is charging and this level is crossed certain actions will be performed automatically.
UPS Recovery Power Threshold
The powered outlets and outlets marked as AlwaysOn with respective power
consumptions below the recovery power threshold (in W) will be power cycled when the
UPS is running on mains power and the battery level goes above the Battery Recovery
Threshold (assuming that the battery level dropped below the Battery Emergency
Threshold first). For more information see the Rules chapter.
SNMP Warning
o
Checked: SNMP traps will be sent when:
UPS Communication status changes
UPS switches between battery or mains
UPS Emergency Threshold is crossed
UPS Recovery Threshold is crossed
o
Unchecked: No SNMP traps are sent
To enable the EnergySwitch to perform actions based on the UPS Integration data please also
refer to the Agent Communication chapter.
Rules
If both UPS Integration is enabled and Agent Communication is correctly configured the
EnergySwitch will perform automated actions
according to strict pre-defined rules (based on
battery level, UPS status, etc.).
Please review the following rules and actions carefully to avoid unexpected behavior.
1.
When the EnergySwitch boots, communication with the UPS is OK and the
Battery Level
is above the
UPS Recovery Threshold
the outlets will be powered as configured by the
user.
2.
When the EnergySwitch boots, communication with the UPS is OK and the
Battery Level
is below the
UPS Recovery Threshold
only outlets marked with
Prevent Outlet
Shutdown
(see the EnergySwitch Configuration chapter) will be powered.
3.
When the EnergySwitch boots and communication with the UPS fails, only outlets
marked with
Prevent Outlet Shutdown
will be powered.
4.
When the UPS is running on battery and the
Battery Level
drops below the
UPS
Emergency Threshold
the EnergySwitch will send a
shutdown
command to all associated
agents.
5.
When the communication with the UPS fails for 5 minutes a
shutdown
command is sent
to all associated agents of powered outlets.
6.
When the UPS switches from mains to battery power while the
Battery Level
is below
the
UPS Emergency Threshold
a
shutdown
command is sent to all associated agents of
powered outlets.