43
Table R: Boiler View Menu
Boiler View Menu
The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well
as software and hardware information
Item
Application
Description
User
BOILER 1
ALL
Enables Boiler for operation
BOILER 2
CASCADE
Enables Boiler for cascade operation
BOILER 3
CASCADE
Enables Boiler for cascade operation
BOILER 4
CASCADE
Enables Boiler for cascade operation
IGNITION
ALL
IDLE=no CFH PREP=pre-purge or inter-purge between trials for ignition IGN=trial for
ignition BURN=burner operating POST=post purge HARD=a hard lockout fault has
occurred requiring manual reset (Ignition Lockout or manual high limit) and SOFT=a
soft lockout fault has occurred which interrupts the heating cycle (any safety other
than ignition or manual high limit).
The CFH will resume after the soft lockout fault has been corrected and a 15 min.
waiting period has expired.
N/A
LIMIT TEMP
ALL
Current Outlet -Limit temperature
N/A
EMS Vdc
ALL
Current EMS signal in Volts DC
N/A
FIRE RATE
ALL
PIM
N/A
SPEEDX 1000
ALL
Blower speed in revolutions per minute (rpm) x 1000
N/A
OUTLET MAX
Mode 1, 2, 3
Defines Max Outlet temperature offset above Target Setpoint (Press and hold up and
down arrows for 3 seconds to enable adjustment), see Versa IC manual, catalog
5000.72.
OPERATOR
ALL
Operator Potentiometer setting on PIM
N/A
DIFF
ALL
Current auto differential – Fixed by PIM
N/A
Pump Post
ALL
Sets the length of the boiler pump purge
N/A
FLAME CUR
ALL
Flame current in micro-amps (µA)
N/A
MASS
ALL
Thermal mass recovery, see Versa IC manual, catalog 5000.72.
IDENTITY
ALL
Identifies the unit as boiler, water heater or pool heater
N/A
IGN TYPE
ALL
PIM Board type
N/A
ID CARD
ALL
Identifies Raypak Identity Card
N/A
SW ID
ALL
PIM Software identification number
N/A
ERROR CODE
ALL
Current Error Code
N/A
Summary of Contents for 88AR-398A
Page 18: ...18 Fig 13 MODE 1 Single Boiler Primary Secondary Piping...
Page 19: ...19 Fig 14 MODE 2 Single Boiler Primary Secondary Piping with Indirect DHW on System Loop...
Page 20: ...20 Fig 15 MODE 3 Single Boiler Primary Secondary Piping with Indirect DHW on Boiler Loop...
Page 47: ...47 WIRING DIAGRAM Fig 46 Wiring Diagram...
Page 54: ...54 Fig 55 Boiler Lighting Shut Off Instructions...
Page 65: ...65 ILLUSTRATED PARTS LIST...
Page 66: ...66...
Page 67: ...67...