Page
22
AN-X-TI-MAS
November 2011
Begin a base definition with a line that consists of the keyword Base,
followed by an equals sign and then the base number, from 1 to 15.
There should be no spaces before or after the equals sign.
Example:
Base=1
End the base definition with a line with just the keyword EndBase.
Between the Base and EndBase lines, enter the slot definitions for the
base. They consist of the keyword Slot, followed by an equals sign and
the slot number, a comma, then the keyword Type, an equals sign, and
the module type. There should be no spaces before or after the equals
signs.
Examples:
Slot=4,Type=8X
Slot=7,Type=4WY
Refer to page 64 for a list of supported module types.
Sample RIO Configuration File
;QTS AN-X TI MAS Auto Configuration Utility
;Copyright (c) 2008 Quest Technical Solutions
;Auto Config TI MAS File
Base=1
,,Slot=1,Type=8x,;Addr=b01s01, ; 8X 0Y 0WX 0WY
,,Slot=2,Type=16y,;Addr=b01s02, ; 0X 16Y 0WX 0WY
,,Slot=3,Type=8wx,;Addr=b01s03, ; 0X 0Y 8WX 0WY
,,Slot=4,Type=16wy,;Addr=b01s04, ; 0X 0Y 0WX 16WY
,,Slot=5,Type=hdm8x8y4wx4wy,;Addr=b01s05, ; 8X 8Y 4WX 4WY
EndBase
Viewing the Current Configuration
To view the remote I/O configuration currently in AN-X, access the web
interface and select
Automation Network/View Active Configuration
.
You can also view the configuration file by accessing the web interface
and selecting
Automation Network/View Configuration Files
. In some
web browsers, for example Internet Explorer, click on the
AN-X-TI-MAS
Network Configuration File
link and select Open to open the file in
whatever application is associated with CSV files on your computer,
usually a spreadsheet or a text editor. Other browsers just display the file
contents.