H56874 4/03
www.tycothermal.com
+1 (650) 474-7400
19
TTDM-128
User Manual
Normal operation
Current Event/Status Display
Line 1
CH01 SERVER ROOM
Line 2
LEAK AT 125 M
Line 3
Line 4
12 :30 21-01-2003
The LCD display is a backlit 4-line by 20-character display. If there is no activity for several
minutes, the back lighting turns off, until a key is pressed.
Line 1
identifies the channel currently displayed, showing the SIM channel
number and user-defined ID tag (up to 14 characters). For a new
system, the user-defined label is blank until edited by the user (see
page 7).
Line 2
indicates the current status of the SIM channel identified on Line 1,
or
In the case of Leak re-alarm, displays the initial Leak location of the
SIM channel identified on Line 1.
Line 3
may advise action or provide special instructions,
or
in the case of Leak re-alarm, indicates the current status of the SIM
channel identified on Line 1.
Line 4
displays the current time (in 24 hour format) and date; the colon
blinks once a second,
or
in the case of Leak re-alarm may advise action or provide special
instructions.
H
INT
: The LCD contrast may be adjusted (feature 27 in the diagram on page 16).
If no new alarm conditions exist, the LCD display scrolls through each connected SIM
channel in sequence. The LCD presents the current event/status screen for each channel
for about 4 seconds, then continues to the next available SIM channel number (and scrolls
back to the first after the last channel).
If the TTDM detects a new Service, Fault, or Leak event, it immediately jumps the display
to the SIM channel affected, turns on the LCD back light, and pauses at that channel
number for several minutes.
N
OTE
: Use the left and right arrow keys to manually select the channel displayed.
Navigating the Menu Structure
Please refer to the “Menu Structure” diagram on page 22 for an overview of the
TTDM-128
menu structure. Refer to the diagram on page 16 to locate the menu keys described below:
Summary of Contents for TraceTek TTDM-128
Page 1: ...LEAK DETECTION powered by TTDM 128 TraceTek Leak Detection Master Module User Manual...
Page 2: ...H56874 4 03 www tycothermal com 1 650 474 7400 2 2003 Tyco Thermal Controls LLC...
Page 4: ...H56874 4 03 www tycothermal com 1 650 474 7400 4...
Page 15: ...H56874 4 03 www tycothermal com 1 650 474 7400 15 TTDM 128 User Manual TTDM 128 Features...
Page 28: ...H56874 4 03 www tycothermal com 1 650 474 7400 28...
Page 40: ...H56874 4 03 www tycothermal com 1 650 474 7400 40...
Page 47: ......