PAXI: CALIBRATION
29
TROUBLESHOOTING
For further assistance, contact technical support at the appropriate company numbers listed.
PROBLEM
REMEDIES
NO DISPLAY
CHECK
: Power level, power connections
PROGRAM LOCKED-OUT
CHECK
: Active (lock-out) user input
ENTER
: Security code requested
CERTAIN DISPLAYS ARE LOCKED OUT
CHECK
: Module 3 programming
INCORRECT DISPLAY VALUE or NOT
COUNTING
CHECK
: Input wiring, DIP switch setting, input programming, scale factor calculation,
input signal level, user input jumper, lower input signal frequency
USER INPUT NOT WORKING CORRECTLY
CHECK
: User input wiring, user input jumper, user input being used for signal, Module 2
OUTPUT DOES NOT WORK
CHECK
: Corresponding plug-in card installation, output configuration, output wiring
JITTERY DISPLAY
CHECK
: Wiring is per EMC installation guidelines, input signal frequency, signal quality,
scaling, update time, DIP switch setting
“
! +#+#
”
RATE
CHECK
: Lower input signal frequency, reduce rate scaling
MODULES or PARAMETERS NOT ACCESSIBLE
CHECK
: Corresponding plug-in card installation, related controlling parameter selected
ERROR CODE
(
1!! 38@
)
PRESS
: Reset key (if unable to clear contact factory.)
SERIAL COMMUNICATIONS
CHECK
: Wiring, connections, meter and host settings
Analog Output Card Calibration
Before starting, verify that a precision meter with an accuracy of 0.05% or
better (voltmeter for voltage output and/or current meter for current output) is
connected and ready. Then perform the following procedure:
1. Use the arrow keys to display
/+$1 @C
and press
PAR
.
2.
/.#+9'
is displayed. Use the arrow keys to select
F1%
and press
PAR
.
3. Using the chart below, step through the five selections to be calibrated. At
each prompt, use the PAXI arrow keys to adjust the output so that the
external meter display matches the selection being calibrated. When the
external reading matches, or if the range is not being calibrated, press
PAR
.
4. When
/($1 72
appears, press
PAR
twice and remove the external meters .
SELECTION
EXTERNAL METER
ACTION
0.0-A
0.00
Adjust if necessary, press
PAR
4.0-A
4.00
Adjust if necessary, press
PAR
20.0-A
20.00
Adjust if necessary, press
PAR
0.0u
0.00
Adjust if necessary, press
PAR
10.0u
10.00
Adjust if necessary, press
PAR
The only item in the PAXI meter that can be calibrated
is the Analog Output. The Count A and B values are scaled
using the parameters in Module 1, Counter C value is scaled
using Module 5 and the Rate value is scaled using Module 4. If the meter appears
to be indicating incorrectly or inaccurately, refer to the Troubleshooting section.
When Analog Out recalibration is required (generally every 2 years), it
should be performed by qualified technicians using appropriate equipment.
Calibration does not change any user programmed parameters.
Calibration may be aborted by disconnecting power to the meter before
exiting Module 9. In this case, the existing calibration settings remain in effect.
Note
: Allow a 30 minute warm-up period before staring calibration.
!
"
@C
/+$1
Shaded areas are model dependent.