AN-X3-GENI Page
21
Genius Network Configuration
Before you can scan a Genius I/O network, you must set the AN-X module’s serial bus address
(node number) and baud rate and configure the network in the AN-X3-GENI.
Set the baud rate and serial bus address before connecting to the Genius network.
Setting the Bus Address and Baud Rate
From the AN-X web interface, select
Automation Network/Genius Node/Baud Settings
.
Check the desired baud rate from the four supported baud rates: 38.4Kbps, 76.8 Kbps, 153.6
KBPS standard or 153.6 Kbps extended. This setting MUST match the existing Genius network
settings.
Enter the serial bus address (SBA) for the AN-X, in the range 0 to 31. This must be a free node
number on the existing Genius Network.
Click the
Submit Changes
button to set the Genius bus properties of the AN-X3-GENI.