H56874 4/03
www.tycothermal.com
+1 (650) 474-7400
45
TTDM-128
User Manual
Appendix 2 -
Connection to Other Devices
N
OTE
: All connections to external devices are made at the TTDM-128.
RELAYS
TTDM-128 has three relays:
Service
Leak
Fault
Relay Logic
Each relay provides two Form-C relay contacts, with normally open and normally closed
contacts both provided. The relays are de-energized to indicate an alarm condition. The
diagram below shows the relay status when each is in an alarm (de-energized) state.
Wiring Options to Gang Alarm Relays on a Single Pair of Wires
The illustrations below show how the relays can be jumpered together to allow remote
monitoring of the TTDM-Plus system status with only a single pair of wires. The TTDM-
128 de-energizes its relays to signal an alarm condition. Therefore, loss of power as well
as any other type of alarm would trip the remote alarm.
Open on Alarm
15 16 17 18 19 20
21 22 23 24 25 26
27 28 29 30 31 32
Monitoring circuit
(open on alarm)
Relays wired
in series
15 16 17
20
19
18
21 22 23
26
25
24
27 28 29
32
31
30
LEAK RELAY
SERVICE RELAY
FAULT RELAY
Summary of Contents for TraceTek TTDM-128
Page 1: ...LEAK DETECTION powered by TTDM 128 TraceTek Leak Detection Master Module User Manual...
Page 2: ...H56874 4 03 www tycothermal com 1 650 474 7400 2 2003 Tyco Thermal Controls LLC...
Page 4: ...H56874 4 03 www tycothermal com 1 650 474 7400 4...
Page 15: ...H56874 4 03 www tycothermal com 1 650 474 7400 15 TTDM 128 User Manual TTDM 128 Features...
Page 28: ...H56874 4 03 www tycothermal com 1 650 474 7400 28...
Page 40: ...H56874 4 03 www tycothermal com 1 650 474 7400 40...
Page 47: ......