29
The Multi-vent connector is capable of using stainless
steel (SST), Polypropylene or PVC/CPVC pipe. Before
installing vent pipe, verify which o-ring gasket will be
used and dispose of the other two.
NOTE:
During winter months check the vent cap
and make sure no blockage occurs from build-up of
snow or ice.
Vent Terminal Location
1. Condensate can freeze on the vent cap. Frozen
condensate on the vent cap can result in a blocked
flue condition.
2. Give special attention to the location of the vent
termination to avoid possibility of property dam-
age or personal injury.
3. Gases may form a white vapor plume in winter.
The plume could obstruct a window view if the ter-
mination is installed near windows.
4. The bottom of the vent terminal and the air intake
shall be located at least 12 in. above grade, includ-
ing normal snow line.
5. Single-wall Category IV metal vent pipe shall not
be used outdoors in cold climates for venting gas-
fired equipment without insulation.
6. Through-the-wall vents for Category IV appli-
ances shall not terminate over public walkways or
over an area where condensate or vapor could
create a nuisance or hazard or could be detrimen-
tal to the operation of regulators, relief valves, or
other equipment.
6. Locate and guard vent termination to prevent acci-
dental contact by people or pets.
7. DO NOT terminate vent in window well, stairwell,
alcove, courtyard or other recessed area.
9. DO NOT terminate above any door, window, or
gravity air intake. Condensate can freeze, causing
ice formations.
10. Locate or guard vent to prevent condensate from
damaging exterior finishes. Use a 300-series
stainless steel backing plate against brick or
masonry surfaces.
Combustion
Air Supply
Exhaust
Configuration
Heater
Venting
Category
Certified Vent
Materials
Combustion
Air Inlet
Material
From Inside Building
(Non-Direct Venting)
Vertical Venting
IV
(Canada Only: ULC-
S636 PVC and CPVC)
Stainless Steel,
AL29-4C,
Sch 40 PVC or CPVC
Polypropylene*
Horizontal Through-
the-Wall Venting
From Outside Building
(Direct Venting)
Vertical Venting
Galvanized Steel,
PVC, ABS,
CPVC
Horizontal Through-
the-Wall Venting
Table L: Venting Category Requirements
* Only Duravent
®
polypropylene is approved for the XPak FT product
.
WARNING:
Condensate is acidic and highly
corrosive. The drain line must not be allowed to
freeze. Take appropriate measures.
COMBUSTION
COM
COMBU
COMBUS
COMBUST
COMBUSTI
COMBUSTIO
COMBUSTION
TEST PORT
COMBUSTION
TEST PO
COMBUSTION
TEST PORT
3 O-RING
COMBUSTION
TEST PORT
3 O-RING
GASKETS
COMBUSTION
TEST PORT
3 O-RING
GASKETS
Fig. 26: 3 in 1 Multi-Vent Connector
Summary of Contents for 88AR-398A
Page 18: ...18 Fig 13 MODE 1 Single Boiler Primary Secondary Piping...
Page 19: ...19 Fig 14 MODE 2 Single Boiler Primary Secondary Piping with Indirect DHW on System Loop...
Page 20: ...20 Fig 15 MODE 3 Single Boiler Primary Secondary Piping with Indirect DHW on Boiler Loop...
Page 47: ...47 WIRING DIAGRAM Fig 46 Wiring Diagram...
Page 54: ...54 Fig 55 Boiler Lighting Shut Off Instructions...
Page 65: ...65 ILLUSTRATED PARTS LIST...
Page 66: ...66...
Page 67: ...67...