INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO BLK-G10+ / HL

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO BLK-G10+ / HL

10

11

2 Planning

2.4 Electrical layout

Module Selection

For detailed key electrical data, please refer to the actual data 

sheet referring to the relevant Module (available at www.qcells.

com).

  For maximum energy yields, mismatches of specified electric 

current (I

MPP

) of more than 5 % should be avoided for all 

modules connected in series.

Safety Factor

During normal operation, a module may generate a greater 

current and / or higher voltage than that determined under 

standardized test conditions. Accordingly, the values of I

SC

 and 

V

OC

 marked on the module should be multiplied by a facot of 1.25 

when determining:

 

the component voltage ratings,

 

conductor ampacities,

 

fuse sizes,

 

size of controls connected to the PV output.

Refer to Section 690-8 of the National Electrical Code for an 

additional multiplying factor of 125 percent (80 percent derating) 

which might be applicable.

  Please follow the valid national guidelines for the installation 

of electrical systems (refer to section 690-8 of the NEC for 

an additional multiplying factor of 125 percent [80 percent 

derating] which may be applicable).

Series Connection

Connection of modules in series is only permitted up to the 

maximum system voltage as listed in the applicable data sheet.

  Take into account all possible operating situations and all 

relevant technical norms and regulations when designing the 

system. This will ensure that the maximum system voltage, 

including all necessary safety margins, is not exceeded.

  Take the voltage limit of the inverter into account when 

determining the maximum number of modules in the string.

Parallel Connection

Modules may be damaged by the occurrence of reverse currents 

(caused by module defects, ground leaks, or defective insulation).

  Ensure that the maximum reverse current load capacity 

indicated in the data sheet is met.

In order to limit reverse currents that may occur, we recommend 

using the following safety options:

1) Layout with a limited number of parallel connected strings :

Without undertaking further current blocking measures, a 

maximum of two module strings may be operated in parallel on a 

single inverter or MPP tracker.

2) Layout with string fuses :

Use overcurrent devices (e.g. fuses) according to the relevant 

standards in each string. Use gPV-fuses according to IEC 

60269-6. Observe the maximum permitted number of strings as 

indicated in the specifications provided by the respective string 

fuse manufacturer and the technical guidelines.

NOTE!

When installing different product versions, the lowest minimum 

permitted reverse current load capacity applies.

Inverters

Inverters with or without transformers may be used.

3 Installation

3.1 Safety and transport

  Leave modules in their original packaging until 

installation.

  Store the modules securely in cool and dry rooms. 

The packaging is not weatherproof.

  Inspect the packaging for damages.

  Contact the transport company regarding any 

damage to the packaging and follow their 

instructions.

  Follow any instructions on the packaging.

  Ensure that all personnel are aware of and adhere to 

accident-prevention and safety regulations.

  While working wear clean gloves.

§

GB

§

I

§

D

Danger! Risk of fatal injury due to electric shock!

  Do not install damaged modules.

  Inform your distributor of any damages immediately.

Warning! Fire Risk!

  Do not install modules indoors.

  Do not install modules on moving objects.

Summary of Contents for Q.PEAK DUO BLK-G10+ / HL Series

Page 1: ...Installation and operation manual Q PEAK DUO BLK G10 HL solar module series...

Page 2: ...The installer and solar module operator are responsible for compliance with all applicable statutory requirements and regulations The following regulations and standards must be upheld at all times d...

Page 3: ...ystem Your financial success depends on the fulfillment of these requirements Other applicable documents This installation manual is only valid in combination with the following technical information...

Page 4: ...tact corrosion Allows for stress free expansion and contraction due to temperature fluctuations Ensure that no additional forces are applied through the mounting system into the module except for the...

Page 5: ...ounting rails If connection cable runs between laminate and mounting it should be running at mounting rails position close to frame parts Modules bend under load Therefore sharp objects e g screws bal...

Page 6: ...ter into account when determining the maximum number of modules in the string Parallel Connection Modules may be damaged by the occurrence of reverse currents caused by module defects ground leaks or...

Page 7: ...nection cables or junction box Carry modules upright and horizontally as shown Note Module damage may occur Never step on modules Do not subject modules to any mechanical stress Do not allow any objec...

Page 8: ...electric arcs may result from the separation of a closed circuit These can result in life threatening injuries The danger increases when several modules are connected in series Please be aware of that...

Page 9: ...y only be performed by qualified and skilled personnel see page 3 Ensure correct polarity Use solar cables for the connection at the junction box outlet Only interconnect connectors of the same type a...

Page 10: ...n to avoid the use of grounding hardware of dissimilar metals which may lead to corrosion Option B Integrated grounding methods The Q CELLS modules can be bonded with the racking system using UL1703 o...

Page 11: ...t taking adequate security precautions Please commission a trade specialist NOTE Module surface damage may occur Remove snow and ice carefully without force e g with a very soft broom Do not scratch o...

Page 12: ...Installation manual solar modules Q PEAK DUO BLK G10 _HL_modules_series_2022 05_Rev01_NA HANWHA Q CELLS AMERICA INC 400 Spectrum Center Drive Suite 1400 Irvine CA 92618 USA EMAIL WEB TEL inquiry us q...

Reviews: