Page
34
AN-X3-GENI
January 2024
The statistics for each connection consists of 10 words of data. Only three words in the ten word
block are used.
Offset
Description
0
Average time for last 32 updates
2
Minimum time since the connection statistics were reset
4
Maximum time since the connection statistics were last reset
The units for the times are 0.1 milliseconds. A value of 87 means 8.7 ms.
To map the statistics for a given connection, include a line with the keyword ConnStatsn, where n
is the connection number, from 0 to 15, in the input section of a connection.
Example:
,ConnStats2
Averages are calculated for the last 32 updates.
Connection 15 Mappings
When you autoconfigure the AN-X, it maps the following diagnostics to inputs on connection
15.
Offset
Length
Description
0
2
Block error table
2
8
Connection diagnostics
10
10
Diagnostic counters
20
10
Connextion statistics for connection 0
We recommend that you use the same mappings and do not change them.
Resetting Connection Statistics
To reset the connection statistics, set bit 0 of output word 0 of connection 15. AN-X resets the
statistics on the transition from 0 to 1.