INSTALLATION AND OPERATION MANUAL B.LINE SOLAR MODULES G4 – HANWHA Q CELLS – EN

INSTALLATION AND OPERATION MANUAL B.LINE SOLAR MODULES G4 – HANWHA Q CELLS – EN

18

Protective Grounding

 

Ä

The modules must be grounded in accordance with the 
local statutory regulations.

Functional grounding

• 

When using an installation tilt of < 5° a functional 
grounding at the negative generator conncetion must 
be implemented.

 

Ä

Ensure that the difference of potential between the 
negative generator connection and the PE(N) of every 
MPP tracker of the respective inverters is 0 V.

 

Ä

Follow the directions of the inverter manufacturer.

 

Ä

Only use inverters which include lincensed grounding 
kits.

5       GROUNDING

DANGER!  
Risk of fatal injury due to electric shock!

 

Ä

Do not attempt to fix any problems yourself (e.g., 

glass cracks, damaged cables).

 

Ä

Please contact an installer or Q CELLS Technical 
Customer Service Department.

FAULTS AND DEFECTS

 

Ä

Do not disconnect modules by yourself.

 

Ä

Please contact an installer or Q CELLS Technical 
Customer Service Department.

 

Ä

Dispose of modules in accordance with the local disposal 
regulations.

7 DISPOSAL

 

Ä

Ensure that all necessary safety and 
functional tests have been carried out 
according to current industry standards.

NOTE

! Module damage may occur!

 

Ä

Ensure that the plug connections are 
secured away from any water-channelling 
surface.  

 

Ä

Integrate the system into the existing 
lightening protection system in 
accordance with the applicable local 
regulations.

WARNING

! Fire Risk!

 

Ä

Do not use light concentrators (e.g. 
mirrors or lenses).

 

Ä

Ensure that the cabling is not exposed 
and/or hanging and is protected from dirt 
and moisture.

4.4  After installation

ELECTRICAL CONNECTION

Summary of Contents for B.LINE G4

Page 1: ...Valid for Africa Asia Europe Latin America North America South America B LINE G4 SOLAR MODULES INSTALLATION AND OPERATION MANUAL...

Page 2: ...tions In particular the installer as well as the operator of a module is responsible for compliance with all applicable statutory requirements and regulations Unless otherwise specified by any laws or...

Page 3: ...ontext of contractual agreements or in the context of accepted guarantees Q CELLS accepts no other responsibility for the functionality and safety of the modules Please observe the instructions for an...

Page 4: ...es e g caused by vibrations twisting or expansion are generated on the module Ensure that the clamps and the mounting frame are compatible Clamp System Requirements Use customary clamps that satisfy t...

Page 5: ...ection cables of the junction box don t run between laminate and substructure Use M8 corrosion proof screws and washers min diameter 16 mm Specifications MODULE TYPE MOUNTING OPTION CLAMPING AREA1 MM...

Page 6: ...tors Sizing of control systems connected to the outlets of the solar modules Please follow the valid national guidelines for the installation of electrical systems Series Connection Connection of modu...

Page 7: ...the installation alone Only install undamaged modules and components Do not modify the module e g do not drill any additional holes 3 2 Preparation of installation 3 INSTALLATION NOTE Module damage ma...

Page 8: ...me caution Ensure that the modules are disconnected at the inverter prior to separation Be sure to observe the specified time intervals after switching off the inverter High voltage components need ti...

Page 9: ...due to electric shock Ensure that all electrical components are in a proper dry and safe condition Standard wiring with a return cable Inverter EN 4 3 Connection of modules 4 ELECTRICAL CONNECTION DA...

Page 10: ...ot attempt to fix any problems yourself e g glass cracks damaged cables Please contact an installer or Q CELLS Technical Customer Service Department 6 FAULTS AND DEFECTS Do not disconnect modules by y...

Page 11: ...alone or without taking adequate security precautions Please commission a trade specialist Clean the modules as follows NOTE Module surface damage may occur Remove snow and ice without force e g with...

Page 12: ...nenallee 17 21 06766 Bitterfeld Wolfen Germany TEL 49 0 34946699 23222 FAX 49 0 34946699 23000 EMAIL service q cells com WEB www q cells com Subject to change without notice Hanwha Q CELLS Installatio...

Reviews: