Page
40
AN-X-TI-MAS
November 2011
ALIAS,"","TI_b01s03wx_00","TI_ Base 1 Slot 3 8wx Module (Word
0)","","TImaster:0:I.Data[3]"
ALIAS,"","TI_b01s03wx_01","TI_ Base 1 Slot 3 8wx Module (Word
1)","","TImaster:0:I.Data[4]"
ALIAS,"","TI_b01s03wx_02","TI_ Base 1 Slot 3 8wx Module (Word
2)","","TImaster:0:I.Data[5]"
ALIAS,"","TI_b01s03wx_03","TI_ Base 1 Slot 3 8wx Module (Word
3)","","TImaster:0:I.Data[6]"
ALIAS,"","TI_b01s03wx_04","TI_ Base 1 Slot 3 8wx Module (Word
4)","","TImaster:0:I.Data[7]"
ALIAS,"","TI_b01s03wx_05","TI_ Base 1 Slot 3 8wx Module (Word
5)","","TImaster:0:I.Data[8]"
ALIAS,"","TI_b01s03wx_06","TI_ Base 1 Slot 3 8wx Module (Word
6)","","TImaster:0:I.Data[9]"
ALIAS,"","TI_b01s03wx_07","TI_ Base 1 Slot 3 8wx Module (Word
7)","","TImaster:0:I.Data[10]"
The ControlLogix data address in the first example is
TImaster:0:I.Data[2]
.
The address is made up of the ClxName and the data location.
Comments
The tag file contains comments for data points for which there are no
aliases, such as the diagnostic counters. If you view the data points in
RSLogix 5000, the comments are displayed.
Using the ControlLogix Log
If there are problems with scheduled connections to the AN-X, use the
ControlLogix log to identify the cause.
From the web interface, select
Log Files/ControlLogix Log
to display the
log. Look for error messages that describe in detail the cause of any
problem with the current configuration.