Status of Individual SIM channels
The TTDM-128 offers access to detailed real-time status information for each SIM
channel. The status display for an individual SIM channel is accessed from the Current
Event/Status display (the normal display mode):
►
If in a menu, press
E
SC
one or more times to return the display to the normal display mode.
►
Use the
L
EFT
or
R
IGHT
arrow keys to select the SIM channel of interest.
►
Press the
D
OWN
arrow to access the detailed status information (as shown below) for the
selected channel.
SIM Status
SIM Address
ID
{SIM Status}
TestLength
Sense Cur
Serv Alert >=
Sense Res
Leak Alarm <=
R-G Res
Y-B Res
SI Version
SI Comm
Add Regions/Relays
{address}
{user defined ID}
{xxxx m}
{xxx uA}
{xx uA}
{xxx kΩ}
{xx kΩ}
{xxxx Ω}
{xxxx Ω}
{xxx}
{xxx%}
N
OTE
: Only four lines are displayed at one time. Arrows in the scroll bar indicate if other
entries can be accessed with the up or down arrow keys.
A description of each entry on the SIM Status Menu appears below:
SIM Address
Channel number for information in current display
ID
An alphanumeric label specified by the user (maximum 14
characters).
SIM status
This is a variable field, which can contain any of the following
text, depending on the state of that SIM channel:
▪
SIM Normal
▪
Leak at {location}
▪
Re-alarm [new location]
▪
Service Required
▪
Fault (for specifics, see page 37)
Test Length
Total length of sensing cable attached to the selected SIM.
The test length should be the same as that recorded when
the channel was mapped. If the length is not the same, it
may mean that the system was modified (sensing cable was
removed or added).
Note: The Test Length is typically about 1% longer than the
physical or mapped length for the channel; this is normal.
Summary of Contents for TraceTek TTDM-128
Page 1: ...LEAK DETECTION powered by TTDM 128 TraceTek Leak Detection Master Module User Manual...
Page 2: ...H56874 4 03 www tycothermal com 1 650 474 7400 2 2003 Tyco Thermal Controls LLC...
Page 4: ...H56874 4 03 www tycothermal com 1 650 474 7400 4...
Page 15: ...H56874 4 03 www tycothermal com 1 650 474 7400 15 TTDM 128 User Manual TTDM 128 Features...
Page 28: ...H56874 4 03 www tycothermal com 1 650 474 7400 28...
Page 40: ...H56874 4 03 www tycothermal com 1 650 474 7400 40...
Page 47: ......