Modem: Define modem dialing strings
▪
▪
Configuration Specific Setup
►
►
►
►
►
t i p
t
i
Remote repeater RS-485 connection diagram
H56874 4/03
www.tycothermal.com
+1 (650) 474-7400
9
TTDM-128
User Manual
Single Channel with Remote Repeater (continued ...)
At the Primary (Slave) TTDM
►
Perform Basic TTDM-128 Setup (page 7)
►
Assign the leak detection channel tag if required (page 7)
►
Make sure that the Host Port Mode Selector Switch on the User Interface
board is set to RS485
►
Set the host port parameters as follows (page 8):
▪
Set baud rate to 9600
▪
Set TTDM mode to Slave
At the Remote Repeater (Master) TTDM
►
Perform Basic TTDM-128 Setup (page 7). Be sure the settings match those of the Primary
TTDM
►
Perform the Host Port Setup as required (page 8). Check that the TTDM mode is set to
Master.
►
Change the Communication Timeout parameter:
▪
With the TTDM in the Current Event/Status display, press
M
ENU
▪
Use the
D
OWN
arrow key to select General Setup, then press
E
NTER
▪
Use the
D
OWN
arrow key to select Password, then press
E
NTER
▪
Input the value 04000, then press
E
NTER
followed by
E
SC
▪
Use the
D
OWN
arrow key to select Special, then press
E
NTER
▪
Use the
D
OWN
arrow key to select Comm Timeout, then press
E
NTER
▪
Use the arrow keys to input the value 660 ms, then press
E
NTER
▪
Press
M
ENU
to return to the Current Event/Status display
►
Initialize the SIM network:
▪
With the TTDM in the Current Event/Status display, press
M
ENU
▪
Use the
D
OWN
arrow key to select SIM Network, then press
E
NTER
▪
Use the
D
OWN
arrow key to select Init Network, then press
E
NTER
►
Change the leak detection channel ID tags (page 7) to match what was set at the Primary
TTDM
SINGLE TTDM-128 WITH NETWORK SYSTEM
►
Perform Basic TTDM-128 Setup (page 7)
►
Perform the Host Port Setup if required (page 8)
►
Assign a unique address to each TTSIM (page 7)
►
Change the leak detection channel ID tags for each TTSIM if required (page 7)
Summary of Contents for TraceTek TTDM-128
Page 1: ...LEAK DETECTION powered by TTDM 128 TraceTek Leak Detection Master Module User Manual...
Page 2: ...H56874 4 03 www tycothermal com 1 650 474 7400 2 2003 Tyco Thermal Controls LLC...
Page 4: ...H56874 4 03 www tycothermal com 1 650 474 7400 4...
Page 15: ...H56874 4 03 www tycothermal com 1 650 474 7400 15 TTDM 128 User Manual TTDM 128 Features...
Page 28: ...H56874 4 03 www tycothermal com 1 650 474 7400 28...
Page 40: ...H56874 4 03 www tycothermal com 1 650 474 7400 40...
Page 47: ......