6. Installation
Step-by-step checklist
1.
Mount RipEX into cabinet (Section 6.1, “Mounting”).
2.
Install antenna (Section 6.2, “Antenna mounting”).
3.
Install feed line (Section 6.3, “Antenna feed line”).
4.
Ensure proper grounding (Section 6.4, “Grounding”).
5.
Run cables and plug-in all connectors except from the SCADA equipment (Section 4.2, “Connect-
ors”).
6.
Apply power supply to RipEX
7.
Connect configuration PC (Section 5.3, “Connecting RipEX to a programming PC”).
8.
Configure RipEX (Chapter 7,
9.
Test radio link quality (Section 5.5, “Functional test”).
10. Check routing by the ping tool (Section 7.6.3, “Ping”) to verify accessibility of all IP addresses with
which the unit will communicate.
11. Connect the SCADA equipment.
12. Test your application.
Note – hazardous locations
Installation in hazardous locations has to be done according to standard
EN 60079-25 Explosive atmospheres Intrinsically safe electrical systems.
6.1. Mounting
6.1.1. DIN rail mounting
The radio modem RipEX is directly mounted using clips to the DIN rail. The mounting can be done
lengthwise (recommended) or widthwise; in both cases with the RipEX lying flat. The choice is made
by mounting the clips, one M4 screw per clip. RipEX is delivered with two clips, two screws and four
threaded holes. Only use the M4×5 mm screws that are supplied. Use of improper screws may result
in damage to the RipEX mainboard!
Fig. 6.1: Flat lengthwise mounting to DIN rail – recommended
85
© RACOM s.r.o. – RipEX Radio modem & Router
Installation