Page
10
AN-X3-GENI
January 2024
Installation
Prevent Electrostatic Discharge
The module is sensitive to electrostatic discharge.
WARNING!
Electrostatic discharge can damage integrated circuits or
semiconductors. Follow these guidelines when you handle the module:
•
Touch a grounded object to discharge static potential
•
Do not touch the connector pins
Power
AN-X requires DC power input of anywhere from 12 to 24 VDC
Left to right the pins on the power connector are chassis ground, negative voltage and positive
voltage. Pin 1 is closest to the Ethernet connector.
The chassis ground should be connected.
Power consumption internally is 200 mA @ 12VDC or 100 mA @ 24VDC.
The part number for the power connector is:
Phoenix 1757022
(Old part number: MSTB 2.5/3-ST-5.08)