SIM Network
The SIM Network menu has the following submenus:
▪
Set SIM Address
▪
Init Network
▪
Update Network
SET SIM ADDRESS
This command allows the user to assign a new address to either the TTDM’s internal
SIM or an external TTSIM. This function is vital to starting up a new leak detection
network. To assign an address to a TTSIM, it must be connected to the TTDM and
able to communicate with it.
I
MPORTANT
:
Be sure to assign a unique SIM address, or
communications problems will result.
To set SIM or TTSIM addresses, the SIM/TTSIM to be addressed must be set to the
configure mode. This is accomplished by placing a jumper on the CFG pins (J1 on the
TTDM’s internal SIM – see TTDM-128 Installation Instructions for details; refer to the
appropriate TTSIM installation instructions for details regarding external TTSIM’s). Note
that only 1 SIM or TTSIM can be set to CFG at a time. After setting the address, you must
remove the CFG jumper before proceeding to the next SIM/TTSIM.
To add a new TTSIM to the leak detection network and assign it an
address
►
Install and connect the TTSIM in accordance with the TTSIM Installation Instructions that
accompanied it.
►
Install the CFG jumper on the TTSIM.
►
Press the
M
ENU
key to access the main menu.
►
Select SIM Network and press
E
NTER
.
►
Select Set SIM Address and press
E
NTER
.
►
Select New Address and press
E
NTER
.
►
Use the arrow keys to set the new address to an unused address between 001 and 127 (note
that address 001 is the factory default for the TTDM’s internal SIM) and press
E
NTER
.
►
Remove the CFG jumper clip from the TTSIM, then press
E
SC
on the TTDM.
►
Repeat as necessary for each TTSIM added to the network.
To add a new TT-NRM to the leak detection network and assign it an
address
►
Install and connect the TT-NRM in accordance with the Installation Instructions that
accompanied it.
►
Using the switches on the TT-NRM base unit, select a unique address. The address must not
be used by any other device on the network, and must be in the range 50 to 59.
I
MPORTANT
:
Be sure to assign a unique address that is not used by any other
TT-NRM,
TTSIM or TTDM units on the network, or communications problems will result.
►
Power up the system and perform a network Update or Initialization (see INIT NETWORK
and UPDATE NETWORK, page 32)
►
Configure relay assignments (see SETTING UP REGIONS AND RELAYS, page 26)
Summary of Contents for TraceTek TTDM-128
Page 1: ...LEAK DETECTION powered by TTDM 128 TraceTek Leak Detection Master Module User Manual...
Page 2: ...H56874 4 03 www tycothermal com 1 650 474 7400 2 2003 Tyco Thermal Controls LLC...
Page 4: ...H56874 4 03 www tycothermal com 1 650 474 7400 4...
Page 15: ...H56874 4 03 www tycothermal com 1 650 474 7400 15 TTDM 128 User Manual TTDM 128 Features...
Page 28: ...H56874 4 03 www tycothermal com 1 650 474 7400 28...
Page 40: ...H56874 4 03 www tycothermal com 1 650 474 7400 40...
Page 47: ......