H56874 4/03
www.tycothermal.com
+1 (650) 474-7400
12
PREPARATION
Before operation, follow the installation instructions to ensure that each module is
properly:
§
Mounted
§
Powered
§
Connected to a TraceTek sensing cable or point contact closure device with a
TraceTek jumper or leader cable
§
Interconnected with the other leak detection modules using RS-485
wiring
If these steps have not been taken, refer to the installation documents provided
for each module. This literature can be obtained from the TraceTek web site (
http:
//www.tycothermal.com
).
I
MPORTANT
:
There should be a “System Map” for each sensor circuit. The system map
should show the sensing cable layout with reference readily identifi
able landmarks and
with actual distance measurements every 5m (15 feet) throughout the system. The map is
normally completed at the time the leak detection system is commissioned. Ensure that a
copy of the system map is kept near the TTDM-128 module. If the TTDM-128 is connected
to a building management system, ensure that a copy of the system map accompanies
the building management system.
Notes
§
Throughout this manual, the examples shown use distances in
meters.
§
Later versions of software may provide new features and change certain other
details. This manual documents UI software version 4.
§
For technical assistance, call your local TraceTek distributor. All distributors are listed
on our web site (
http://www.tycothermal.com
).
sensing circuit, if different types of fluid are being monitored in the same area it may be
more effective to create multiple circuits, each with dedicated sensor cable of a specific
that can be configured in many different ways. For more information on the products and
completes each branch. At the branching connector, the system first counts
Summary of Contents for TraceTek TTDM-128
Page 1: ...LEAK DETECTION powered by TTDM 128 TraceTek Leak Detection Master Module User Manual...
Page 2: ...H56874 4 03 www tycothermal com 1 650 474 7400 2 2003 Tyco Thermal Controls LLC...
Page 4: ...H56874 4 03 www tycothermal com 1 650 474 7400 4...
Page 15: ...H56874 4 03 www tycothermal com 1 650 474 7400 15 TTDM 128 User Manual TTDM 128 Features...
Page 28: ...H56874 4 03 www tycothermal com 1 650 474 7400 28...
Page 40: ...H56874 4 03 www tycothermal com 1 650 474 7400 40...
Page 47: ......