TTDM-128
User Manual
Common Setup Procedures
All modules, cables and sensors should be installed in accordance with their installation
instructions prior to performing the setup procedures.
BASIC TTDM-128 SETUP (FOR ALL CONFIGURATIONS)
►
Power up the TraceTek system. Wait while the TTDM completes its self test and network
initialization process.
►
With the TTDM on the Current Event/Status display, press the
M
ENU
key
►
Using the
D
OWN
Arrow key, scroll to General Setup and press
E
NTER
▪
Select the desired language
▪
Set the Time and Date (adjust values as necessary using the arrow keys, then press
E
NTER
)
▪
Select the units (feet, meters or zones)
►
Press
M
ENU
to return to the Current Event/Status display
SETTING TTSIM ADDRESSES ON NETWORK SYSTEMS
If your system includes TTSIM modules, their network addresses must be set to unique
values typically in the range from 2 to 127 (address 1 is the default address of the
TTDM’s internal Sensor Interface board). If TT-NRM network relay modules are installed,
the TTSIM addresses must be different than any TT-NRM addresses. (
Note: TT-NRM
modules can only be set to addresses in the 50-59 range.
)
►
With the TTDM on Current Event/Status display, press Menu
►
Use the
DOWN
arrow key to select
SIM Network
, then press
E
NTER
►
For each TTSIM:
▪
Place the TTSIM configuration jumper in the CFG position (see TTSIM Installation
Instructions).
▪
With the TTDM in the
SIM Network
menu, use the
U
P
and
D
OWN
arrow keys to select Set
SIM Address, then press
E
NTER
▪
Press
E
NTER
again, use the arrow keys to input the new TTSIM address, then press
Enter
▪
Return the TTSIM configuration jumper to the normal operating position (see TTSIM
Installation Instructions)
►
Press
Menu
to return the TTDM to normal operating mode
CHANGING LEAK CHANNEL ID TAGS
Each leak detection channel (TTDM or TTSIM) can be given a unique alpha-numeric
identification tag. To change the ID tag of a channel:
►
With the TTDM in normal operating mode and displaying the status of the desired leak
detection channel, press the
D
OWN
ARROW
key
▪
Use the
down arrow
key to scroll to select ID, then press
Enter
▪
Using the
L
EFT
and
R
IGHT
arrow keys to select the character position, and the
U
P
and
D
OWN
arrow keys to change the letters and numbers, enter the desired ID tag. Press
Enter
when
finished.
▪
Press
M
ENU
to return to the normal operating mode.
Quick Setup
Time saving hint
▪
If the space to the right is blank, press
the right arrow to duplicate the last
letter entered
▪
Use the
R
ESET
key to jump between
letters, numbers and blank
Summary of Contents for TraceTek TTDM-128
Page 1: ...LEAK DETECTION powered by TTDM 128 TraceTek Leak Detection Master Module User Manual...
Page 2: ...H56874 4 03 www tycothermal com 1 650 474 7400 2 2003 Tyco Thermal Controls LLC...
Page 4: ...H56874 4 03 www tycothermal com 1 650 474 7400 4...
Page 15: ...H56874 4 03 www tycothermal com 1 650 474 7400 15 TTDM 128 User Manual TTDM 128 Features...
Page 28: ...H56874 4 03 www tycothermal com 1 650 474 7400 28...
Page 40: ...H56874 4 03 www tycothermal com 1 650 474 7400 40...
Page 47: ......