 7 CONSTRUCTION This unit is rated for NEMA 4X IP65 indoor use Installation Category I Pollution Degree 2 8 WEI...

Page 18: ...t up to two 14 AWG wires Note The Reflective CUB4 will NOT have a screw terminal installed at the V terminal since it is NOT required for operation and is not internally connected Refer to the Orderin...

Page 19: ...or a backlit CUB4L8W measuring an AC input voltage the neutral of the single phase AC signal is connected to Terminal 1 COM and line hot is connected to Terminal 5 LS The DC supply for the backlightin...

Page 20: ...quipment may be impaired Do not use this unit to directly command motors valves or other actuators not equipped with safeguards To do so can be potentially harmful to persons or equipment in the event...

Page 21: ...BILITY Notes 1 Burst to DC backlight power had a power line filter installed RLC LFIL0000 or equivalent at the unit 2 Self recoverable loss of performance during EMI disturbance at 10 V rms to backlig...

Page 22: ...short cable runs Therefore keep cable runs as short as possible WIRING CONNECTIONS The electrical connections are made via screw clamp terminals located on the back of the unit All conductors should...

Page 23: ...Lion Controls 20 Willow Springs Circle York PA 17406 Tel 1 717 767 6511 Fax 1 717 764 0839 Red Lion Controls AP 31 Kaki Bukit Road 3 06 04 05 TechLink Singapore 417818 Tel 65 6744 6613 Fax 65 6743 336...

Page 24: ...d to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a manner not specified by the manufacturer the protection provided by th...

Page 25: ...max operating temperature to 40 C Must use the MLPS or a Class 2 or SELV rated power supply 4 SIGNAL INPUT LS terminal 4 See Count Edge under Programming for incrementing edge of input signal Contact...

Page 26: ...on Signal and Control cables as close to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line filters on the p...

Page 27: ...ted into an enclosed panel The viewing window and reset button are factory sealed for a washdown environment A sponge rubber gasket and mounting clip are provided for installing the unit in the panel...

Page 28: ...nt must be less than 2 A Note The RC protection circuit on the RST Input causes a delay of approximately 15 msec in Reset response L S INPUT CONTACT VERSIONS 30 Hz MAX Connecting the L S Input to Comm...

Page 29: ...wer supply The external supply is connected between the V and common terminals as shown in the drawing APPLICATION TOTAL YARDS OF MATERIAL A fabric manufacturer wants to know as economically as possib...

Page 30: ...7 This page intentionally left blank...

Page 31: ...based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalti...

Page 32: ...ovided by the equipment may be impaired Do not use this unit to directly command motors valves or other actuators not equipped with safeguards To do so can be potentially harmful to persons or equipme...

Page 33: ...ding motors solenoids SCR controls and heaters etc The cables should be run in metal conduit that is properly grounded This is especially useful in applications where cable runs are long and portable...

Page 34: ...the gasket Slide the panel gasket over the rear of the unit to the back of the bezel Insert the mounting screws onto both sides of mounting clip Tip of screw should NOT project from hole in mounting...

Page 35: ...65 6744 6613 Fax 65 6743 3360 Red Lion Controls BV Basicweg 11b NL 3821 BR Amersfoort Tel 31 0 334 723 225 Fax 31 0 334 893 793 LIMITED WARRANTY The Company warrants the products it manufactures again...

Page 36: ...Power Versions 115 VAC 10 50 60 Hz 0 5 VA 230 VAC 10 50 60 Hz 0 5 VA 10 to 28 VAC 10 50 60 Hz 2 5 VA D C Power Version 10 to 28 VDC 1 W 3 OUTPUT RELAY Type Form A Max Power 50 VA Max Voltage 250 VAC...

Page 37: ...reached the output relay closes for the amount of time programmed The counter will automatically reset to zero at the beginning of the timed output and continue to accumulate counts MODE 4 LATCH OUTPU...

Page 38: ...dering information CAUTION On 10 to 28 VAC version units the input common on the five position connector black wire is not isolated internally from the AC power connection When making connections exte...

Page 39: ...significant digit press the P button to enter the new value The unit automatically returns to the normal operating mode The new preset value is displayed and takes affect immediately In the Preset Va...

Page 40: ...not change the state until the button is released If testing of the relay is not desired press the P button to exit self test Note If the relay test is not performed the state of the relay will remai...

Page 41: ...od limited to one year from the date of shipment provided the products have been stored handled installed and used under proper conditions The Company s liability under this limited warranty shall ext...

Page 42: ...Button and Terminal Actuation Modes The second method is available to provide means to reset each count individually This method requires pressing two pushbuttons First press and hold the E button the...

Page 43: ...e 0 to 50 C Storage Temperature 40 to 70 C Operating and Storage Humidity 85 max relative humidity non condensing from 0 to 50 C Altitude Up to 2000 meters 14 WEIGHT 2 1 lbs 0 9 kg PROGRAMMABLE FUNCTI...

Page 44: ...sary in the same manner until the complete Preset or Scale Factor value is registered on the display Pressing the E pushbutton completes the entry sequence To interrogate the Batch Preset value Press...

Page 45: ...d if using the serial communication capability of the GEMINI 3300 TYPICAL BATCH COUNTER APPLICATIONS Cont d CANDY BAR PACKAGING SYSTEM A typical batching application shown above requires two separate...

Page 46: ...5...

Page 47: ...6...

Page 48: ...7...

Page 49: ...based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalti...

Page 50: ...the use of DIP switches The Down Arrow Key will also function as a front panel display reset Once the front panel programming is complete the buttons can be disabled by a DIP switch setting The meter...

Page 51: ...mation 2 General Meter Specifications 3 Installing the Meter 3 Setting the Switches 4 Wiring the Meter 4 Reviewing the Front Buttons and Display 6 Scaling the Meter 6 Programming the Meter 7 TABLE OF...

Page 52: ...losure rating Rear of unit IEC 529 ELECTROMAGNETIC COMPATIBILITY Emissions and Immunity to EN 61326 Electrical Equipment for Measurement Control and Laboratory use Notes 1 Criterion A Normal operation...

Page 53: ...ter becomes more immune to EMI with fewer I O connections Cable length routing and shield termination are very important and can mean the difference between a successful or troublesome installation Li...

Page 54: ...e meter will be held in the reset mode and not able to count Inhibit When low this input will prevent the meter from counting If the input remains low or connected to the common the meter will not be...

Page 55: ...tly into the meter as the Scale Factor and the Scale Multiplier can be left at 1 For calculated SF values greater than 9 99999 If the Scale Factor is a value over 9 99999 maximum value the Scale Multi...

Page 56: ...olls through each digit position Repeat the select and set sequence until all digits are displaying the desired Scale Factor value Press the PAR key to save the displayed value and advance to the next...

Page 57: ...based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalti...

Page 58: ...r tampering by unauthorized personnel to the presets prescale or timed output values The front panel reset button can also be enabled or disabled by a rear panel DIP switch This counter also has an on...

Page 59: ...n power is removed or interrupted Power Cycles ON OFF 100 000 min Data Retention 10 years min 9 INPUT POWER AND OUTPUT CONNECTIONS Fixed terminal block 10 CERTIFICATIONS AND COMPLIANCES EMC EMISSIONS...

Page 60: ...TS AUTOMATIC RESET TO ZERO AFTER TIMED OUTPUT 2 The unit counts from zero when preset 1 is reached output 1 turns on and when preset 2 is reached output 2 turns on The outputs turn off at the end of t...

Page 61: ...up than short cable runs Therefore keep cable runs as short as possible 6 Switching of inductive loads produces high EMI Use of snubbers across inductive loads suppresses EMI Snubbers RLC SNUB0000 WIR...

Page 62: ...n the desired value for that digit is reached release the button Repeat this step until the desired preset value is obtained THIRD Press the E button to enter the value into the unit s memory As Soon...

Page 63: ...t is exited When the switch is DOWN the digit shows a one When the switch is UP the digit shows a zero During the time the mode switch settings are displayed the outputs can be tested To activate the...

Page 64: ...r Control Terminal 5 02 Motor Control Terminal 6 UP DN To Terminal 2 COMM Terminal 7 PGM DIS No Connection Terminal 8 RMT RST To Start Reset switch Front Panel Programming Preset 1 3 Preset 2 20 Presc...

Page 65: ...s employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pur...

Page 66: ...ich is activated during power up self test DIP switch must be enabled Power and input connections are made via a removable terminal strip located at the rear of the unit This strip can accept one 14 A...

Page 67: ...tromagnetic field 1 EN 61000 4 2 Electrostatic discharge ESD 2 EN 61000 4 4 Electrical fast transient burst EFT 1 EN 61000 4 8 Power frequency magnetic field Notes for APLT only 1 EMI filter placed on...

Page 68: ...effective Install them on Signal and Control cables as close to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install...

Page 69: ...t pulse widths never decrease below 5 milliseconds and the count rate does not exceed 100 cps 3 VIL and VIH levels given are nominal values 10 when counter voltage on DC OUT Terminal is 12 VDC These n...

Page 70: ...nto the wide end of the hole located on either side of the case Then snap the clip onto the case Tighten the screws evenly to apply uniform compression thus providing a water tight seal CAUTION Only m...

Page 71: ...o indicate status of the counter A count light illuminates whenever the count signal is high At slow count rates individual counts can be observed by the blinking of this light and at higher count rat...

Page 72: ...t Momentary output time is adjustable from 0 05 to 1 second Count can proceed upward if not reset and if count direction is then reversed by pulling U Ddown to B the outputs will again reactivate as t...

Page 73: ...ontains three LED lights to indicate status of the counter A count light illuminates whenever the count signal is high At slow count rates individual counts can be observed by the blinking of this lig...

Page 74: ...at preset Momentary output time is adjustable from 0 05 to 1 second Count can proceed upward if not reset and if count direction is then reversed by pulling U Ddown to B the outputs will again reacti...

Page 75: ...ion is 2 sec and release is 4 sec 5 OUTPUTS Preset Counters All SC Presettable counters have 2 complementary outputs per preset level Models SC2DU and SC2DD have two sets of outputs one set for each p...

Page 76: ...or counter tachometer installations all terminal A s and B s can be paralleled for load sharing For unusually high sensor current requirements use Accessory Power Supply See Accessory Section of Catal...

Page 77: ...hanges in the preset number once a run has started and also avoids accidental over runs that can occur with counters that allow setting on the fly Electrical connections are made to terminal strips on...

Page 78: ...S5 6 7 8 Reset cycle modes below are shown for Reset to Zero action RTZ S8 OFF where the reset returns the count to zero and the counter then counts up activating the outputs at the preset value Reset...

Page 79: ...number When U D is pulled low the counter will decrement count DOWN to decrease the accumulated number Response time to change count direction is 2 sec Note SC Counters count in complementary numbers...

Page 80: ...all digits of a 6 digit unit display 8 s and with 100 mA relay load s on preset counters If all 6 digits are not used an additional 45 mA is available for each digit not displayed 4 digit models will...

Page 81: ...r once a run has started and also avoids accidental over runs that can occur with counters that allow setting on the fly Electrical connections are made to terminal strips on the rear of the unit Thes...

Page 82: ...paralleled with SCD to share load RESET CYCLE MODES SWITCHES S5 6 7 8 Reset cycle modes below are shown for Reset to Zero action RTZ S8 OFF where the reset returns the count to zero and the counter t...

Page 83: ...he counting sequence when decrementing is 3 2 1 0 999999 999998 999997 etc Also See Note 7 4 INHIBIT I Counter is inhibited from accepting counts as long as I is pulled low to Term B Response time for...

Page 84: ...over the current rating stated SC counter power supplies are not regulated and in multiple counter or counter tachometer installations all terminal A s and B s can be paralleled for load sharing For...

Page 85: ...FORM A 3A or either quad sinking or quad sourcing open collector logic outputs The setpoint alarms can be configured to suit a variety of control and alarm requirements Communication and Bus Capabilit...

Page 86: ...or the PAXI Software can be downloaded from www redlion controls com PAXCDC50 PAXCDL10 PAXCDC4C SFPAX Profibus DP Communications Card Analog Output Card Extended Modbus Communications Card with Dual R...

Page 87: ...sure rating Face only UL50 IECEE CB Scheme Test Certificate UL 5854B UL CB Scheme Test Report 02ME04503 04122002 Issued by Underwriters Laboratories Inc IEC 1010 1 EN 61010 1 Safety requirements for e...

Page 88: ...utput state SP4 setpoint 4 output state RATE DISPLAY Accuracy 0 01 Minimum Frequency 0 01 Hz Maximum Frequency 34 KHz Maximum Display 5 Digits 99999 Adjustable Display low Update 0 1 to 99 9 seconds O...

Page 89: ...PRESCALER OUTPUT NPN Open Collector ISNK 100 mA max VOL 1 VDC max VOH 30 VDC max With duty cycle of 25 min and 50 max PAXI SPECIFICATIONS MAXIMUM SIGNAL FREQUENCIES TABLE To determine the maximum fre...

Page 90: ...outputs can be reversed in the programming These plug in cards include PAXCDS10 Dual Relay FORM C Normally open closed PAXCDS20 Quad Relay FORM A Normally open only PAXCDS30 Isolated quad sinking NPN...

Page 91: ...the finger tabs It is recommended to release the latch on one side then start the other side latch Warning Exposed line voltage exists on the circuit boards Remove all power to the meter and load circ...

Page 92: ...tion To Install 1 With the case open locate the Plug in card connector for the card type to be installed The types are keyed by position with different main circuit board connector locations When inst...

Page 93: ...nes conductors feeding motors solenoids SCR controls and heaters etc The cables should be ran in metal conduit that is properly grounded This is especially useful in applications where cable runs are...

Page 94: ...Generators Etc Input A Two Wire Proximity Current Source Input A Magnetic Pickup Input A Current Sourcing Output Input A Interfacing With TTL Input A Current Sinking Output Input A Switch or Isolated...

Page 95: ...of wires distances up to 4 000 ft and data rates as high as 10M baud the PAX is limited to 19 2k baud The same pair of wires is used to both transmit and receive data RS485 is therefore always half du...

Page 96: ...crement or decrement that digit to the desired number PROGRAMMING MODE EXIT DSP KEY or at PAR KEY The Programming Mode is exited by pressing the DSP key from anywhere in the Programming Mode or the PA...

Page 97: ...A rising edge when Input B is low Input B rising edge when Input A is high and Input B falling edge when Input A is low Quad X4 quAd4 Adds Input A rising edge when Input B is high and Input A falling...

Page 98: ...DD Number of pulses per single unit x CM x SM Where Number of pulses per single unit pulses per unit generated by the process i e of pulses per foot CM Counter Mode x times factor of the mode 1 2 or 4...

Page 99: ...complete about 100 msec an additional transmission will occur Only one transmission will take place with each function key depression This selection will only function when a serial communications Plu...

Page 100: ...HI NO Counter C C CNt NO Counter B b CNt NO Counter A A CNt FACTORY DESCRIPTION DISPLAY 1 1 9 83 1 1 53 ACTIVATE SETPOINT MOMENTARY EDGE When activated momentary action the meter activates the setpoi...

Page 101: ...actor values can be programmed for 1 or 1 5 SCALE FACTOR A B C ACCESS LOCK OUT 1 5 Entry of a non zero value will cause the prompt 1 to appear when trying to access the Full Programming Mode Access wi...

Page 102: ...For non zero based 2 scaling point applications set 1A B3 to enter both the zero segment 2 2 and segment 1 3 3 2 1A 18 18 2 2422 242222 242 24222 Factory Setting can be used without affecting basic s...

Page 103: ...that corresponds to the incoming input signal rate The PAXI and PAXR are capable of showing a rate display value for any linear process KEY IN SCALING METHOD CALCULATION If a display value versus inpu...

Page 104: ...1 3 243 2423 01 Module 5 is the programming for Counter C For maximum input frequency the counter operating mode should be set to 1 when not in use When set to 1 the remaining related parameters are...

Page 105: ...alarm output Reverse 1 displays the corresponding setpoint annunciator of an off alarm output 5 flashes the display and the corresponding setpoint annunciator of an on alarm output 83 8 8 8 55 1 5 9 8...

Page 106: ...alues determine the cycling times tOUt With Boundary action the setpoint output activates when the rate value is greater than or equal to for G or less than or equal to for G the setpoint value The se...

Page 107: ...f 9 Example SP1 deactivates when SP2 is activated and then times out The last setpoint will wrap around to the first 1 1 Factory Setting can be used without affecting basic start up For Reverse Action...

Page 108: ...ingle unit an address is not needed and a value of zero can be used With multiple units RS485 applications a unique 2 digit address number must be assigned to each meter PARAMETER MENU C22 6A22 22 A22...

Page 109: ...e unit address If the address assigned is 00 two spaces are substituted A space byte 3 follows the unit address field The next three characters bytes 4 to 6 are the register mnemonic The numeric data...

Page 110: ...047 Output Signal Register Value 0 005 1 0 000 0 0 20 mA COUNTER C SLAVE COMMUNICATIONS Counter C may be programmed for 1 to act as a serial slave display By doing this the carriage return CR is added...

Page 111: ...to 15 V a b 200 mV mark idle 0 TXD RXD 3 to 15 V a b 200 mV space active Voltage levels at the Receiver COMMAND RESPONSE TIME The meter can only receive data or transmit data at any one time half dup...

Page 112: ...value within the selected Analog Assignment that corresponds to the low limit of the type selected The decimal point is determined by the decimal point setting of the assigned counter or rate The sca...

Page 113: ...ent output is connected and ready Then perform the following procedure 1 Use the arrow keys to display 1 C and press PAR 2 9 is displayed Use the arrow keys to select F1 and press PAR 3 Using the char...

Page 114: ...UE SCALING PT 10 INPUT VALUE SCALING PT 9 INPUT VALUE SCALING PT 7 INPUT VALUE SCALING PT 5 INPUT VALUE SCALING PT 8 INPUT VALUE SCALING PT 6 INPUT VALUE SCALING PT 4 INPUT VALUE SCALING PT 3 INPUT VA...

Page 115: ...Y SETTING PARAMETER DISPLAY 6 SPt Setpoint Alarm Parameters PRINT SCALE FACTORS See Module 2 Exchanging Parameter Lists for details on programming this value Shaded areas are model dependent 9 fCS Fac...

Page 116: ...sition Counter C Scale Factor Counter C Scale Multiplier Counter C Count Load Value Counter C Reset at Power up A8 1 8 9 8 9 8 8 8 8 8 Setpoint Select Setpoint Annunciators Output Logic Power up State...

Page 117: ...be 0 1 sec The Libra counters have an internal non volatile memory device which eliminates the need for battery back up When input power is removed this device will maintain all data necessary for sy...

Page 118: ...28 VDC resistive load 1 8 H P 120 VAC inductive load The operate time is 5 msec nominal and the release time is 3 msec nominal Relay Life Expectancy 100 000 cycles at max rating As load level decrease...

Page 119: ...start the cycle over During automatic reset no counts will be lost as long as the count rate does not exceed 2 500 cps Manual reset will turn off the output if turned on and reset the count to preset...

Page 120: ...2 AT ZERO MANUAL RESET TO PRESET In this mode as the unit counts from preset 2 output 1 will turn on when preset 1 is reached When zero is reached output 2 will turn on and output 1 will turn off Out...

Page 121: ...ecially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter 3 Signal or Control cable...

Page 122: ...continuously scroll the digit from 0 through 9 then back to 0 again When the desired value for that digit is reached release the button Do this for all the digits to be changed This value can be set b...

Page 123: ...indoor use when properly installed The units are intended to be mounted into an enclosed panel with a gasket to provide a water tight seal Two mounting clips and screws are provided for easy installa...

Page 124: ...d which places a red ink marking at the end of a roll of printing paper this marking is used to indicate when the end of the roll is near The unit must also stop the system when the proper amount of p...

Page 125: ...idental changes or tampering by unauthorized personnel to the preset or timed output value The front panel reset button can also be enabled or disabled by a rear panel DIP switch This counter also has...

Page 126: ...rage Temperature 40 to 70 C Operating and Storage Humidity 85 max relative humidity non condensing from 0 C to 50 C Altitude Up to 2000 meters 10 CERTIFICATIONS AND COMPLIANCES SAFETY IEC 1010 1 EN 61...

Page 127: ...ptible to EMI pickup than short cable runs Therefore keep cable runs as short as possible 6 Switching of inductive loads produces high EMI Use of snubbers across inductive loads suppresses EMI Snubber...

Page 128: ...1 and 2 of TBB The DC plus power is connected to TBB 1 and the minus is connected to TBB 2 OUTPUT WIRING Terminals 3 4 and 5 are used to connect to the output relay See Block Diagram The solid state o...

Page 129: ...vated without affecting the count missing a preset point affecting the timed output durations or interfering with control functions This test verifies that all digits operate Also the DIP switch setti...

Page 130: ...nel that is too thin may distort and not provide a water tight seal Recommended minimum panel thickness is 0 125 3 18 mm After the panel cut out has been completed and deburred carefully slide the pan...

Page 131: ...propriate time to cut each form to length When this happens the output of the knife causes the LYNX display to increment When the counter reaches the desired preset value the output fires for the pred...

Page 132: ...n personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed...

Page 133: ...t The Lynx Series of counters have a sealed high impact plastic bezel and meet NEMA 4X IP65 specifications for wash down and or dust when properly installed SAFETY SUMMARY All safety related regulatio...

Page 134: ...afety requirements for electrical equipment for measurement control and laboratory use Part 1 IP65 Enclosure rating Face only IEC 529 Type 4X Enclosure rating Face only UL50 ELECTROMAGNETIC COMPATIBIL...

Page 135: ...al conduit that is properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commer...

Page 136: ...ss the E button to enter the value into the unit s memory As Soon As the E button is pressed the new preset value takes effect If the E button is not pressed within 10 seconds the unit returns to norm...

Page 137: ...d output the unit automatically resets to preset and starts the cycle over MODE 15 When down count is desired such as reset to preset modes of operation the UP DN terminal must be tied to the COMM ter...

Page 138: ...FOR DUAL PRESET LYNX COUNTER Cont d SELF TEST The self test feature can be activated without affecting the count missing a preset point affecting the timed output durations or interfering with contro...

Page 139: ...to an enclosed panel with a gasket to provide a water tight seal One mounting clip and two screws with tinnerman nuts are provided for easy installation Consideration should be given to the thickness...

Page 140: ...ss Relay 2 turns on when the counter reaches 0 stopping the motor completely The operator manually cuts the carpet and removes the full roll replacing it with an empty one The REMOTE RESET button and...

Page 141: ...a sealed high impact plastic bezel and meets NEMA 4X IP65 specifications for wash down and or dust when properly installed SAFETY SUMMARY All safety related regulations local codes and instructions th...

Page 142: ...SWITCH SET UP S1 DIS RST Disables front panel reset EN RST Enables front panel reset S2 to S5 These are the mode select DIP switches See Modes of Operation for the switch settings of a specific mode S...

Page 143: ...OFF AT PRESET 2 TIMED OUTPUT 2 AT PRESET 2 MANUAL RESET TO ZERO The unit times from zero when preset 1 is reached output 1 turns on When preset 2 is reached output 1 turns off and output 2 turns on f...

Page 144: ...s reached output 1 turns on when zero is reached output 2 turns on Time continues to decrement after the preset levels have been reached When a manual reset is performed the time resets to preset 2 th...

Page 145: ...ET 2 AT ZERO The unit times down from preset 2 when preset 1 is reached output 1 turns on When zero is reached output 2 turns on The outputs turn off at the end of their respective programmed time val...

Page 146: ...voltage and current ratings for each terminal Also cabling should conform to appropriate standards of good installation local codes and regulations It is recommended that power supplied to the unit AC...

Page 147: ...self test feature can be activated without affecting the time missing a preset point affecting the timed output durations or interfering with control functions This test verifies that all digits opera...

Page 148: ...use tools of any kind screwdrivers pens pencils etc to operate the keypad of the unit Installation The unit meets NEMA 4X IP65 requirements for indoor use when properly installed The units are intend...

Page 149: ...rammable User Inputs and a programmable front panel function key The user inputs can be configured as sinking active low or sourcing active high inputs via a single plug jumper The user inputs and the...

Page 150: ...es summed 7 USER INPUTS Configurable as current sinking active low or current sourcing active high inputs via a single plug jumper Current Sinking VIL 1 5 VDC max 22 K pull up to 5 VDC Current Sourcin...

Page 151: ...ordered with an optional prescaler output C48CP 3 PRESET BATCH MODELS The C48CB has a secondary counter that can be used for batch counting or to keep a total count This second counter can be program...

Page 152: ...d 8 Auto Reset to Preset at Timed Output End SINGLE PRESET OPERATING MODES Auto Reset to Preset 3 at 03 Timed Output End 8 Auto Reset to Preset 3 03 Timed 7 Auto Reset to Zero at 03 Timed Output End 6...

Page 153: ...tch is moved to the up position to enable the Program Security function Circumference Of Pinch Roller circumference diameter 12 56636 3 14159 4 00 Pulses Per Yard 36 1 i y n a c r h d es 12 1 56 re 6...

Page 154: ...C48CB 3 Preset Batch Counter Reflective LCD Yes O1 Yes No C48CB003 N A 3 Preset Batch Counter Reflective LCD Yes O1 Yes Yes C48CB008 N A 3 Preset Batch Counter Reflective LCD Yes No Yes C48CB005 N A 3...

Reviews: