EN
.
43
Parameter no. 78
–
Scale Selection
This parameter determines in which measurement unit the device will report temperature
(Fahrenheit or Celsius) and determines the scale the configuration parameters (43, 44, 44, 45,
60, 61, 110, 120) are interpreted as.
Values (size is 1 byte dec):
•
Default value 0 = degrees Celsius
•
0 = degrees Celsius
•
1 = degrees Fahrenheit
NOTE1: This scale has influence on Temperature reporting. The device is capable of receiving a
Set point in all supported scales.
NOTE2: This configuration parameter has impact on configuration parameters 43, 44, 44, 45,
60, 61, 110, 120. If scale is set to degrees Fahrenheit configuration values at parameters 43, 44,
44, 45, 60, 61, 110, 120 will be converted to degrees Celsius. Please note that converted values
could drift when converting values back and forth.
Parameter no. 110
–
Temperature Sensor Offset Settings
Set value is added to or subtracted from the actually measured value to adjust the temperature
report sent by an external sensor.
Values (size is 2 byte dec):
•
default value 0
•
-270 - 270
NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is
-150
–
150 (-15.0
°C –
15.0
°C, resolution 0.1
°C)
NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is
-270 - 270 (-27.0
°F –
27.0
°F, resolution 0.1
°F)
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit
values will be converted to Celsius degrees. Due to conversion algorithm please be advised that
configuration value could drift when converting values back and forth.