Installation
Prevent Electrostatic Discharge
The module is sensitive to electrostatic discharge.
WARNING!
Electrostatic discharge can damage integrated circuits or
semiconductors. Follow these guidelines when you handle the module:
•
Touch a grounded object to discharge static potential
•
Do not touch the connector pins
Power
AN-X requires a DC power input of anywhere from 12 to 24 VDC.
Left to right the pins on the power connector are chassis ground, negative
voltage and positive voltage.
The chassis ground should be connected.
Power consumption is 300 mA @ 12VDC or 150 mA @ 24VDC.
The part number for the power connector is Phoenix MSTB
2.5/3-ST-5.08
Contact QTS if you need a suitable wall adapter.
Cabling and Termination
Refer to the Simatic TI545/TI555 System Manual, publication
PPX:545/555–8101-2 for detailed information on cabling and
installation.
The module has a standard 9-pin connector for connection to the remote
I/O network. The AN-TI-MAS is wired just like a TI scanner. Follow