AN-X3-GENI
January 2024
The output length is defined by the keyword Out= and can range from 0 to 128 bytes. If the
output length definition is omitted, the output length defaults to a length of 0.
If the AN-X3-GENI is to control the outputs on a module, include the keyword Scan. If the AN-
X3-GENI is only to monitor the inputs on a module, omit the keyword Scan.
The part number for a module is defined by the keyword Part= and can be from 1 to 15 characters
long. The part number text must be enclosed in double quotes, for example
Part="IC660BBD024".
The description for a module is defined by the keyword Desc= and can be from 1 to 95 characters
long. The description text must be enclosed in double quotes, for example Desc="12/24VDC 32
Ckt Source I/O Block".
The part number and description are used for comments only. You can put whatever you want in
them.
Each definition ends with the keyword EndBlock, which is required.
Parameter
Keyword
Valid entries
Serial bus address
Block=
0-31
Input length, bytes
Inp=
0-128
Output length, bytes
Out=
0-128
Scan mode
Scan
Scan
Part number
Part=
Maximum 15 characters, enclosed in double
quotes
Description
Desc=
Maximum 95 characters, enclosed in double
quotes
End of block definition
EndBlock
Examples:
Block=0,Inp=0,Out=0,,Part="IC660HHM501",Desc="Hand-held Monitor",EndBlock
Block=1,Inp=2,Out=2,Scan,Part="IC660BBR101",Desc="16-Ckt Normally-open Relay Block",EndBlock
When AN-X creates a Genius I/O configuration file after an autoconfiguration, it inserts part
numbers and descriptions from its internal module database.
Global Data Sent by AN-X3-GENI
If the AN-X3-GENI is to send global data on the Genius network, add a line of the form
GlobSend=length