Use and maintenance manual
HRV 180 PLUS
Page 17
Rev.2 04/12/2020
EN
Set-ups for the smoke evacuation system
Be careful when building the smoke evacuation system and observe the regulations in force in the country where
the stove is installed.
! IMPORTANT
The Manufacturer will not be held liable for incorrectly sized and non-regulation smoke
evacuation systems.
Smoke ducts and fittings
The term smoke duct indicates all ducts that connect the combustion equipment to the chimney.
The following requirements need to be applied:
•
observe product standard EN 1856-2;
•
the horizontal sections must have a minimum slope of 3% upwards;
•
the length of the horizontal section must be as minimum as possible, and its projection on the horizontal plane must not exceed
2 metres;
•
changes in direction must not have an angle of more than 90° (45° bends are recommended);
•
the number of direction changes, including the one necessary for insertion into the chimney, must not exceed 3;
•
the cross section must have a constant diameter, the same from where it exits the firebox up to the fitting into the chimney;
•
it is forbidden to use flexible metal and fibre cement pipes;
•
smoke ducts must not cross rooms where the installation of combustion equipment is prohibited.
In any case, the smoke ducts must be sealed against combustion products and condensation, as well as insulated if they lead outside
of the installation room.
Installing manual draught adjustment devices is not allowed.
! IMPORTANT
Creating an initial straight vertical smoke duct section of at least 1 m to ensure proper
smoke ejection is mandatory.
Chimney
The chimney is a particularly important element for correct stove operation.
The chimney must be sized so as to guarantee the draught declared by the Manufacturer.
Do not connect the stove to a collective chimney.
.
The chimney must be built applying the following regulations:
•
it must observe product standard EN 1856-1;
•
it must be made of materials that are suitable to guarantee resistance against normal mechanical, chemical and thermal stress
and be correctly thermally insulated to limit the formation of condensation;
•
it must be mainly vertical and not feature any bottlenecks along its entire length;
•
it must be correctly spaced with an air gap and insulated from flammable materials;
•
there must be a maximum of 2 changes in direction and angles must not exceed 45°;
•
the chimney inside the home, however, must be insulated and can be inserted into a skylight shaft, as long as it respects
standards regarding placing inside a tube;
•
the smoke conduit must be connected to the chimney using a "T" fitting with an inspection collection chamber for combustion
residue and especially for collecting condensation.
! IMPORTANT
It is necessary to check the safety distances that need to be observed when there are
flammable materials and the type of insulating material that needs to be used is on the
chimney data plate.
Use watertight pipes with silicone seals.
It is forbidden to use the discharge mounted directly on the wall or directed towards indoor spaces and any other
type of discharge that is not set forth by the regulation in force in the country of installation (Note: in Italy only
roof-discharge is allowed).
Chimney pot
The chimney pot, i.e. the top end of the chimney, must fulfil the following characteristics:
•
the cross-section of the smoke outlet must be at least twice the internal cross-section of the chimney;
•
it must stop water or snow from getting in;
•
make sure the smoke is taken away even when there is wind (wind resistant chimney pot);
•
the outlet height must be outside of the reflux zone (refer to national and local regulations to calculate the reflux zone);
•
it must always be built at a distance from antennas or dishes, it must never be used as support.
Summary of Contents for HRV 180 PLUS
Page 2: ...HRV 180 PLUS MANUALE D USO E MANUTENZIONE...
Page 3: ......
Page 17: ...Manuale uso e manutenzione HRV 180 PLUS Pag 16 Rev 2 04 12 2020 ITA 1 2 3 4 5 6...
Page 47: ...DATE WORK PERFORMED MAINTENANCE...
Page 48: ...DATE WORK PERFORMED MAINTENANCE...
Page 50: ...HRV 180 PLUS MANUEL D UTILISATION ET D ENTRETIEN...
Page 51: ......
Page 55: ......
Page 65: ...Manuel d utilisation et d entretien HRV 180 PLUS Page 16 Rev 2 04 12 2020 FR 1 2 3 4 5 6...
Page 92: ......
Page 95: ...DATE WORK PERFORMED MAINTENANCE...
Page 96: ...DATE WORK PERFORMED MAINTENANCE...
Page 98: ...HRV 180 PLUS USE AND MAINTENANCE MANUAL...
Page 99: ......
Page 103: ......
Page 112: ...Use and maintenance manual HRV 180 PLUS Page 15 Rev 2 04 12 2020 EN 1 2 3 4 5 6...
Page 141: ...DATE WORK PERFORMED MAINTENANCE...
Page 142: ...DATE WORK PERFORMED MAINTENANCE...
Page 143: ......
Page 144: ......
Page 146: ...HRV 180 PLUS BEDIENUNGS UND WARTUNGSHANDBUCH...
Page 147: ......
Page 151: ......
Page 160: ...Bedienungs und Wartungshandbuch HRV 180 PLUS S 15 Rev 2 04 12 2020 DE 1 2 3 4 5 6...
Page 188: ......
Page 191: ...DATE WORK PERFORMED MAINTENANCE...
Page 192: ...DATE WORK PERFORMED MAINTENANCE...
Page 194: ...HRV 180 PLUS MANUAL DE USO Y MANTENIMIENTO...
Page 195: ......
Page 199: ......
Page 208: ...Manual de uso y mantenimiento HRV 180 PLUS P g 15 Rev 2 04 12 2020 ES 1 2 3 4 5 6...
Page 237: ...DATE WORK PERFORMED MAINTENANCE...
Page 238: ...DATE WORK PERFORMED MAINTENANCE...
Page 239: ......
Page 240: ......