61
System
Purge
Time
OFF,
0:20 ~ 20:00 min
Sets the length of system pump (P2) post purge i.e. pump
run on (only when Modbus Mode para = Temp or Rate and
if PIM DIP switch 3 is ON - Default DIP 3 setting is ON)
0:20 min
Glycol %
0 ~ 50%
Not used for MVB
0%
Ind DHW
Sensor S5
OFF, ON
Select ON if an indirect DHW tank sensor S5 is used in lieu
of an indirect DHW tankstat (only avail if Mode para = 2 or
3)
OFF
Ind Supply
Setpoint
300.0,
0.5 ~ 93.0°C
Indirect DHW tank target setpoint temp when a tankstat is
used in lieu of tank sensor S5 (only avail if MODE para = 2
or 3 and Ind DHW Sensor S5 para = OFF)
82.0°C
Ind DHW
Setpoint
OFF,
10.0 ~ 82.0°C
Indirect DHW target setpoint temp (only avail if Mode para
= 2 or 3 and Ind DHW Sensor S5 para = ON)
60.0°C
(82ºC Max)
Ind
Differential
1.0 ~ 5.0°C
Subtractive differential for Ind DHW Setpoint para i.e. 3°
diff = CFH at 3° below Ind DHW Setpoint and CFH end at
Ind DHW Setpoint (only avail if Mode para = 2 or 3 and Ind
DHW Sensor S5 para = ON)
3°C
Ind Priority
Enable
OFF, ON
Select ON if indirect DHW priority is required during an
indirect DHW tank CFH (only avail if Mode para = 2.
Indirect priority is always on for mode 3)
OFF
Priority
Ovr Timer
AUTO,
0:10 ~ 2:00 hr
Sets length of priority override time (only avail if Mode para
= 3
or
if Mode para = 2 and Ind Priority Enable para is set
to ON
1:00 hr
WWSD
4.0 ~ 37.5°C
OFF
Warm weather heating shut down temp (only avail if Target
Mode para = RSET) Note: Indirect DHW CFH will override
21.0°C
Outdoor
Start
1.6 ~ 29.4°C
Outdoor reset start temp (only avail if Target Mode para =
RSET)
21.1°C
Outdoor
Design
-51.1 ~ 7.2°C
Outdoor reset design temp (only avail if Target Mode para
= RSET)
-12.2°C
Boiler
Start
1.6 ~ 65.5°C
Starting heater target temp when outdoor temp is at
Outdoor Start temp (only avail if Target Mode para =
RSET)
21.0°C
Boiler
Design
21.1 ~ 93.3°C
RSET target setpoint. Calculated when outdoor temp is as
cold as Outdoor Design temp (only avail if Target Mode
para = RSET)
82.2°C
(80ºC Max)
Modbus
Mode
Off, Monitor,
Temp, Rate
BMS Modbus operating mode (Temp = Temp control, Rate
= Rate control)
Monitor
Address
1 ~ 170
Modbus slave address (not avail if Modbus Mode para =
OFF)
1
Data Type
RTU, ASCH
Modbus data type (not avail if Modbus Mode para = OFF)
RTU
Parity
None, Odd, Even
Modbus parity (not avail if Modbus Mode para = OFF)
Even
Baud Rate
2400, 9600,
19200, 57600,
115000
Modbus baud rate (not avail if Modbus Mode para = OFF)
19200
(1
) Split differential for hydronic Target Setpoint e.g. 5.0°C diff = CFH at 2.5°C below Target Setpoint &
CFH end at 2.5°C above Target Setpoint (only available to be viewed/changed if PIM DIP switch 1 is
ON otherwise hydronic differential is 12°C split (6°C above/below setpoint) and parameter is not
displayed
– Default DIP 1 setting is OFF).