9
•
in compliance with the Plumbing Standard AS/NZS 3500.4,
▪
The water heater is suitable for either indoor or outdoor installation.
•
in compliance with the Australian / New Zealand Wiring Rules AS/NZS 3000,
▪
Isolation switches must be installed in the electrical circuit to the water heater in accordance with
the Wiring Rules, so the water heater can be switched off.
▪
The power supply wires are to be directly connected to the terminal block and earth tab
connection, with no excess wire loops inside the front cover. The temperature rating of the power
supply wires insulation and any sensor or interlock wiring must suit this applicationor the wiring
protected by insulating sleeving with an appropriate temperature rating if it can make contact with
the internal header. The temperature of the internal header can reach up to 82°C under normal
operation.
•
in compliance with AS/NZS 5601.1 and AS 3814 as applicable under local regulations,
•
in compliance with all local codes and regulatory authority requirements.
•
in New Zealand, the installation must also conform to Clauses G11, G12 and H1 of the New Zealand
Building Code.
•
The water heater must be commissioned and certified in accordance with AS 3814.
Installation and commissioning requirements and details for the installing plumber, gas fitter and
licensed electrical worker commence on page 20.