background image

A

PPENDIX

 F

108

ISO Product Controller II and Hawkeye Operation Manual

completed, the ISO icon at the top right of the screen will be green. Hawkeye nozzle control valves must be 

properly indexed for this to work.

8. Inspect the status of the overlap control unlock. Temporary unlock is usually active upon start-up but a 

permanent unlock purchase is required to ensure proper overlap control operation.

9. Ensure the alarm indicator is green. Red indicates a serious error condition that will prevent the system from 

spraying. Yellow alarm indicates a warning that requires investigation but will not prevent spraying. Clear all 

conditions as necessary.

10. Enter a test speed in the UT mode. The boom section switches on the vehicle should respond with the 

corresponding boom section icons in the UT window. No triangle indicates that the boom is off. an empty 

triangle indicates the boom is active but is being controlled by Accuboom. A triangle that is filled in blue 

indicates the boom is spraying. The nozzle control valves should click of operating properly. Expect a pump 

pressure error because the pump is not running.

NOTE:

With water in the tank this step can be performed with the engine running. Do not run the pump for 

an extended period of time with no liquid in the tank because this may damage the seals.

11. Start a job. Ensure that all necessary widgets are available to the operator to allow proper machine operation. 

Make a copy for the complete widget setup for the operator to modify.

12. In job view mode, enter a test speed. Verify that the section control is off. The boom section switches should 

respond to the corresponding boom sections in the UT window. No triangle means the boom is off. An empty 

triangle indicates the boom is active but is being controlled by Accuboom. A triangle filled in blue means the 

boom should be spraying. Expect a pump pressure error since the pump is not running. if the booms do not 

respond correctly, delete and import the boom settings.

NOTE:

With water in the tank this step can be performed with the engine running. Do not run the pump for 

an extended period of time with no liquid in the tank because this may damage the seals.

13. After all systems are functions properly, will the tank with water and complete the functional inspection.

FUNCTIONAL INSPECTION

Refer to the following sections for assistance with validating that the Hawkeye nozzle control system has been 

installed properly:

NOZZLE CONTROL VALVE FUNCTION

To verify that the Hawkeye nozzle control system is functioning properly after installation:
1. Flush the main product tank and boom plumbing with clean water, and verify the tank contains at least 100 

gallons [379 L] of clean water.

2. Park the equipment in an area with enough space to unfold the booms and allows for visual inspection of the 

spray pattern from a moderate distance (e.g. 20 ft [6.1 m]).

3. Set the Hawkeye nozzle control system to manual mode, and set both the pump PWM and nozzle PWM to 

50%. Refer to the ± Bump section on page 43 for assistance with adjusting the PWM percent values in the 

manual control mode.

4. Toggle all section switches and the master switch.

 

WARNING

Equipment will begin spraying. Avoid inhaling 

spray particulate and avoid direct contact with 

any agricultural chemicals. Seek immediate 

medical attention if symptoms of illness occur 

during, or soon after, use of agricultural 

chemicals, products, or equipment.

Summary of Contents for ISO Product Controller II

Page 1: ...ISO Product Controller II and Hawkeye Operation Manual P N 016 0171 584 H 01 19 E32470 Copyright 2019...

Page 2: ...ven Industries shall not be held responsible for any modifications or repairs made outside our facilities nor damages resulting from inadequate maintenance of this system As with all wireless and sate...

Page 3: ...ss Diagnostic Control 10 Care and Use 10 Updates 10 Chapter 3 System Calibration 13 Initial Start Up and Calibration Wizard 13 Calibration Wizard 13 Functional Inspection 16 Nozzle Control Valve Funct...

Page 4: ...a Register 51 Tally Register Definitions 52 Task Tallies 52 Lifetime Tallies 52 Device Stats 52 Distance 52 Flow Rate Display 52 Area Hour Display 52 Chapter 7 Hawkeye Nozzle Control Valve Diagnostics...

Page 5: ...rol Settings 92 Response Rate 92 Appendix D Maintenance Schedule and Replacement Parts 93 Hawkeye Nozzle Control Valve Maintenance 93 Nozzle Control Valve Maintenance Procedure 97 Hawkeye Nozzle Contr...

Page 6: ...e Operation Manual Appendix G Hawkeye Flowchart 111 Hawkeye Flowchart 111 Appendix H Remote Control and Diagnostics Application 119 Remote Operation 119 Diagnostics Application Operation 119 Diagnosti...

Page 7: ...ENERAL IMPLEMENT INFORMATION TANK FILL SETTINGS PRODUCT CONTROL SETTINGS UNITS US Acres SI Hectares Nozzle Spacing Boom Offset Speed Cal Tip Size Boom Section Widths Boom Cal 1 5 9 13 2 6 10 14 3 7 11...

Page 8: ...km h Kilometers per Hour GPA Gallons per Acre US Volume per Acre lit ha Liters per Hectare SI Volume per Hectare ml ha Milliliters per Hectare TU Volume per 1 000 Square Feet GPK Gallons per 1 000 Sq...

Page 9: ...6 pounds 32 N 1 U S gallon 11 65 pounds 10 34 0 Length Pressure 1 millimeter mm 0 039 inches 1 psi 6 89 kPa 1 centimeter cm 0 393 inches 1 kPa 0 145 psi 1 meter m 3 281 feet 1 kilometer km 0 621 miles...

Page 10: ...CHAPTER 1 viii ISO Product Controller II and Hawkeye Operation Manual...

Page 11: ...g product control when a safe working distance has diminished Disable the system prior to starting any maintenance work on the machine or parts of the control system AGRICULTURAL CHEMICAL SAFETY Alway...

Page 12: ...any component of the implement INSTRUCTIONS FOR WIRE ROUTING The word harness is used to mean all electrical leads and cables bundled and unbundled When installing harness secure it at least every 30...

Page 13: ...vice personnel or operators might step or use as a grab bar Damage when passing through metal structures IMPORTANT Avoid directly spraying electrical components and connections with high pressure wate...

Page 14: ...tachments Ground engaging components For hose sections that move during machine operation Allow sufficient length for free movement without interference to prevent pulling pinching catching or rubbing...

Page 15: ...or connections using low pressure water pressurized air or an aerosol electrical component cleaning agent Remove visible surface water from components connections or seals using pressurized air or an...

Page 16: ...CHAPTER 1 6 ISO Product Controller II and Hawkeye Operation Manual...

Page 17: ...llowing aspects of the Hawkeye nozzle control system Initial Setup and Navigation Calibration Hawkeye System Operation Hawkeye Operation When Used With Direct Injection Updating Hawkeye Components NOT...

Page 18: ...to monitor the flow through the flow through the system and adjust a control valve to maintain target application rate This allows the operator to turn on and off sections and change vehicle speeds w...

Page 19: ...Nozzle Control Valve Diagnostic Definitions on page 53 for additional information on Wheel Tracks VIRTUAL SECTIONS Whether one section or ten the Hawkeye Virtual Section feature will automatically div...

Page 20: ...chemical residues or build up by flushing the system with soap and water 3 Prime the system plumbing with a 50 water and automotive antifreeze mixture to prevent freezing of NCV components Freezing wi...

Page 21: ...shape the future of our product documentation and the overall service we provide We appreciate the opportunity to see ourselves as our customers see us and are eager to gather ideas on how we have be...

Page 22: ...CHAPTER 2 12 ISO Product Controller II and Hawkeye Operation Manual...

Page 23: ...features TRANSFERRING UT S When multiple UT s are detected on the system a Transfer UT softkey will appear Use this button to transfer the PCII working set to an alternate UT at any point before duri...

Page 24: ...atch the expected number of nozzle control valves connected to the system refer to Chapter 8 Troubleshooting for assistance with the Hawkeye nozzle control valve circuit 2 The Hawkeye Product Controll...

Page 25: ...matic indexing process completes 2 Enable the fence row option if fence row valves are connected to the system Select the Enable On Screen Buttons box to control fence row valves through the on screen...

Page 26: ...d press the Next button to proceed to the meter cal prompt METER CAL AND UNITS 1 Select the Meter Cal field and enter the calibration value for the flow meter used to monitor the Hawkeye system produc...

Page 27: ...sed so it is easier to observe the stream from each nozzle While driving at a speed between 5 and 10 mph 8 and 16 km h and maintaining a safe working distance observe the inner most and outer most spr...

Page 28: ...Injection system or features INJECTION WIZARD 1 Turn the UT power on and allow the display to power up and initiate the ISOBUS system NOTE If properly connected and powered the UT will automatically d...

Page 29: ...Controller II ECU serial number The serial number is typically located on the front or top of the direct injection pump 8 Assign the desired Sidekick Pro ICD Product Controller II ECU to the desired p...

Page 30: ...duct Controller II and Hawkeye Operation Manual FIGURE 7 Product Controller II ECU Desired Target Rate NOTE For more information on setup and operation of Sidekick Pro ICD pumps refer to the Sidekick...

Page 31: ...estart the injection or Hawkeye System Calibration wizards System Settings Adjust the following setting and feature categories for the main product or any of the injection products Product Controller...

Page 32: ...r desired to change modes in the field close the job change the mode and then re open the job SECTION CONTROL MODE Use the Section Control drop down field to select the section control mode Virtual Bo...

Page 33: ...m default settings Refer to System Information Tab section on page 38 for assistance with restoring default system settings INJECTION WIZARD Select the Injection Wizard button to re assign the Sidekic...

Page 34: ...configuration FENCE ROWS DISPLAY Fence rows are only available if calibrated as a sprayer If fence rows are enabled the operator may use the left and right fence row switches to toggle fence row valv...

Page 35: ...eld close the job change the mode and open the job again To disable nozzle control 1 Open the UT Menu and select the Hawkeye Menu button 2 From the home screen select the Tools Menu softkey along the...

Page 36: ...If the UT is not capable of automatic section control Hawkeye will not automatically control sections regardless of the state of the section control feature on this screen It is recommended to de sele...

Page 37: ...is 15 seconds The override seconds valve can only be changed outside of a job from this location If the user desired to change this value while in a job use the on screen override widget on the Viper...

Page 38: ...zle Control mode if three or more injection pumps are present or when the system is toggled in Manual application mode BOOM RECIRCULATION NOTE Turn on an output from the ECU that can open a valve to r...

Page 39: ...tank volume for a known volume of product added to the tank Either enter the volume manually upon refilling or use the tank flowmeter to automatically monitor the tank level LOW TANK LIMIT Enable the...

Page 40: ...ficiency limit feature allows the user to monitor system performance The system will display an alarm in the actual efficiency exceeds the ideal efficiency by more than the set percentage Typical effi...

Page 41: ...essure presets to allow the equipment operator to quickly switch between the set pressures during field operations in the automatic product control mode Pressure presets are disabled in some nozzle co...

Page 42: ...this feature is disabled SYSTEM SETTINGS TAB PRODUCT CONTROL To access the Product Control Settings Menu 1 Open the UT Menu and select the Hawkeye Menu button 2 Select the Tools Menu softkey along the...

Page 43: ...rease this value until the minimum desired spray pattern is reached in the liquid system The default value is 25 NOTE To help avoid under application or skips in coverage review Avoiding Skips with Ha...

Page 44: ...ture requires a pressure transducer to monitor product pressure during application and will allow the operator to set the lowest tolerable pressure during field operations If the application system re...

Page 45: ...boom pressure transducer if present to a known value The system will calibrate this automatically during the calibration wizard but the value can be adjusted at any time Calibrate to a known pressure...

Page 46: ...ics Info tab along the top of the display The following controller information will be displayed DTC List The diagnostic trouble code DTC list provides a list of recent errors for the equipment operat...

Page 47: ...umber is used to calibrate the system gyro for turn compensation Pressure Signal Displays pressure signal as a voltage from the boom pressure transducer The value should be not be zero when the boom i...

Page 48: ...rmation will be available NOTE This information is for display purposes only and may be useful when contacting technical support WIRELESS Shows the status of the connected wireless device Unknown will...

Page 49: ...rming a software update record all settings in the Calibration Reference Sheet on page v After the update is complete reset the system defaults and recalibrate the system FEATURE UNLOCKS Unlocks allow...

Page 50: ...CHAPTER 4 40 ISO Product Controller II and Hawkeye Operation Manual...

Page 51: ...is equipped with a master tank valve verify the tank valve is open to direct flow to the carrier pump 8 If the machine is equipped with a toggle switch to engage the pump it may be necessary to engag...

Page 52: ...additional switch to open a master tank valve and or turn on the main product pump ensure the machine s switch is turned on before the on screen softkey is used and the master switch is toggled on to...

Page 53: ...eset softkeys MAIN PUMP MANUAL CONTROL In the manual control mode the rate bump and preset softkeys are replaced with manual pump buttons Select these softkey to manually increase or decrease the main...

Page 54: ...iagnostics prompts NOTE This button also indicates the nozzle control mode The images below show the nozzle control mode HAWKEYE UPPER HOME SCREEN The upper portion of the Hawkeye home screen displays...

Page 55: ...he Flow Meter Maintenance section on page 99 for additional assistance with calibrating the flow meter If the Use Gauges to Toggle Quick Key Selection option is enabled touch the rate gauge to toggle...

Page 56: ...73 are for reference purposes only Actual speed ranges will depend on the main product pump performance system plumbing configurations and specific spray tip flow characteristics Displayed speed rang...

Page 57: ...Home Screen FIGURE 6 Injection Lower Home Screen PRODUCT SELECTS Product Selects shows the target application rate if the product is calibrated and the product is toggled on and the actual rate for e...

Page 58: ...red to allow the tank volume indicator to display the tank level VOLUME APPLIED Volume applied is for quick reference of the volume of product dispensed during a field operation The field volume tally...

Page 59: ...view the Raven ISOBUS Switch Box Operation Guide for additional assistance with the Raven ISO Switch Box Use the manual section control buttons at the bottom of the Hawkeye home screen to manually ena...

Page 60: ...ected NCV duty cycle at a given target rate pressure and tip size Examples include when there is a leak tip size is programmed too large flowmeter calibration value is too low pressure calibration val...

Page 61: ...G A REGISTER To reset a register 1 Open the UT Menu and select the Hawkeye Menu button 2 From the home screen select the Tally Registers softkey along the right side of the display 3 On the Totals Dat...

Page 62: ...and volume statistics register keeps a running tally of the operating life of the Hawkeye system This tally cannot be reset by the machine operator DISTANCE The distance register functions as a Hawke...

Page 63: ...ON DISPLAY The current section for which diagnostic information is being displayed is shown at the top of the nozzle diagnostics prompt Select the left or right section select arrow buttons to cycle t...

Page 64: ...e Individual Nozzle Diagnostics section on page 54 for additional information NOTE NCV offset percentage entries greater than zero will provide additional softkey options that allow use of flow offset...

Page 65: ...te in a turn and when a flow offset is enabled Values go to zero when master switch or all boom switches are off Estimated Flow The estimated flow rate through each nozzle is reported to the Hawkeye m...

Page 66: ...the diagnostics prompt Offline Count Offline Count indicates the number of times the NCV stopped communicating This number resets when the power PCII ECU power cycles Flow Offset Enable Wheel Tracks...

Page 67: ...res calibration Blue Actuating Mode Auto Red Loading New Software Amber Alarm Active 5 Hz Amber No ISOBUS Communication Alternating 1 Hz Blue Green Actuating Mode Manual Green Magenta Not Calibrated S...

Page 68: ...equire NCV s to be recalibrated Disconnect the boom cable from the nozzle control valve Hold the connector so that the retention clip is facing toward the 12 o clock position FIGURE 2 Nozzle Control V...

Page 69: ...the keyway is facing toward the 12 o clock position Pin Description Pin Description 1 Chassis Power 10 5 16 0 VDC 6 Chassis Ground 0 VDC 2 CAN High 2 0 2 7 VDC 5 Switch In 8 0 13 0 VDC coming from PCI...

Page 70: ...System Settings tab along the top of the display and select the Product Control Settings button 4 Enter a value of one for the Meter Cal value 5 Select the Home softkey along the right side of the di...

Page 71: ...y and correct issues with system during field operations Code ID Description Recommended Actions 10 13 UT display is not on line 1 If this error occurs frequently check the ISOBUS connections and revi...

Page 72: ...Check for nozzle control valve software version differences Update the nozzle control valves to a consistent software version Refer to the Raven Service Tool Operation manual for assistance with the...

Page 73: ...imum pressure set point 16 Monitored system pressure higher than the target pressure deadband 1 Reduce the equipment speed 2 Refer to the Pressure 1 and 2 Presets section on page 31 for assistance wit...

Page 74: ...t in the diagnostics information tab 3 Check LED lights on the NCV s Hawkeye Nozzle Control Valve Status section on page 57 4 Check the NCV s connections relays cables and fuses for damage 5 Recalibra...

Page 75: ...e control system 3 Cycle system power and reset defaults 31 No NCV tip size selected 1 Enter a NCV tip size into the calibration summary tab 523009 2 Nozzle calibration spacing mismatch error 1 Restar...

Page 76: ...ng position and verify the Product Controller II ECU is securely mounted 2 Recalibrate the Product Controller II ECU gyro 523136 16 Monitored flow rate is higher than the target rate deadband 1 Reduce...

Page 77: ...ow the speed range single nozzle 1 Increase equipment speed to the range displayed on the Hawkeye home screen Refer to the Hawkeye Upper Home Screen section on page 44 and Hawkeye Lower Home Screen se...

Page 78: ...ue is not resolved 523915 31 Nozzle Product Controller II ECU no master multiple 1 Verify the NCV voltage is above 10 5v 2 Check the system cabling for damage 3 Contact a local Raven dealer if the iss...

Page 79: ...s securely mounted 1 Recalibrate the Product Controller II ECU gyro 31 Chemical tank is filling 1 The remote chemical tank fill switch is active Section control is not unlocked 1 Verify section contro...

Page 80: ...ol Settings menu decrease response sensitivity if system pressure and rate oscillate slightly in AUTO mode Increase if the system is unresponsive Avoid Pressure Response Rate and Product Response Sens...

Page 81: ...or the transducer is selected In Pressure Settings lower the Response Rate to stabilize the system Verify the pressure on UT matches separate external mechanical gauge Individual nozzle will not commu...

Page 82: ...ice Diagnostic app is open Cannot control with mobile device Verify mobile device is connected to Product Controller II ECU Verify the Enable Wireless Control checkbox is selected in User Settings scr...

Page 83: ...150 pattern overlap a When using 80 spray tips 20 spacing have a minimum spray tip height of 36 91 4 cm 15 spacing have a minimum spray tip height of 27 68 6 cm 10 spacing have a minimum spray tip hei...

Page 84: ...nches 53 3 cm FIGURE 1 Alternating Spray Pattern and Even Area Coverage NOTE In Automatic control mode the Hawkeye nozzle control system will adjust the system to maintain the optimal application cove...

Page 85: ...ere to toggle the application mode from Automatic to Manual and then increase the application speed from 15 mph 24 1 km h to 22 mph 35 4 km h without manually increasing the nozzle control valve duty...

Page 86: ...rn NOTE Refer to Recommendations for Hawkeye Nozzle Control Operation section on page 73 and recall the recommended spray height for 80 spray tips Refer to Tip Selection and Application Speed Guide se...

Page 87: ...e a 06 or 08 tip At 40 PSI either tip would create the desired droplet size TABLE 1 Nozzle Drift Control by Manufacturer Tip Size Boom Pressure PSI Wilger www wilger net TeeJet www teejet co m Hypro w...

Page 88: ...are based on 20 nozzle spacing 08 20 C C VC UC VC VC C C 30 C XC XC XC C VC UC C C M C 40 C VC XC XC M C UC C C M M 50 C VC XC XC M C UC C C M M 60 C C VC XC M C XC C C M M 10 30 C XC XC UC C UC C VC...

Page 89: ...11 7 35 8 7 0 21 5 4 4 13 4 3 5 10 7 2 3 7 2 1 7 5 4 04 20 0 9 5 27 2 5 7 16 3 3 6 10 2 2 9 8 2 1 9 5 4 1 4 4 1 30 0 11 1 33 3 6 6 20 0 4 1 12 5 3 3 10 0 2 2 6 7 1 7 5 0 40 0 12 3 38 5 7 4 23 1 4 6 1...

Page 90: ...8 3 2 8 6 2 1 9 4 2 1 6 3 6 200 10 3 24 9 6 2 14 9 4 1 10 0 3 1 7 5 2 1 5 0 1 8 4 3 275 11 4 29 2 6 8 17 5 4 6 11 7 3 4 8 8 2 3 5 8 2 0 5 0 350 12 3 32 9 7 4 19 7 4 9 13 2 3 7 9 9 2 5 6 6 2 1 5 6 400...

Page 91: ...40 1 144 2 24 1 86 5 16 1 57 7 12 0 43 3 8 0 28 8 5 9 24 7 400 42 6 154 2 25 6 92 5 17 1 61 7 12 8 46 3 8 5 30 8 7 3 26 4 12 5 200 35 9 127 1 21 5 76 3 14 4 50 9 10 8 38 1 7 2 25 4 6 2 21 8 275 41 4 1...

Page 92: ...APPENDIX A 82 ISO Product Controller II and Hawkeye Operation Manual...

Page 93: ...the Product Controller II ECU with various UT displays These generic diagrams are good examples for both factory and after market installations Refer to equipment specific drawings and installation ma...

Page 94: ...APPENDIX B 84 ISO Product Controller II and Hawkeye Operation Manual FIGURE 2 Generic Cabling for Pull Type Sprayer Option 2...

Page 95: ...P N 016 0171 584 H 85 FIGURE 3 Generic Cabling for Self Propelled Sprayer...

Page 96: ...APPENDIX B 86 ISO Product Controller II and Hawkeye Operation Manual FIGURE 4 Generic Cabling for Self Propelled Sprayer with Existing Raven CAN...

Page 97: ...P N 016 0171 584 H 87 FIGURE 5 Generic Cabling for Pull Type Sprayer with Existing Raven CAN...

Page 98: ...APPENDIX B 88 ISO Product Controller II and Hawkeye Operation Manual FIGURE 6 Generic Cabling for Pull Type Sprayers with Existing IBBC Connections...

Page 99: ...P N 016 0171 584 H 89 FIGURE 7 20 Spacing Generic Cabling...

Page 100: ...ISO Product Controller II and Hawkeye Operation Manual FIGURE 8 Generic Nozzle Control System Connection Diagram Cable Primary Left Cable Primary Right Secondary Cable Nozzle Terminator Secondary Cab...

Page 101: ...inches 356 cm Enter 140 356 as the width for this section EQ 1 TARGET RATE CALIBRATION The following information must be known in order to determine which spray nozzles to use with the sprayer Nominal...

Page 102: ...e if the system pressure and rate oscillate slightly Increase sensitivity if control is unresponsive Avoid setting response rate and sensitivity above 70 The default value is 50 DEADBAND The deadband...

Page 103: ...urely tied to the boom cables System Rinse Daily after use 1 Ensure the main product tank is cleaned and filled with at least 100 gallons of fresh water or that the pump is drawing fresh water from th...

Page 104: ...mical has been flushed from the system 6 Turn Off the master switch and product pump Verify the valve positions are set for the next application Walk Around Inspection of System Cables and Components...

Page 105: ...1005 003 5 Outlet Seal 219 1005 001M 6 O Ring 219 1005 115M 2 3 5 6 Replacement Seal Kit Quantity of 100 117 1005 211 1 2 3 5 6 Single NCV Seal Replacement Kit Quantity of 1 117 1005 051 063 0173 810...

Page 106: ...05 210 1 2 3 5 6 Single NCV Seal Replacement Kit Quantity of 1 117 1005 050 Wilger 063 0173 674 1 Fly Nut 117 1005 215 2 Plunger Assembly N A 3 O Ring N A 4 Stainless Valve Body 107 1005 002 5 Outlet...

Page 107: ...l 1 Loosen the fly nut item 1 and remove the Hawkeye nozzle control valve from the nozzle body 2 Inspect the large o ring item 6 on the face of the valve body item 4 Replace if necessary 3 Inspect the...

Page 108: ...assembly item 2 into nozzle control valve cavity 4 Thread the valve body onto the nozzle control valve and finger tighten 5 Using a valve body removal tool P N 321 0000 457 turn valve body 1 4 to 1 3...

Page 109: ...OTE Remove system pressure and chemical from the hoses and all other system lines prior to disassembling the flow meter fittings or hoses 1 Remove flow meter from the equipment and flush with clean wa...

Page 110: ...the calibration number stamped on the tag of the flow meter 13 Repeat this procedure several times to confirm accuracy Always zero out the total volume display before retesting NOTE For increased pre...

Page 111: ...P N 016 0171 584 H 101...

Page 112: ...APPENDIX D 102 ISO Product Controller II and Hawkeye Operation Manual...

Page 113: ...Hawkeye boom cable to the Hawkeye Nozzle Control Valves NCV perform the following steps to all 6 pin NCV connectors and 19 pin circular connectors between the boom cables and Product Controller II ECU...

Page 114: ...ebris 5 Remove all residue of deoxidizing agent from the connection Not removing deoxidizing agent can damage the connector seal 6 Dry out the connection with dry compressed air Dust Off Electronics D...

Page 115: ...www corrosionx com corrosionx heavy duty html into the NCV connection Be sure the corrosion inhibitor has coated the NCV contacts and recessed portions of the connector NOTE To determine is corrosion...

Page 116: ...APPENDIX E 106 ISO Product Controller II and Hawkeye Operation Manual...

Page 117: ...y that 80 mesh or finer screens are installed upstream of the Hawkeye nozzle control valves 2 Flush the boom plumbing and tank before running liquid through the Hawkeye nozzle control valves 3 Ensure...

Page 118: ...should respond to the corresponding boom sections in the UT window No triangle means the boom is off An empty triangle indicates the boom is active but is being controlled by Accuboom A triangle fille...

Page 119: ...nd 16 km h and maintaining a safe working distance observe the inner most and outer most spray tips while the implement is turning sharply NOTE The nozzle PWM percent value may also be used to monitor...

Page 120: ...APPENDIX F 110 ISO Product Controller II and Hawkeye Operation Manual...

Page 121: ...Hawkeye Flowchart 111 APPENDIXGHAWKEYE FLOWCHART HAWKEYE FLOWCHART This section provides a flowchart of the Hawkeye screens and may be useful for navigating though the UT The flowcharts start on the...

Page 122: ...APPENDIX G 112 ISO Product Controller II and Hawkeye Operation Manual FIGURE 1 Hawkeye Screen Flow Tools Menu Softkey...

Page 123: ...P N 016 0171 584 H 113 FIGURE 2 Hawkeye Screen Flow Tools Menu Softkey Continued Press OK on any of the settings screens to return to the System Settings...

Page 124: ...APPENDIX G 114 ISO Product Controller II and Hawkeye Operation Manual FIGURE 3 Hawkeye Screen Flow Tools Menu Softkey Continued...

Page 125: ...P N 016 0171 584 H 115 FIGURE 4 Hawkeye Screen Flow Tally Registers and Diagnostics Menu Softkeys...

Page 126: ...APPENDIX G 116 ISO Product Controller II and Hawkeye Operation Manual FIGURE 5 Hawkeye Injection Screen Flow Diagnostics Information and Calibration...

Page 127: ...P N 016 0171 584 H 117 FIGURE 6 Hawkeye Injection Screen Flow Product Setup Alarms and System Information...

Page 128: ...APPENDIX G 118 ISO Product Controller II and Hawkeye Operation Manual...

Page 129: ...rgy compatible device To use the diagnostics application System speed must be zero The application must be connected to PC II The Enable Wireless Control check box must be checked in the PC II User Se...

Page 130: ...Control checkbox in the User Settings screen Any time the Enable Wireless Control box is unchecked or the boom and master switches are in the wrong position Control Disabled will display on the app AP...

Page 131: ...play on the UT screen If the Product Controller II ECU Wireless ID has already been connected no passcode is required and the application will automatically switch to the next page NOTE Only one Produ...

Page 132: ...cation is not controlling the sections Possible issues could be the master switch is off wireless control is disabled or actual speed detected Turn the section to the left on Turn product pump on off...

Page 133: ...P N 016 0171 584 H 123 Turn product pump off Section Status Green border indicates on Gray border indicates off Icon Function...

Page 134: ...APPENDIX H 124 ISO Product Controller II and Hawkeye Operation Manual...

Page 135: ...ion Wizard and Calibration 18 Introduction Unit Definitions and Conversions vi Unit of Measure Conversions vi Unit of Measure Definitions vi M Manual Section Controls 49 Master Switch Status 48 Max Ta...

Page 136: ...e 91 Target Pressure 46 Target Rate 45 Testing Flow Meter Cables 59 Testing for Leaks 99 Testing NCV Cable Connections 58 Tip Selection and Application Speed Guide 77 Tip Size Option 23 Toggle Nozzle...

Page 137: ...r s responsibility The Return Materials Authorization RMA number must appear on the box and all documentation including proof of purchase must be included inside the box to be sent to Raven Industries...

Page 138: ...claim and send it to Raven Industries for final approval The freight cost to Raven Industries will be the customer s responsibility The Return Materials Authorization RMA number must appear on the box...

Reviews: