56
XPak FT Fault Text
Error Display
If there is an active error, then it is displayed as the first
item in the Toolbox Menu and it is the default display
for the control until the error is resolved.
Table X: Error Display
Error Item
Description and Troubleshooting
OUTLET SEN
Check the outlet water sensor and its wiring.
LIMIT SEN
Check the high limit sensor and its wiring.
INLET SEN
Check the inlet sensor and its wiring.
GAS PRESS
Check PIM wiring.
IGNITION
Reset control, push and release RESET button
LIMIT TRIP
Boiler temperature tripped the high limit.
FLAME
False flame detected. Shut off gas supply, recycle power.
ID CARD
Identity card, check ID card and wiring.
IGN CTRL
Internal control fault. Reset power, replace control.
DELTA T
Temperature difference between the inlet and outlet exceeded the set
point. Check water flow.
LOW 24VAC
Low 24 VAC power. Check power supply wiring and transformer.
BLOW SPEED
Blower speed out of range. Check blower wiring and blower.
3/16”
NOTE: If receiving a NO FLAME, check the gap spacing between
points on the electrode by holding two quarters together and sliding
them through the gap. There should be no resistance.
Fig. 56: Direct Spark Igniter
CAUTION:
If overheating occurs or the gas supply
fails to shut off, do not turn off electrical power to the
circulating pump. This may aggravate the problem
and increase the likelihood of boiler damage.
Instead, shut off the gas supply to the boiler at the
gas service valve.
CAUTION:
Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing. See wiring diagram.
WARNING:
Do not use this appliance if any part
has been under water. Improper or dangerous
operation may result. Contact a qualified service
technician to inspect the boiler and to repair or
replace any part of the boiler that has been under
water prior to placing the boiler back in operation.
Summary of Contents for 88AR-398A
Page 18: ...18 Fig 13 MODE 1 Single Boiler Primary Secondary Piping...
Page 19: ...19 Fig 14 MODE 2 Single Boiler Primary Secondary Piping with Indirect DHW on System Loop...
Page 20: ...20 Fig 15 MODE 3 Single Boiler Primary Secondary Piping with Indirect DHW on Boiler Loop...
Page 47: ...47 WIRING DIAGRAM Fig 46 Wiring Diagram...
Page 54: ...54 Fig 55 Boiler Lighting Shut Off Instructions...
Page 65: ...65 ILLUSTRATED PARTS LIST...
Page 66: ...66...
Page 67: ...67...