Revision: 05
5.2-6/11
154-625-2
5.2.7 Setting with the Windows
®
software (RACO Setup Tool)
Attention:
The EPS02 is factory set when delivered enclosed at an electric actuator (
unless otherwise specified
in the order, the final positions are usually set on both sides for maximum stroke length minus a stroke
reserve
),
including the system-dependent rotation and the transmission ratio
.
Caution when changing parameters, particularly the system-dependent parameters in order to avoid
malfunction and damage!
Before changing the original parameter date, save the data file and store it at a save place for using
this file in an emergency case to get the original state again. In a further file save the data set with the
changes which were made at site.
Procedure for saving data sets:
-
Over the button "Read Parameter Block" read the parameters into the RACO Setup Tool.
-
Select in the menu bar under "Values", "Save to File".
-
Assign a file name and save the file.
To restore a saved data set, proceed as follows:
-
Select in the menu bar under "Values" "Read from file".
-
Select the desired parameter data set and open it.
-
Over the button "Send Parameter Block", the parameters will be written to the EPS02.
To configure all functionality, a Windows
®
software (RACO Setup Tool) is provided, which allows all
settings conveniently. To change the parameters, after a successful connection to the PC, the param-
eters are first read from the EPS02 via the button "Read parameter block" in the RACO Setup Tool.
Modified parameters are restored via the "Send parameter block" in the EPS02.
Summary of Contents for 1190642-0010
Page 3: ...2 2 Operating Instructions Compact Size 2 ...
Page 21: ...3 2 Maintenance Instruction Size 2 Compact 2 7 ...
Page 25: ...4 2 Description of the RACO Motor Size 2 ...
Page 31: ...5 2 Description Position Sensoric EPS02 ...
Page 43: ...5 2 1 Wiring Example EPS 02 ...
Page 46: ...8 1 EC Installation Declaration ...
Page 47: ......
Page 48: ...8 2 Dimensional drawing ...