AN-X-TI-MAS Page
27
DataOutput ; ,<ClxBaseTag> Outputs from ControlLogix
,b01s02y,b01s02y,; Ofs= 0 Len= 1
,b01s05y,b01s05y,; Ofs= 1 Len= 1
,b01s07y,b01s07y,; Ofs= 2 Len= 1
,b01s10y,b01s10y,; Ofs= 3 Len= 1
; *** WY - TI Word Outputs
,b01s04wy,b01s04wy,; Ofs= 4 Len= 8
,b01s09wy,b01s09wy,; Ofs= 12 Len=16
,b01s10wy,b01s10wy,; Ofs= 28 Len=28
; *** X - TI Discrete Inputs
ClxSlot,0
DataInput ; ,<ClxBaseTag> Inputs to ControlLogix
,BaseErr
,b01s01x,b01s01x,; Ofs= 2 Len= 1
,b01s05x,b01s05x,; Ofs= 3 Len= 1
,b01s06x,b01s06x,; Ofs= 4 Len= 1
,b01s10x,b01s10x,; Ofs= 5 Len= 2
; *** WX - TI Word Inputs
,b01s03wx,b01s03wx,; Ofs= 7 Len= 8
,b01s08wx,b01s08wx,; Ofs= 15 Len=16
,b01s10wx,b01s10wx,; Ofs= 31 Len=14
Program Mode Behaviour
The ControlLogix processor that is the exclusive owner of the connection
in slot 0 controls how the AN-X-TI-MAS module scans the network.
For that reason, when you map the data, you must always include a
connection to the generic module in slot 0.
By default, when the ControlLogix processor with the exclusive owner
connection to slot 0 on the AN-X is in program mode or the connection
is stopped, the AN-X stops scanning the network.
You can override this program mode behaviour by including a line with
the keyword ScanInProg in the configuration file. This causes the
AN-X-TI-MAS module to continue to communicate with the remote I/O
network when the ControlLogix processor is in program mode.